9. After a 15 second delay while flue products are purged

from the furnace heat exchanger, the induced draft
blower motor is de-energized.

10. The air circulation blower has an adjustable delay-off

timing of 60, 90, 120 or 180 seconds (starting from the
time the gas valve closes). This allows more heat from
the furnace to be transferred to the conditioned space.
After this time has elapsed, the blower will be de-
energized.

NORMAL COOLING SEQUENCE - INTEGRATED
IGNITION CONTROL
With the room thermostat in the FAN-AUTO position, the
indoor air circulation blower and outdoor condensing unit
will be energized when a call for cooling occurs. When the
call for cooling ends, the outdoor condensing unit will be de-
energized. The indoor air circulation blower will continue to
run for 45 seconds.

OTHER ITEMS

Constant Fan. During normal operation, the air circu-
lation blower will continually run at “Cooling” speed as
long as power is present at terminal G. If a call for heat
occurs, the blower will run at heating speed throughout
the heating cycle.

If a trip on high/auxiliary/rollout limit occurs, the air
circulation blower will run at “Heating” speed. Even if
power is present at terminal G, the blower will run at
heating speed until the limit closes.

X. Start-Up, Adjustments, and Checks

GENERAL OPERATION
This furnace is equipped with an electronic ignition device
to light the burners and an induced draft blower to exhaust
combustion products.

An interlock switch prevents furnace operation if the blower
door is not in place.  Keep the blower access doors in place
except for inspection and maintenance.

This furnace is also equipped with a self-diagnosing elec-
tronic control module. In the event a furnace component is
not operating properly, the control module LED  will  flash
on and off in a factory-programmed sequence, depending
on the problem encountered.  This light can be viewed
through the observation window in the blower access door.
Refer to the 

Diagnostic Signal Chart for further explanation

of the lighting codes and Section X, 

Abnormal Operation -

Integrated Ignition Control for an explanation of the pos-
sible problem.

On new installations, or if a functional part such as the gas
valve, pressure switch, or limit control has been replaced,
verify that the furnace is operating properly after servicing.

Check furnace operation as outlined in the following in-
structions. If any sparking, odors, or unusual noises are
encountered, shut off electrical power and recheck for
wiring errors, or obstructions in or near the blower motors.
Various shipping materials must be removed before the
blower motor is operated.

CAUTION

To prevent personal injury, use only blunt
pointed screws to attach the plenum to the
furnace and filter rack.  Screws should not
be placed where they could interfere with
filter replacement.

S iz e_ Air 

Dim ension "A",  

Inc he s

M inimum R e comme nded 

F ilter Siz e s,  Inches

F low

T hrow aw ay

Perm.

F iberglas s 

T hrow aw ay

P erma ne nt

045_30

15-1/2

8

(2) 16x 20x 1

(2) 10x 20x 1

070_30

15-1/2

8

(2) 16x 20x 1

(2) 10x 20x 1

070_40

19-3/4

8

(2) 20x 20x 1

(2) 10x 20x 1

090_30

14-1/4

13

(2) 16x 20x 1

(2) 15x 20x 1

090_50

24-1/4

13

(2) 25x 20x 1

(2) 15x 20x 1

115_40

17-3/4

11

(2) 20x 20x 1

(2) 15x 20x 1

115_50

23-1/2

11

(2) 25x 20x 1

(2) 15x 20x 1

140_50

23-1/2

11

(2) 25x 20x 1

(2) 15x 20x 1

Figure 30

Counterflow Furnaces

3. With the air flow direction arrow pointing toward the

furnace, insert the filters from the left side of the blower.
Starting with the right filter, push the filter into the
plenum so the bottom of the filter fits into the filter rack
and the upper edge rests against the side of the
plenum. Repeat with the left filter (Figure 29).

OTHER FILTER OPTIONS
External filter grilles can be used instead of the filter rack.

IX. Sequence of Operation (Integrated

Ignition Control)

Refer to Timing Charts for sequencing.

NORMAL HEATING SEQUENCE

1. Thermostat calls for heat.

2. The induced draft blower is energized.

3. The ignitor is energized and is allowed to preheat for 17

seconds.

4. The gas valve is energized delivering gas to the burners

and starting combustion.

5. The control checks for a signal from the flame sensor

within seven seconds after the gas valve is energized.
Gas will only continue to flow if a signal is present.

6. The control waits 30 seconds and turns on the air

circulation blower to the speed that was selected for
heating operation.

7. The thermostat is satisfied and opens.

8. The control de-energizes the gas valve.

Содержание GCI Series

Страница 1: ...hem TheprecautionslistedinthisInstallationManualshould not supersede existing practices but should be considered as supplemental information Amana Fayetteville TN 37334 A higher standard of comfort He...

Страница 2: ...il it today This will assist Amana in contacting you should any service or warranty information change in the future When filling in the registration card be sure to include the Model Manufacturing an...

Страница 3: ...to be set on a floor that may become wet or damp at times the furnace should be supported above the floor on a concrete base sized approximately 1 1 2 larger than the base of the furnace ADDITIONAL L...

Страница 4: ...al injury or property damage may occur if the furnace and other fuel burning appliances are not provided withenoughfreshairforpropercombustion and ventilation of flue gases Most homes require outside...

Страница 5: ...th doors are considered a part of the unconfined space 5 3 3 Equipment Located in Confined Spaces a All Air from Inside the Building The confined space shall be provided with two permanent openings co...

Страница 6: ...vers and grilles will have 60 75 percent free area Louvers and grilles shall be fixed in the open position or interlocked with the equipment so that they are opened automatically during equipment oper...

Страница 7: ...evious con ditions of use g If improper venting is observed during any of the above tests the common venting system must be corrected in accordance with the latest edition of the National Fuel Gas Cod...

Страница 8: ...n can occur inside masonry chimneys when a single fan assisted Category I appliance 80 AFUE furnace is vented without adequate dilution air Do not connect an 80 furnace to a masonry chimney unless the...

Страница 9: ...nd or Reline Fix 4 Cleanout free of debris Check 4 Reline Fix 4 Liner in good condition Check 5 Dilution air available Check 6 Complete the installation Check 7 Reline Fix 4 Reline Fix 4 No Yes Yes Ye...

Страница 10: ...f the tile liner Rusted pieces of the metallic liner reline the chimney Fix 4 CHECK 5 LINER CONDITION If a metal liner is present it must be checked It cannot be assumed that all existing metal liners...

Страница 11: ...relined Fix 4 FIX 1 LINER TERMINATION Any cap or roof assembly used with a liner must be approved by the liner manufacturer for such use The liner and cap roof assembly must then terminate above the...

Страница 12: ...s very tall The vent connectors used are very long or have a large number of elbows Local experience indicates that flexible liners installed without insulation are likely to have condensation problem...

Страница 13: ...irigid metallic tubing and metallic fittings Alumi num alloy tubing must not be used in exterior loca tions Listed gas appliance connectors used in accor dance with the terms of their listing must be...

Страница 14: ...ugh the left side of the furnace the installer must supply a straight pipe to reach the exterior of the furnace Figure 17 Figure 17 Gas Inlet Through Left Side Counterflow A ground joint union drip le...

Страница 15: ...ch WC at the furnace manifold with all gas appliances in operation Maintaining proper gas pressure depends on three main factors 1 Vaporization rate depending on temperature of the liquid and wetted s...

Страница 16: ...ARNING To prevent death or personal injury due to electric shock disconnect electrical power before changing any electrical wiring CAUTION When servicing controls label all wires before disconnecting...

Страница 17: ...ow voltage wiring may enter through the right or left side of the furnace as viewed for an upflow installation top or bottom for a horizontal installation See Specification Sheet for hole locations Ru...

Страница 18: ...America Manual D A duct system must be installed in accordance with Stan dards of the National Board of Fire Underwriters for the Installation of Air Conditioning Warm Air Heating and Ventilating Syst...

Страница 19: ...For air delivery of 1800 CFM or higher use two side returns or one side return plus bottom return Guide dimples locate the side and bottom return cutout locations Use a straight edge to scribe lines...

Страница 20: ...er Continuous Light 1 Internal Control Failure 1 Flash 2 System Lockout 2 Flashes 3 Pressure Switch Stuck Closed 3 Flashes 4 Pressure Switch Stuck Open 4 Flashes 5 Open Limit Control 5 Flashes 6 Open...

Страница 21: ...anation of the pos sible problem On new installations or if a functional part such as the gas valve pressure switch or limit control has been replaced verify that the furnace is operating properly aft...

Страница 22: ...our screws This is intentional and not a manufacturing defect 3 As shipped the rollout protection device is located near the flame sensor end of the manifold assembly Re move and save the mounting scr...

Страница 23: ...ontrol determines that a measurable combustion can not be established or maintained after three consecu tive tries four if flame is established then lost to turn on the furnace If a flame is not sense...

Страница 24: ...ff the electrical power supply to the furnace 3 Set room thermostat to lowest possible setting 4 Remove the door on the front of the furnace Note This furnace is equipped with an ignition device to au...

Страница 25: ...r consult with local utility Figure 41 Measuring Inlet Gas Pressure Alternate Method CHECK MANIFOLD PRESSURE A tapped opening is provided in the gas valve to facilitate measurement of the manifold pre...

Страница 26: ...rnace as marked on the rating plate CHANGING BLOWER SPEEDS WARNING To avoid death or personal injury due to electricalshock turnoffpowertothefurnace before changing speed taps All furnaces ship at hig...

Страница 27: ...er location and procedures for removal cleaning and replacing them If help is needed contact the installer of the furnace or a qualified servicer AIR FILTER UPFLOW FURNACES If the filter is in the fur...

Страница 28: ...s are permanently lubricated No further lubrication is required INDUCED DRAFT BLOWER MOTOR The induced draft blower motor is permanently lubricated No further lubrication is required FLAME SENSOR INTE...

Страница 29: ...the burners 5 Use bottle brush to clean burner insert and inside of burner 6 Replace burners and burner retention bracket inspect the burner assembly for proper seating of burners in retention slots 7...

Отзывы: