BURNER BOX
This furnace must use indoor air for combustion. It is not a
direct vent furnace, and it cannot be installed as a direct
vent furnace. The burner box (on some models) is present
only to reduce the burner sound transmission.

AUXILIARY LIMIT CONTROL (FIGURE 35)
A manual reset limit is located on the blower side of the
blower deck, near the center. To access this auxiliary limit,
disconnect the electrical power and remove the blower
door. If the limit control opens, the air circulation blower will
run continuously. The diagnostic light will flash four times.
These symptoms are identical to a trip of the primary limit
control. See Section X,

 Abnormal Operation - Integrated

Ignition Control for diagnosis.

The auxiliary limit control is designed to prevent furnace
operation in case of main blower failure on horizontal and
counterflow installations. It may also open if the power
supply is interrupted while the furnace is firing.

The auxiliary limit control is suitable for both horizontal right
and horizontal left installations. Regardless of airflow direc-
tion, it does not need to be relocated.

WARNING

To prevent death, personal injury or property
damage due to fire, follow these directions
for the auxiliary limit control. If the auxiliary
limit control opens, it may be reset one time
only.

(SERVICER’S NOTE: If it becomes necessary to slide the
blower assembly out of the furnace, the auxiliary limit
control should be removed first. After the blower assembly
is reinstalled, the auxiliary limit must be reinstalled.)

Figure 35

Auxiliary Limit Control

ABNORMAL OPERATION - INTEGRATED IGNITION
CONTROL
The following presents the probable causes of question-
able furnace operation and how to fix them. Look through

the observation window in the blower access door and
make a note of the number of flashes in sequence between
pauses. Next, refer to the 

Diagnostic Signal Chart for an

interpretation of the signals and to this section for a descrip-
tion.

1. Internal Control Failure with Integrated Ignition

Control

An internal control failure occurs when the integrated
ignition control senses an internal problem and stops
the unit.

To solve this problem, replace the ignition control.

2. System Lockout

A system lockout occurs when the integrated ignition
control determines that a measurable combustion can-
not be established or maintained after three consecu-
tive tries (four, if flame is established then lost) to turn
on the furnace.

If a flame is not sensed during the first six seconds after
a gas valve has been energized, the ignition control will
internally turn off the gas. After 60 seconds, during
which time the induced draft blower purges the heat
exchanger, the ignitor will re-energize and preheat for
27 seconds.  The gas valve is then re-energized.  If a
flame is not sensed again in six seconds, the gas valve
will de-energize and another purge is performed.  The
ignition control will cycle the gas valve 

three times

before it determines it cannot establish measurable
combustion and enter a lockout state.  If a flame is
sensed but lost after 10 seconds, the control will cycle
four more times before locking out.  A lockout stops
ignition attempts and causes the air blower to run
continuously.  The diagnostic light will indicate either
condition with one short flash followed by a longer off.

The control can be reset and brought out of lockout
mode by turning the thermostat off and then back on. It
can also reset by turning off the electrical disconnect
switch to the furnace for 30 seconds.  The control will
reset after one hour.

IMPORTANT: If you have to frequently reset your furnace,
it means that a problem exists that should be corrected.
Contact a qualified servicer for further information.

3. Pressure Switch Stuck Closed

A sticking pressure switch can be caused by either a
faulty pressure switch, faulty wiring, a disconnected
hose, or a restricted intake or flue piping.  In the case
of  a  pressure switch sticking closed, the probable
cause is a faulty pressure switch or wiring.

If  the ignition control senses that the pressure switch
is closed and the induced draft blower is off, it will shut
down the unit until the fault is corrected. The light code
for this problem is two short flashes followed by a
longer pause.

4. Pressure Switch Stuck Open

A sticking open pressure switch can be caused by a
faulty pressure switch, a disconnected hose to the
pressure switch, a restricted air intake or flue piping, or
a faulty wiring.

If the ignition control senses that the induced draft
blower is energized but the pressure switch is not
closed, the control will keep the blower on and wait for
the switch to close. The diagnostic light code for this
problem is three short flashes followed by a pause.

Содержание GCI Series

Страница 1: ...hem TheprecautionslistedinthisInstallationManualshould not supersede existing practices but should be considered as supplemental information Amana Fayetteville TN 37334 A higher standard of comfort He...

Страница 2: ...il it today This will assist Amana in contacting you should any service or warranty information change in the future When filling in the registration card be sure to include the Model Manufacturing an...

Страница 3: ...to be set on a floor that may become wet or damp at times the furnace should be supported above the floor on a concrete base sized approximately 1 1 2 larger than the base of the furnace ADDITIONAL L...

Страница 4: ...al injury or property damage may occur if the furnace and other fuel burning appliances are not provided withenoughfreshairforpropercombustion and ventilation of flue gases Most homes require outside...

Страница 5: ...th doors are considered a part of the unconfined space 5 3 3 Equipment Located in Confined Spaces a All Air from Inside the Building The confined space shall be provided with two permanent openings co...

Страница 6: ...vers and grilles will have 60 75 percent free area Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment oper...

Страница 7: ...evious con ditions of use g If improper venting is observed during any of the above tests the common venting system must be corrected in accordance with the latest edition of the National Fuel Gas Cod...

Страница 8: ...n can occur inside masonry chimneys when a single fan assisted Category I appliance 80 AFUE furnace is vented without adequate dilution air Do not connect an 80 furnace to a masonry chimney unless the...

Страница 9: ...nd or Reline Fix 4 Cleanout free of debris Check 4 Reline Fix 4 Liner in good condition Check 5 Dilution air available Check 6 Complete the installation Check 7 Reline Fix 4 Reline Fix 4 No Yes Yes Ye...

Страница 10: ...f the tile liner Rusted pieces of the metallic liner reline the chimney Fix 4 CHECK 5 LINER CONDITION If a metal liner is present it must be checked It cannot be assumed that all existing metal liners...

Страница 11: ...relined Fix 4 FIX 1 LINER TERMINATION Any cap or roof assembly used with a liner must be approved by the liner manufacturer for such use The liner and cap roof assembly must then terminate above the...

Страница 12: ...s very tall The vent connectors used are very long or have a large number of elbows Local experience indicates that flexible liners installed without insulation are likely to have condensation problem...

Страница 13: ...irigid metallic tubing and metallic fittings Alumi num alloy tubing must not be used in exterior loca tions Listed gas appliance connectors used in accor dance with the terms of their listing must be...

Страница 14: ...ugh the left side of the furnace the installer must supply a straight pipe to reach the exterior of the furnace Figure 17 Figure 17 Gas Inlet Through Left Side Counterflow A ground joint union drip le...

Страница 15: ...ch WC at the furnace manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate depending on temperature of the liquid and wetted s...

Страница 16: ...ARNING To prevent death or personal injury due to electric shock disconnect electrical power before changing any electrical wiring CAUTION When servicing controls label all wires before disconnecting...

Страница 17: ...ow voltage wiring may enter through the right or left side of the furnace as viewed for an upflow installation top or bottom for a horizontal installation See Specification Sheet for hole locations Ru...

Страница 18: ...America Manual D A duct system must be installed in accordance with Stan dards of the National Board of Fire Underwriters for the Installation of Air Conditioning Warm Air Heating and Ventilating Syst...

Страница 19: ...For air delivery of 1800 CFM or higher use two side returns or one side return plus bottom return Guide dimples locate the side and bottom return cutout locations Use a straight edge to scribe lines...

Страница 20: ...er Continuous Light 1 Internal Control Failure 1 Flash 2 System Lockout 2 Flashes 3 Pressure Switch Stuck Closed 3 Flashes 4 Pressure Switch Stuck Open 4 Flashes 5 Open Limit Control 5 Flashes 6 Open...

Страница 21: ...anation of the pos sible problem On new installations or if a functional part such as the gas valve pressure switch or limit control has been replaced verify that the furnace is operating properly aft...

Страница 22: ...our screws This is intentional and not a manufacturing defect 3 As shipped the rollout protection device is located near the flame sensor end of the manifold assembly Re move and save the mounting scr...

Страница 23: ...ontrol determines that a measurable combustion can not be established or maintained after three consecu tive tries four if flame is established then lost to turn on the furnace If a flame is not sense...

Страница 24: ...ff the electrical power supply to the furnace 3 Set room thermostat to lowest possible setting 4 Remove the door on the front of the furnace Note This furnace is equipped with an ignition device to au...

Страница 25: ...r consult with local utility Figure 41 Measuring Inlet Gas Pressure Alternate Method CHECK MANIFOLD PRESSURE A tapped opening is provided in the gas valve to facilitate measurement of the manifold pre...

Страница 26: ...rnace as marked on the rating plate CHANGING BLOWER SPEEDS WARNING To avoid death or personal injury due to electricalshock turnoffpowertothefurnace before changing speed taps All furnaces ship at hig...

Страница 27: ...er location and procedures for removal cleaning and replacing them If help is needed contact the installer of the furnace or a qualified servicer AIR FILTER UPFLOW FURNACES If the filter is in the fur...

Страница 28: ...s are permanently lubricated No further lubrication is required INDUCED DRAFT BLOWER MOTOR The induced draft blower motor is permanently lubricated No further lubrication is required FLAME SENSOR INTE...

Страница 29: ...the burners 5 Use bottle brush to clean burner insert and inside of burner 6 Replace burners and burner retention bracket inspect the burner assembly for proper seating of burners in retention slots 7...

Отзывы: