background image

14

secure flange to cabinet.

8.  Connect  drain  hose  to  the  uncapped  port  on  the 

RF000142 coupling, refer to page 19, Section entitled 

“Horizontal Installation with Left Side Down - Alternate” 

for drain connection details.

When  using  the  alternate  venting  location,  either  in  a 

horizontal left side down installation or a vertical installation 

using down – venting, the alternate combustion air opening 

can be used. A locating dimple is located on the right side of 

the furnace cabinet. The locating dimple is 1-7/8” measured 

from the front edge of the cabinet in line with the knock out. 

To use the alternate combustion air location:

1.  Remove screws and combustion air flange and gasket 

from cabinet.

2.   Insert the 3” cabinet plug from the drain bag assembly 

in the unused combustion air hole.

3.   Drill a pilot hole at the cabinet dimple (size dictated by 

knockout tool used).

4.   Use a knockout tool to create a 3” diameter hole.

5.   Secure the combustion air flange and gasket to the 

furnace cabinet using the self-tapping screws removed 

in step 1.

Pipe Termination

Products of combustion must always be vented outside. A 

vent pipe must never terminate in an attic, crawl space, or 

any other part of a dwelling. Follow the vent pipe & intake 

pipe  termination  requirements  listed  below  as  well  as  all 

applicable local, State and National codes.

 

All terminations (vent and/or intake) must be located at least 

12” above ground level or the anticipated snow level.

 

All  vent  terminations  (non-direct  and  direct  vent)  must 

terminate at least 3 feet above any forced air inlet located 

within 10 feet.

 

The vent termination of a non-direct vent application must 

terminate at least 4 feet below, 4 feet horizontally from, or 

1 foot above any door, window, or gravity air inlet into any 

building.

 

The  vent  termination  of  a  direct  vent  application  must 

terminate at least 12” from any opening through which flue 

gases may enter a building (door, window, or gravity air inlet).

 

The vent termination of vent pipe run vertically through a 

roof must terminate at least 12” above the roof line (or the 

anticipated snow level) and be at least 12” from any vertical 

wall (including any anticipated snow build up).

 

A vent termination shall not terminate over public walkways 

or over an area where condensate or vapor could create a 

nuisance or hazard or could be detrimental to the operation 

of regulators, relief valves, or other equipment.

 

The  combustion  air  intake  termination  of  a  direct  vent 

application should not terminate in an area which is frequently 

dusty or dirty. 

Vent  &  combustion  air  pipes  may  terminate  vertically 

through a roof, or horizontally through an outside wall. The 

combustion air intake and vent pipe terminations must be 

in the same atmospheric pressure zone. Vertical vent pipe 

terminations should be as shown in figure 14. The penetration 

of pipes through the roof must be sealed water tight with 

proper flashing such as is used with a plastic plumbing vent.

Horizontal vent pipe terminations should be as shown in the 

following figures. To secure the pipe passing through the wall 

and prohibit damage to piping connections, a coupling should 

be installed on either side of the wall and solvent cemented 

to a length of pipe connecting the two couplings. The length 

of pipe should be the wall thickness plus the depth of the 

socket fittings to be installed on the inside and outside of 

the wall. The wall penetration should be sealed with silicone 

caulking material.

12"

Non-Direct Vent

Vent/Flue Termination

No Terminations

 Above Walkway

12"

min.

4'

min.

Non-Direct Vent

Vent/Flue Termination

Direct Vent

Vent/Flue Termination

<10'

Forced Air

Inlet

Non-Direct Vent

&

Direct Vent

Vent/Flue Terminations

Grade or Highest

 Anticipated 

Snow Level

3' min.

12" min.

4' min.

12" min.

Vent Termination Clearances

Figure 12

Содержание MES96 U Series

Страница 1: ...R SERVICE PROCEDURES IF YOU SERVICE THIS UNIT YOU ASSUME RESPONSIBILITY FOR ANY INJURY OR PROPERTY DAMAGE WHICH MAY RESULT IN ADDITION IN JURISDICTIONS THAT REQUIRE ONE OR MORE LICENSES TO SERVICE THE...

Страница 2: ...Air Opening Upflow Models 24 Filters Read This Section Before Installing The Return Air Duct work 24 Upright Installations 25 Horizontal Installations 25 Drain Trap Priming 25 Furnace Operation 25 Ga...

Страница 3: ...me trap at time of installation may have a negative effect on combustion quality and pressure switch action WARNING FIRE OR EXPLOSION HAZARD Failue to follow safety warnings exactly could re sult in s...

Страница 4: ...d other discounts or reductions Copy of the inspection report issued by carrier s representative at the time damage is reported to carrier Electrostatic Discharge ESD Precautions NOTE Discharge your b...

Страница 5: ...n instructions provided and per local and national codes It must be installed indoors in a building constructed on site It must be part of a ducted system and not used in a free air delivery applicati...

Страница 6: ...eater POSSIBLE PROPERTY DAMAGE PERSONAL INJURY OR DEATH DUE TO FIRE EXPLOSION SMOKE SOOT CONDENSATION ELECTRICAL SHOCK OR CARBON MONOXIDE MAY RESULT FROM IMPROPER INSTALLATION REPAIR OPERATION OR MAIN...

Страница 7: ...Seal any unused openings in the venting system 2 Inspect the venting system for proper size and horizon tal pitch as required by the National Fuel Gas Code ANSI Z223 1 instructions Determine that ther...

Страница 8: ...ization can cause back drafting or improper combustion of gas fired appliances thereby exposing building occupantstogascombustionproductsthatcouldincludecarbon monoxide If this furnace is to be instal...

Страница 9: ...en marche alors que tous les autres appareils raccord s au syst me de ventila tion ne sont pas en marche 1 Sceller toutes les ouvertures inutilis es du syst me de ventilation 2 Inspecter le syst me d...

Страница 10: ...onally the appropriate downward piping slope must be maintained from the drain trap to the drain location Refer to Condensate Drain Trap and Lines for further details If the drain trap and drain line...

Страница 11: ...A masonry chimney may be used as a chase or passage way for approved venting materials providing the masonry chimney is not also being used to vent products of combustion Never common vent this appli...

Страница 12: ...Lengths shown in table 3 apply to single pipe two pipe installations In a two pipe installation do not add intake and vent pipe lengths together Both pipes would normally be equal in length if differ...

Страница 13: ...ng the horizontal alternate vent configuration you must use the RF000142 vent drain kit See Figures 10 11 follow steps below NOTE In the horizontal left installation position a means of condensate col...

Страница 14: ...rect vent application must terminate at least 12 from any opening through which flue gases may enter a building door window or gravity air inlet The vent termination of vent pipe run vertically throug...

Страница 15: ...HEIGHT DIFFERENCE 12 MIN TO ROOF OR HIGHEST ANTICIPATED SNOW LEVEL Figure 14 Vertical Termination STRAIGHT ELBOWS Figure 15 VENT FLUE TEE or 45 ELBOW TURNED DOWN or 90 ELBOW TURNED DOWN OPTIONAL 12 M...

Страница 16: ...swiththeexhaustventandairintaketerminations of a single unit If more than one direct vent furnace is to be installed horizontally through a common side wall maintain the clearances as in the following...

Страница 17: ...Drain Trap A condensing gas furnace achieves its high level of efficiency by extractingheatfromtheproductsofcombustiontothepointwhere condensation takes place The condensate must be collected in the f...

Страница 18: ...barbed end goes in the cabinet through the hole in the left side of the cabinet and secure with two field supplied 8 self tapping screws see Figure 24 2 Locate the long drain hose 3 and cut at B line...

Страница 19: ...rip leg port must be sealed to prevent flue gases from escaping Insert the rubber plug removed in step 6 into the unused elbow drain port Inserting a blunt tool such as a 3 16 Allen wrench into the ce...

Страница 20: ...ctrical circuit containing prop erly sized wire and fuse or circuit breaker The fuse or circuit breaker must be sized in accordance with the maximum overcurrent protection specified on the unit rating...

Страница 21: ...ERSONAL INJURY OR DEATH MAY OCCUR IF THE CORRECT CONVERSION KITS ARE NOT INSTALLED THE APPROPRIATE KITS MUST BE APPLIED TO ENSURE SAFE AND PROPER FURNACE OPERATION ALL CONVERSIONS MUST BE PERFORMED BY...

Страница 22: ...rning The orientation of the gas valve on the manifold must be maintained as shipped from the factory Maximum torque for the gas valve connection is 375 in lbs excessive over tightening may damage the...

Страница 23: ...ressures in excess of psig 3 48 kPa Isolate this unit from the gas supply piping system by closing its external manual gas shutoff valve before pressure testing supply piping system with test pressure...

Страница 24: ...e cor ners of the opening cut the sheet metal along the scribe lines to free the duct flanges Using the scribe line along the duct flange as a guide unfold the duct flanges around the perimeter of the...

Страница 25: ...MUST BE AS SPECIFIED ON THE UNIT RATING PLATE WITH ALL OTHER HOUSEHOLD GAS FIRED APPLIANCES OPERATING Furnace Startup 1 Closethemanualgasshutoffvalveexternaltothefurnace 2 Turn off the electrical powe...

Страница 26: ...ure regulator gas piping size etc and or consult with local gas utility 5 Turn OFF gas to furnace at the manual shutoff valve and disconnect manometer Reinstall plug and tighten as needed before turni...

Страница 27: ...essure cannot vary by more than 0 2 w c for Natural gas from the specified setting Consult your local gas supplier if additional input rate adjustment is required 4 Turn ON gas to and relight all othe...

Страница 28: ...ule performs internal checks LED will flash once at power up then remain on Integrated control module monitors safety circuits continuously Furnace awaits call from thermostat Heating Mode The normal...

Страница 29: ...osed electrically auto reset sensor This switch guards against the burner flames not being properly drawn into the heat exchanger Pressure Switches The pressure switches are normally open closed durin...

Страница 30: ...ol will return to lockout Refer to the Troubleshooting Chart for aid in determining the cause Field Test Mode Function When the SW1 button is pressed and held until the LED is blinking in AMBER more t...

Страница 31: ...ly Annually inspect the drain tubes drain trap and field sup plied drain line for proper condensate drainage Check drain system for hose connection tightness blockage and leaks Clean or repair as nece...

Страница 32: ...Open RED When an open limit is detected the control energizes the blower at cooling speed and the inducer at the RUN setting no CFH required Once the limit closes and the CFH is present the furnace r...

Страница 33: ...Press and hold the SW1 button for more than 5 seconds results in the display of this mode Releasing the Button during this indication will cause the Error History to be cleared The button must be rel...

Страница 34: ...CFM Rise CFM CFM CFM Red High Cool 3 1350 NA 1310 NA 1273 NA 1234 NA 1198 NA 1156 1117 1078 Blue Med Hi Heat 2 5 1247 29 1212 30 1167 31 1129 32 1087 33 1043 997 952 Brown Med Low 2 1151 31 1107 32 1...

Страница 35: ...ore servicing or installing this unit Multiple power sources may be present Failure to do so may cause property damage personal injury or death Wiring is subject to change Always refer to the wiring d...

Страница 36: ...a relatively short process and entitles you to additional warranty protection except that failure by California and Quebec residents to register their product does not diminsh their warranty rights Fo...

Отзывы: