Remote Thermostat and Low Voltage Control 

Connection

Remote Thermostat

All VTAC units are factory configured to be controlled

by using a single stage heat/cool remote wall mounted 

thermostat.  The thermostat may be auto or manual 

changeover as long as the control configuration matches

that of the VTAC unit.

To connect the wall mounted thermostat:

1. Pull the disconnect switch.

2. Unscrew and remove the control box panel.

3. Select which side to run your thermostat wire.

4. Run the wires through the side hole in the box to

reach the connection terminal wiring.

5. Make the connections, appropriately matching the

wires as shown in the wiring diagram.

6. Reattach the control box cover.

Front Desk Control Terminals

The VTAC has built-in provisions for connection to an 

external switch to control power to the unit.  The switch can 

be a central desk control system door switch.

For desk control operation, connect on side of the switch to 

the D1 terminal and the other to the D2 terminal. When the 

circuit is closed, unit operation will stop.

NOTE: The desk control system and switches must be 

field supplied.

Maximum Wire Length for Desk Control Switch

AWG Wire Size 

Maximum Length (ft.)

24

400

22

600

20

900

18

1500

16

2000

Auxiliary Fan Control

The VTAC also has the ability to control a 24VAC relay to 

activate an auxiliary or transfer fan. The outputs are F1 and 

F2 on the control board.

To connect the relay, simply wire one side of the relay to F1 

and the other side to F2.

NOTE: The relay and auxiliary fans must be field 

supplied.  The relay must be 24VAC @ 100mA or less.

Interface Definition 

Terminal Code

Wire Connection Function

C

Common Ground Terminal

GH

Call for High Fan 

GL

Call for Low Fan

B

Call for Heat Pump (Reversing Valve)

Y

Call for Compressor

W

Call for Heating (Electric)

R

24VAC to Wall Thermostat

NOTE: It is the installer’s responsibility to ensure that 

all control wiring connections are made in accordance 

with the installation instructions. Improper connection 

of the thermostat control wiring and/or tampering 

with the unit’s internal wiring can void the equipment 

warranty and may result in property damage, personal 

injury, or death.  Questions concerning proper 

connections to the unit should be directed to the 

factory.

15

Содержание AVH09

Страница 1: ...e equipment specified in this manual only licensed personnel should servise the equipment Improper installation adjustment servicing or repair of the equipment specified in this manual or attempting t...

Страница 2: ...ntent of this manual the precautions listed here take precedence Important Note to the Servicer Read this manual and familiarize yourself with the specific items which must be adhered to before attemp...

Страница 3: ...Y Wire sizes are per NEC Recommended Branch Circuit Sizes Nameplate Maximum Circuit Breaker Size AWG Wiring Size 15A 14 20A 12 30A 10 AWG American Wire Gauge Single circuit from main box Based on 100...

Страница 4: ...the HIGH speed output to the GH terminal VTAC Required Minimum Clearances Building Exterior Unit Opening Requirements VTAC units must be installed on an outside wall Confined spaces and or covered are...

Страница 5: ...ation Overview and Dimensional Data Closet View NOTE It is recommened that 6 of clearance is provided on the side where the primary condensate is plumbed 3 4 Exterior Wall Adapter Cut Out Dimensions W...

Страница 6: ...1 8 26 1 8 CLOSET INSTALLATIONS 5 Access Door Cutout 27 Min 3 Required 23 1 8 23 1 8 30 5 8 Min Required Inside Closet Dimension 23 1 8 Access Door Cutout 27 23 1 8 23 1 8 30 5 8 Min Required Inside...

Страница 7: ...x 24 1 8 W x 30 3 8 H Large Chassis Unit Unit height 47 Filter 14 x 20 Small Chassis Unit Unit height 32 Filter 14 x 20 AVDK18 2401B drain pan required Sold Shipped Separately Architectural Grille AV...

Страница 8: ...ry any structural load A load bearing header must be built above the rough opening 1 Prepare the rough opening The rough opening should be lined with metal or wood The Wall Adapter will warp if sealed...

Страница 9: ...pilot holes on the interior of the inside Wall Adapter half Part B as show in Detail B Pilot holes should be located approximately 4 from the top and bottom of the inside Wall Adapter half on both th...

Страница 10: ...safety tether Final Wall Adapter and Architectural Louver Installation NOTE Ensure that the weather strip is undamaged and provides a continuous seal around the inner perimeter of the Wall Adapter App...

Страница 11: ...tem drain waste vent may result in staining of the outside wall 2 Insert the provided 3 4 nipple into the determined connection using field supplied Teflon tape or pip joint compound 3 With the slip e...

Страница 12: ...of the removed gasket The secondary overflow lip must extend into the plenum to prevent water leaks The pan should be mounted against the 3 4 flange of the plenum refer to view A Figure 2 Install Dra...

Страница 13: ...ndensate line as shown in Option 4 below as the drain line will come into contact with the factory installed isolators beneath the unit Figure 5 Option 1 Run condensate line to left of unit Option 3 R...

Страница 14: ...ERSONAL INJURY OR DEATH DUE TO ELECTRICAL SHOCK DO NOT USE AN EXTENSION CORD WITH THIS UNIT CAUTION TO AVOID RISK OF PROPERTY DAMAGE PERSONAL INJURY OR FIRE USE ONLY COPPER CONDUCTORS CAUTION TO AVOID...

Страница 15: ...for a maximum friction rate of 3 water column taking into consideration all fittings registers and or diffusers NOTE Do not operate the unit without a supply duct attached The return air to the VTAC...

Страница 16: ...ation will stop NOTE The desk control system and switches must be field supplied Maximum Wire Length for Desk Control Switch AWG Wire Size Maximum Length ft 24 400 22 600 20 900 18 1500 16 2000 Auxili...

Страница 17: ...with outdoor ambient conditions greater than 110 F Chassis Operation Fresh Air Door The fresh air door is an intake system It is opened via a slide mechanism on the front of the chassis located just a...

Страница 18: ...hrough the filter and collect on the indoor ai These minor accumulations can be carefully vacuumed away with a brush attachment on a vacuum claner Care must be taken to avoid bending the aluminum finn...

Страница 19: ...ration after lockout time 8 Unit Cycles greater than 9 Times per hour The unit will continue to operate and be monitored 9 Unit Cycles less than 3 Times per Hour The unit will continue to operate and...

Страница 20: ...anization To obtain an authorized servicer contact your sales representative is a registered trademark of Maytag Corporation or its related companies and is used under license to Goodman Company L P H...

Отзывы: