ERROR CODES AND ALARM STATUS

Unit Control Panel

The display shown below has four (4) digits. The left two digits indicate the error code (1 to 24), The On/Off icons above 

these two digits indicate the currents state of the error code. The right two digits show the history count (up to 99) of the 

associated error code. The display contains a maintenance icon (wrench) that will illuminate to indicate when the unit 

needs maintenance.

Error 

Code

Problem

Action

1

Front Panel Button Stuck For More Than 20 Seconds

Continue to Monitor for “OPEN” (Unstuck) switch. Do not process switch input. 

2

Input Voltage Out of Specification (103-127/187-253

Unit stops, open all relays until voltage is back within specs then resume 

operation. 

3

Indoor Temperature Sensor is Open or Shorted 

Unit defaults to 75°F in COOLING or 68°F in HEATING and will continue to 

operate. 

4

Indoor Coil Temperature Sensor is Open or Shorted

The unit’s control board defaults 40°F. It will override the sensor and the unit will 

continue to operate. 

5

Outdoor Coil Temperature Sensor is Open or Shorted

The unit defualts to 20°F, overriding the sensor. The unit will continue to operate. 

Using Elec Heat if available for HEATING. If not available, it will use HEAT PUMP 

if the outdoor temperature allows. 

6

Outdoor Coil > (greater than) 175°F

The unit will shut down for 5 minutes. Resume operation for 3 minutes. If test fails 

3 times, the severity is increased and the unit operation is locked out. 

7

Indoor Coil < (less than) 30°F for 2 consecutive 

minutes

The compressor will turn off and the High Fan speed will run. When coil temp 

reaches 45°F the unit will resume operation after lockout time. 

8

Unit Cycles > (greater than) 9 Times per hour

The unit will continue to operate and be monitored.

9

Unit Cycles < (less than) 3 Times per Hour

The unit will continue to operate and be monitored.

10

Room Freeze Protection 

Only use if Electric Heat is available. Run High Speed and Electric Heat until room 

temp reaches 46°F. The unit will display “FRZ” during operation. Logged Only. 

11

WallStat Problem or Connection Issue 

The unit will not operate. 

12

Not Applicable 

Not Applicable

13

High Pressure LImit Switch is Open 

If unit is cooling or heat pump is on, shut down compressor. Run high fan until 

switch closes, then resume operation. The third occurance in 1 hour locks unit out. 

Applicable to 24K unit only. 

14

Not Applicable 

Not Applicable

15

Heat Pump Error 

If indoor coil temperature is less than ambient temperature for 3 minutes the unit 

will use electric heat to satisfy the heating demand. 

16

Temperature Beyond Operating Limits 

Occurs if the ambient temperature range falls below 0°F or greater than 130°F. 

The error code will remain on until the temperature reaches the operating range 

and then the unit will return to normal operation. 

17

Equipment Doesn’t Meet Minimum Configuratio

The compressor must be enabled and have at least 2 fan speeds 

18

Not Applicable 

Not Applicable

19

Not Applicable

Not Applicable

20

Not Applicable

Not Applicable

21

Not Applicable

Not Applicable

22

Outdoor Coil Temperature < 30°F for 2 consecutive 

Minutes 

Unit will use electric heat to satisfy heating demands until the tempearture equals 

or exceeds 45°F. Applicable for Heat Pump models only. 

23

Frost Protection 

Unit will run active defrost for a minimum of 6 minutes when Heat Pump run time is 

greater than 60 minutes and outdoor coil temperature is 26°F or less. 

24

Not Applicable

Not Applicable

18

Содержание AVH09

Страница 1: ...e equipment specified in this manual only licensed personnel should servise the equipment Improper installation adjustment servicing or repair of the equipment specified in this manual or attempting t...

Страница 2: ...ntent of this manual the precautions listed here take precedence Important Note to the Servicer Read this manual and familiarize yourself with the specific items which must be adhered to before attemp...

Страница 3: ...Y Wire sizes are per NEC Recommended Branch Circuit Sizes Nameplate Maximum Circuit Breaker Size AWG Wiring Size 15A 14 20A 12 30A 10 AWG American Wire Gauge Single circuit from main box Based on 100...

Страница 4: ...the HIGH speed output to the GH terminal VTAC Required Minimum Clearances Building Exterior Unit Opening Requirements VTAC units must be installed on an outside wall Confined spaces and or covered are...

Страница 5: ...ation Overview and Dimensional Data Closet View NOTE It is recommened that 6 of clearance is provided on the side where the primary condensate is plumbed 3 4 Exterior Wall Adapter Cut Out Dimensions W...

Страница 6: ...1 8 26 1 8 CLOSET INSTALLATIONS 5 Access Door Cutout 27 Min 3 Required 23 1 8 23 1 8 30 5 8 Min Required Inside Closet Dimension 23 1 8 Access Door Cutout 27 23 1 8 23 1 8 30 5 8 Min Required Inside...

Страница 7: ...x 24 1 8 W x 30 3 8 H Large Chassis Unit Unit height 47 Filter 14 x 20 Small Chassis Unit Unit height 32 Filter 14 x 20 AVDK18 2401B drain pan required Sold Shipped Separately Architectural Grille AV...

Страница 8: ...ry any structural load A load bearing header must be built above the rough opening 1 Prepare the rough opening The rough opening should be lined with metal or wood The Wall Adapter will warp if sealed...

Страница 9: ...pilot holes on the interior of the inside Wall Adapter half Part B as show in Detail B Pilot holes should be located approximately 4 from the top and bottom of the inside Wall Adapter half on both th...

Страница 10: ...safety tether Final Wall Adapter and Architectural Louver Installation NOTE Ensure that the weather strip is undamaged and provides a continuous seal around the inner perimeter of the Wall Adapter App...

Страница 11: ...tem drain waste vent may result in staining of the outside wall 2 Insert the provided 3 4 nipple into the determined connection using field supplied Teflon tape or pip joint compound 3 With the slip e...

Страница 12: ...of the removed gasket The secondary overflow lip must extend into the plenum to prevent water leaks The pan should be mounted against the 3 4 flange of the plenum refer to view A Figure 2 Install Dra...

Страница 13: ...ndensate line as shown in Option 4 below as the drain line will come into contact with the factory installed isolators beneath the unit Figure 5 Option 1 Run condensate line to left of unit Option 3 R...

Страница 14: ...ERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DO NOT USE AN EXTENSION CORD WITH THIS UNIT CAUTION TO AVOID RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE USE ONLY COPPER CONDUCTORS CAUTION TO AVOID...

Страница 15: ...for a maximum friction rate of 3 water column taking into consideration all fittings registers and or diffusers NOTE Do not operate the unit without a supply duct attached The return air to the VTAC...

Страница 16: ...ation will stop NOTE The desk control system and switches must be field supplied Maximum Wire Length for Desk Control Switch AWG Wire Size Maximum Length ft 24 400 22 600 20 900 18 1500 16 2000 Auxili...

Страница 17: ...with outdoor ambient conditions greater than 110 F Chassis Operation Fresh Air Door The fresh air door is an intake system It is opened via a slide mechanism on the front of the chassis located just a...

Страница 18: ...hrough the filter and collect on the indoor ai These minor accumulations can be carefully vacuumed away with a brush attachment on a vacuum claner Care must be taken to avoid bending the aluminum finn...

Страница 19: ...ration after lockout time 8 Unit Cycles greater than 9 Times per hour The unit will continue to operate and be monitored 9 Unit Cycles less than 3 Times per Hour The unit will continue to operate and...

Страница 20: ...anization To obtain an authorized servicer contact your sales representative is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company L P H...

Отзывы: