WARNING

HIGH VOLTAGE

DISCONNECT ALL POWER BEFORE SERVICING 

OR INSTALLING THIS UNIT.  MULTIPLE POWER 

SOURCES MAY BE PRESENT.  FAILURE TO DO SO 

MAY CAUSE PROPERTY DAMAGE, PERSONAL 

INJURY OR DEATH.

Routine Maintenance

Performing Routine Maintenance

With the proper maintenance and care, your system will 

operate ecomomically and dependably. Maintenance 

can be accomplished easily by referring to the following 

directions. However, before performing any maintenance, 

see above stated 

WARNING

.

CAUTION

CUT / SEVER HAZARD

SOME EDGES MAY BE SHARP, USE GLOVES 

OR OTHER HAND PROTECTION WHEN  

HANDLING UNIT.

FAILURE TO DO SO CAN RESULT IN MINOR TO 

MODERATE PERSONAL INJURY.

Replace Air Filter

A dirty air filter reduces the efficiency of the  AC and 

allows lint and dirt to accumulate on the indoor-air coil. Lint 

and dirt on the indoor-air coil can damage your unit. 

The air filter should be replaced as it becomes dirt .

To replace the filter (chassis mounted return air filter

1. Slide the filter clear of the filter rail

2. Remove the filte .

3. Install new disposable filte .

NOTE: DO NOT OPERATE YOUR SYSTEM WITHOUT 

A FILTER IN PLACE OR BLOCK THE FRONT OF THE 

UNIT RETURN AIR OPENING.

To Remove the Chassis from the Closet: 

A. Switch the wall thermostat off.

B. Pull the Power Disconnect located in the front of the

chassis.

C. Disconnect the power coming into the unit from

the main breaker panel or the closet mounted

disconnect.

D. Disconnect the electrical connection.

E. Disconnect the duct work.

F. Slide the chassis out of the wall adapter.

G. Lift the chassis out of the utility closet.

Inspect and Clean Indoor-air Coil

Eventually, minor amounts of lint and dirt may pass 

through the filter and collect on the indoor-ai . These minor 

accumulations can be carefully vacuumed away with a 

brush attachment on a vacuum claner. Care must be taken 

to avoid bending the aluminum finns on the coil. Bent fin

should be straightened using a special fin tool avalable

from most HVAC supply depots.

Inspect Outdoor-Air (OA) Intake and Exhaust 

The unit’s outdoor-air intake and outdoor-air exhaust paths 

must remain clear. Check the OA exhaust frequently. Keep 

it free of all debris, snow, or ice. The OA intake should also 

be kept free of obstructions. Blocking the OA exhaust or 

OA intake opening will reduce the efficiency of your unit

and could damage it. 

Inspect and Clean Condensate Drain

The condensate drain must be routed to a suitable 

drainage area. Check the unit condensate drain 

periodically. Keep it free of anything that may block or 

impede the flow of condensate wate . If there is any 

accumulation of foreign matter in the drain pipe, it should 

be removed and cleaned. The entire drain line must be 

protected from freezing.

Warranty

All warranty service work must be done by an authorized 

servicer. See Product Warranty, and consult your dealer or 

contractor for details.

Electronic Control Error Code Diagnostics 

and Test Mode

Error Code Diagnostics

The VTAC electronic control continuously monitors the 

VTAC unit operation and will store error codes if certain 

conditions are witnessed. In some cases the unit may take 

action an shut the unit off until conditions are corrected.

To access the error code menu press the  

‘ENTER’

 button. 

If error codes are present they will be displayed. If multiple 

codes exist you can toggle between error codes using the 

‘SCROLL’

 button. To clear all codes press the 

 ‘ENTER’

 

and 

‘SCROLL’

 buttons for three  seconds  while in the error 

code mode. To exit without losing codes press the “

LOW 

FAN

” button. 

17

Содержание AVH09

Страница 1: ...e equipment specified in this manual only licensed personnel should servise the equipment Improper installation adjustment servicing or repair of the equipment specified in this manual or attempting t...

Страница 2: ...ntent of this manual the precautions listed here take precedence Important Note to the Servicer Read this manual and familiarize yourself with the specific items which must be adhered to before attemp...

Страница 3: ...Y Wire sizes are per NEC Recommended Branch Circuit Sizes Nameplate Maximum Circuit Breaker Size AWG Wiring Size 15A 14 20A 12 30A 10 AWG American Wire Gauge Single circuit from main box Based on 100...

Страница 4: ...the HIGH speed output to the GH terminal VTAC Required Minimum Clearances Building Exterior Unit Opening Requirements VTAC units must be installed on an outside wall Confined spaces and or covered are...

Страница 5: ...ation Overview and Dimensional Data Closet View NOTE It is recommened that 6 of clearance is provided on the side where the primary condensate is plumbed 3 4 Exterior Wall Adapter Cut Out Dimensions W...

Страница 6: ...1 8 26 1 8 CLOSET INSTALLATIONS 5 Access Door Cutout 27 Min 3 Required 23 1 8 23 1 8 30 5 8 Min Required Inside Closet Dimension 23 1 8 Access Door Cutout 27 23 1 8 23 1 8 30 5 8 Min Required Inside...

Страница 7: ...x 24 1 8 W x 30 3 8 H Large Chassis Unit Unit height 47 Filter 14 x 20 Small Chassis Unit Unit height 32 Filter 14 x 20 AVDK18 2401B drain pan required Sold Shipped Separately Architectural Grille AV...

Страница 8: ...ry any structural load A load bearing header must be built above the rough opening 1 Prepare the rough opening The rough opening should be lined with metal or wood The Wall Adapter will warp if sealed...

Страница 9: ...pilot holes on the interior of the inside Wall Adapter half Part B as show in Detail B Pilot holes should be located approximately 4 from the top and bottom of the inside Wall Adapter half on both th...

Страница 10: ...safety tether Final Wall Adapter and Architectural Louver Installation NOTE Ensure that the weather strip is undamaged and provides a continuous seal around the inner perimeter of the Wall Adapter App...

Страница 11: ...tem drain waste vent may result in staining of the outside wall 2 Insert the provided 3 4 nipple into the determined connection using field supplied Teflon tape or pip joint compound 3 With the slip e...

Страница 12: ...of the removed gasket The secondary overflow lip must extend into the plenum to prevent water leaks The pan should be mounted against the 3 4 flange of the plenum refer to view A Figure 2 Install Dra...

Страница 13: ...ndensate line as shown in Option 4 below as the drain line will come into contact with the factory installed isolators beneath the unit Figure 5 Option 1 Run condensate line to left of unit Option 3 R...

Страница 14: ...ERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DO NOT USE AN EXTENSION CORD WITH THIS UNIT CAUTION TO AVOID RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE USE ONLY COPPER CONDUCTORS CAUTION TO AVOID...

Страница 15: ...for a maximum friction rate of 3 water column taking into consideration all fittings registers and or diffusers NOTE Do not operate the unit without a supply duct attached The return air to the VTAC...

Страница 16: ...ation will stop NOTE The desk control system and switches must be field supplied Maximum Wire Length for Desk Control Switch AWG Wire Size Maximum Length ft 24 400 22 600 20 900 18 1500 16 2000 Auxili...

Страница 17: ...with outdoor ambient conditions greater than 110 F Chassis Operation Fresh Air Door The fresh air door is an intake system It is opened via a slide mechanism on the front of the chassis located just a...

Страница 18: ...hrough the filter and collect on the indoor ai These minor accumulations can be carefully vacuumed away with a brush attachment on a vacuum claner Care must be taken to avoid bending the aluminum finn...

Страница 19: ...ration after lockout time 8 Unit Cycles greater than 9 Times per hour The unit will continue to operate and be monitored 9 Unit Cycles less than 3 Times per Hour The unit will continue to operate and...

Страница 20: ...anization To obtain an authorized servicer contact your sales representative is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company L P H...

Отзывы: