5. Open Limit Control (Primary or Auxiliary)

An open limit control can be caused by a low condi-
tioned air flow due to dirty filter or resistance in duct
work, a faulty blower, a blower speed set too low, or a
faulty limit.

When the limit control opens, the induced draft and air
circulation blowers are turned on.  The induced draft
blower will remain on for the first fifteen seconds of this
period. The air circulation blower will remain on until
the limit control is closed.  The diagnostic light code for
this is four short flashes followed by a pause.

6. Open Rollout Control

An open rollout control is can be caused by insufficient
combustion air, a restricted flue passage, or a re-
stricted heat exchanger.

The opening of the rollout control signals the air circu-
lation blower and the induced draft blower to turn on.
The air circulation blower will remain on  until the limit
is manually reset. The induced draft blower will remain
on for the first fifteen seconds of this period. The
diagnostic light code for this is five short flashes
followed by a pause.

7. Flame Sensed with No Call for Heat

If the control senses a flame when the gas valve is de-
energized, it will run the air circulation blower and the
induced draft blower continuously. The diagnostic light
code for this is continuous light flashing. Probable
cause is miswiring.

OPERATING INSTRUCTIONS

1. Close the manual gas valve external to the furnace.

2. Turn off the electrical power supply to the furnace.

3. Set room thermostat to lowest possible setting.

4. Remove the door on the front of the furnace.

Note: This furnace is equipped with an ignition device to
automatically light the burners. Do not try to light burners
by hand.

5.

Honeywell Model VR8205, or White Rodgers Model
36E36, or Robertshaw Model 7222: Turn the gas
control knob clockwise 

 to the OFF position.

Note:  The knob should turn easily. Do not use exces-
sive force.

White Rodgers Model 36E22:  Push the switch to the
OFF position.

6. Wait five minutes to clear out any gas. Then smell for

gas, including near the floor.

7. If gas can be smelled following the five minute waiting

period in Step 6, immediately follow the instructions on
Page 2 of this manual. If you do not smell gas after five
minutes:

Honeywell Model VR8205, or White Rodgers Model
36E36, or Robertshaw Model 7222:  Turn the gas
control knob counterclockwise 

 to the ON posi-

tion.  The knob should turn easily. Do not use exces-
sive force.

White Rodgers Model 36E22:  Push the switch to the
ON position.

8. Replace the door on the front of the furnace.

9. Open the manual gas valve external to the furnace.

10. Turn on the electrical power supply to the furnace.

11. Set the room thermostat to the desired temperature.

NOTE: There is an approximate 20 second delay between
thermostat energizing and burner firing.

Gas Valves

Figure 36

Honeywell Model VR-8205

Figure 37

White Rodgers Model 36E36

Gas Control 
Valve Lever

(In ON Position)

INLET

OUTLET

Pressure Regulator
Adjustment (Under
Cap Screw)

Outlet Pressure Tap
(Side of Valve)

Inlet Pressure Tap

Figure 38

Robertshaw Model 7222

Содержание GCI Series

Страница 1: ...hem TheprecautionslistedinthisInstallationManualshould not supersede existing practices but should be considered as supplemental information Amana Fayetteville TN 37334 A higher standard of comfort He...

Страница 2: ...il it today This will assist Amana in contacting you should any service or warranty information change in the future When filling in the registration card be sure to include the Model Manufacturing an...

Страница 3: ...to be set on a floor that may become wet or damp at times the furnace should be supported above the floor on a concrete base sized approximately 1 1 2 larger than the base of the furnace ADDITIONAL L...

Страница 4: ...al injury or property damage may occur if the furnace and other fuel burning appliances are not provided withenoughfreshairforpropercombustion and ventilation of flue gases Most homes require outside...

Страница 5: ...th doors are considered a part of the unconfined space 5 3 3 Equipment Located in Confined Spaces a All Air from Inside the Building The confined space shall be provided with two permanent openings co...

Страница 6: ...vers and grilles will have 60 75 percent free area Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment oper...

Страница 7: ...evious con ditions of use g If improper venting is observed during any of the above tests the common venting system must be corrected in accordance with the latest edition of the National Fuel Gas Cod...

Страница 8: ...n can occur inside masonry chimneys when a single fan assisted Category I appliance 80 AFUE furnace is vented without adequate dilution air Do not connect an 80 furnace to a masonry chimney unless the...

Страница 9: ...nd or Reline Fix 4 Cleanout free of debris Check 4 Reline Fix 4 Liner in good condition Check 5 Dilution air available Check 6 Complete the installation Check 7 Reline Fix 4 Reline Fix 4 No Yes Yes Ye...

Страница 10: ...f the tile liner Rusted pieces of the metallic liner reline the chimney Fix 4 CHECK 5 LINER CONDITION If a metal liner is present it must be checked It cannot be assumed that all existing metal liners...

Страница 11: ...relined Fix 4 FIX 1 LINER TERMINATION Any cap or roof assembly used with a liner must be approved by the liner manufacturer for such use The liner and cap roof assembly must then terminate above the...

Страница 12: ...s very tall The vent connectors used are very long or have a large number of elbows Local experience indicates that flexible liners installed without insulation are likely to have condensation problem...

Страница 13: ...irigid metallic tubing and metallic fittings Alumi num alloy tubing must not be used in exterior loca tions Listed gas appliance connectors used in accor dance with the terms of their listing must be...

Страница 14: ...ugh the left side of the furnace the installer must supply a straight pipe to reach the exterior of the furnace Figure 17 Figure 17 Gas Inlet Through Left Side Counterflow A ground joint union drip le...

Страница 15: ...ch WC at the furnace manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate depending on temperature of the liquid and wetted s...

Страница 16: ...ARNING To prevent death or personal injury due to electric shock disconnect electrical power before changing any electrical wiring CAUTION When servicing controls label all wires before disconnecting...

Страница 17: ...ow voltage wiring may enter through the right or left side of the furnace as viewed for an upflow installation top or bottom for a horizontal installation See Specification Sheet for hole locations Ru...

Страница 18: ...America Manual D A duct system must be installed in accordance with Stan dards of the National Board of Fire Underwriters for the Installation of Air Conditioning Warm Air Heating and Ventilating Syst...

Страница 19: ...For air delivery of 1800 CFM or higher use two side returns or one side return plus bottom return Guide dimples locate the side and bottom return cutout locations Use a straight edge to scribe lines...

Страница 20: ...er Continuous Light 1 Internal Control Failure 1 Flash 2 System Lockout 2 Flashes 3 Pressure Switch Stuck Closed 3 Flashes 4 Pressure Switch Stuck Open 4 Flashes 5 Open Limit Control 5 Flashes 6 Open...

Страница 21: ...anation of the pos sible problem On new installations or if a functional part such as the gas valve pressure switch or limit control has been replaced verify that the furnace is operating properly aft...

Страница 22: ...our screws This is intentional and not a manufacturing defect 3 As shipped the rollout protection device is located near the flame sensor end of the manifold assembly Re move and save the mounting scr...

Страница 23: ...ontrol determines that a measurable combustion can not be established or maintained after three consecu tive tries four if flame is established then lost to turn on the furnace If a flame is not sense...

Страница 24: ...ff the electrical power supply to the furnace 3 Set room thermostat to lowest possible setting 4 Remove the door on the front of the furnace Note This furnace is equipped with an ignition device to au...

Страница 25: ...r consult with local utility Figure 41 Measuring Inlet Gas Pressure Alternate Method CHECK MANIFOLD PRESSURE A tapped opening is provided in the gas valve to facilitate measurement of the manifold pre...

Страница 26: ...rnace as marked on the rating plate CHANGING BLOWER SPEEDS WARNING To avoid death or personal injury due to electricalshock turnoffpowertothefurnace before changing speed taps All furnaces ship at hig...

Страница 27: ...er location and procedures for removal cleaning and replacing them If help is needed contact the installer of the furnace or a qualified servicer AIR FILTER UPFLOW FURNACES If the filter is in the fur...

Страница 28: ...s are permanently lubricated No further lubrication is required INDUCED DRAFT BLOWER MOTOR The induced draft blower motor is permanently lubricated No further lubrication is required FLAME SENSOR INTE...

Страница 29: ...the burners 5 Use bottle brush to clean burner insert and inside of burner 6 Replace burners and burner retention bracket inspect the burner assembly for proper seating of burners in retention slots 7...

Отзывы: