Amana PGB**C Скачать руководство пользователя страница 7

7

Table 3

Propane Gas Pipe Sizing

WARNING

To prevent death, serious personal in-
jury or property damage due to fire or
explosion caused by a propane gas leak,
install a gas detecting warning device.

If the propane gas unit is installed in an
excavated area or a confined space, a
warning device is required due to:

• Propane gas is heavier than air and

any leaking gas can settle in any low
areas or confined spaces.

• Propane gas odorant may fade, mak-

ing the gas undetectable except with
a warning device.

If the presence of gas is suspected, fol-
low the instructions on Page 2 of this
manual.

For satisfactory operation, propane gas pressure must
be 10 inch W.C. at the unit manifold with all gas appli-
ances in operation. Maintaining  proper gas pressure
depends on three main factors:

1. Vaporization rate, which depends on (a) tempera-

ture of the liquid, and (b)  wetted surface area of the
container or containers.

2. Proper pressure regulation.

3. Pressure drop in lines between regulators, and

between second stage regulator and the appliance.
Pipe size required will depend on length of pipe run
and total load of all appliances.

Complete information regarding tank sizing for vapor-
ization, recommended regulator settings and pipe siz-
ing is available from most regulator manufacturers and
propane gas suppliers.

Since propane gas will quickly dissolve white lead or
most standard commercial compounds, special pipe
dope must be used. Shellac base compounds resistant
to the actions of liquefied petroleum gases such as
Gasolac, Stalactic, Clyde’s or John Crane are satisfac-
tory.

Please refer to Figure  3  for typical propane gas instal-
lations.

Figure 3

Typical Propane Gas Piping

Содержание PGB**C

Страница 1: ...afety practices follow them The precautions listed in this Installation Manual should not supersede existing practices but should be considered as supplemental information ATTENTION INSTALLING PERSONN...

Страница 2: ...shut off turn off the manual gas control valve to the unit before shut ting off the electrical supply WARNING To prevent death personal injury or prop erty damage do not use this unit if any part of t...

Страница 3: ...rn air entering the unit must be between 50 F and 100 F Provisions must be made for adequate combustion and ventilation air in accordance with Section 5 3 Air for Combustion and Ventilation of the Nat...

Страница 4: ...ht bill or indemnity in lieu thereof c Original invoice or certified copy thereof showing trade and other discounts or reductions d Copy of the inspection report issued by carrier representative at th...

Страница 5: ...propane gas and for altitude adjust ments Piping IMPORTANT NOTE To avoid possible unsatisfactory operation or equipment damage due to under firing of equipment do not undersize the natural propane ga...

Страница 6: ...ring which may result in heat failure This unit and its shut off valve must be disconnected from the gas supply dur ing any pressure testing of that system at test pressures in excess of 1 2 PSIG 3 48...

Страница 7: ...er gas pressure depends on three main factors 1 Vaporization rate which depends on a tempera ture of the liquid and b wetted surface area of the container or containers 2 Proper pressure regulation 3...

Страница 8: ...re 5 V Electrical Wiring Locating The Thermostat Thermostat should be mounted 5 feet above the floor on a vibration free inside wall in a room or a hallway that has good air circulation Movement of ai...

Страница 9: ...sformer primary lead and induced draft blower mo tor leads as shown on the unit wiring diagram Heat Anticipator Setting The heat anticipator in the room thermostat must be correctly adjusted to obtain...

Страница 10: ...duct should be provided with an access panel This access should be large enough to inspect the air chamber downstream from the heat exchanger for any smoke or combustion gas leaks A cover should be ti...

Страница 11: ...ocated and other spaces of the building Turn on clothes dryers and any appliance not connected to the common venting system Turn on any exhaust fans such as range hoods and bathroom exhausts so they w...

Страница 12: ...ll Out Protector Figure 9 Rollout Protection IX Heating Sequence of Operations Normal Sequence of Operation Heating 1 Thermostat calls for heat The combustion blower is immediately energized 2 The pre...

Страница 13: ...Figure 12 With Power And Gas On 2 Put unit into heating cycle and turn on all other gas consuming appliances Figure 12 Measuring Inlet Gas Pressure Alternate Method Secondary Limit Control On the PGB...

Страница 14: ...per cubic foot as deter mined by Step 2 then Input 1000 x 3600 0 34 106 000 BTU per Hour NOTE BTU content of the gas should be obtained from the gas supplier This measured input must not be greater t...

Страница 15: ...ishing phases of construction on a new struc ture This type of use may result in pre mature failure of the unit due to extremely low return air temperatures and expo sure to very dirty atmospheres To...

Страница 16: ...d with water thoroughly dried and sprayed with a filter adhesive before being reinstalled Filter adhesives may be found at many hardware stores Permanent filters should last several years However shou...

Страница 17: ...sonal injury due to electrical shock do not remove any in ternal compartment covers or attempt any adjustment Contact a qualified ser vicer at once if an abnormal flame ap pearance should develop At l...

Страница 18: ...ng Flame Roll Out Switch Blower Motor Gas Orifice Blower Wheel Heat Exchanger Burner High Limit Switch Compressor Secondary Limit Condenser Coil Ignitor Flame Sensor Condenser Fan Blade Induced Draft...

Отзывы: