background image

10

it  will  be  affected  by  drafts,  hot  or  cold  water  pipes  or  air 

ducts in walls, radiant heat from fireplace, lamps, the sun, 

television, etc. Consult the Instruction Sheet packaged with 

thermostat for mounting instructions.
All units have two stages of heating and two stages of me-

chanical cooling. Units which will have economizers may 

use thermostats with two or three stages of cooling. All units 

can use single stage or multi-stage thermostats. Refer to 

figures later in this section for wiring.

WARNING

To avoid personal injury, electrical shock or death, 

disconnect electrical power before servicing or changing 

any electrical wiring.

The units are designed for operation on 60 hertz current and 

at voltages as shown on the rating plate. All internal wiring 

in the unit is complete. It is necessary to bring in the power 

supply to the contactor as shown on the unit wiring diagram 

which is supplied with each unit. The low voltage wiring must 

be connected between the unit control panel and the room 

thermostat. 

R C W1W2 G Y1 Y2

R

Y2

C

Y1

W1

G

W2

I

ntegrated

Control Module

Thermostat

Two-Stage Heating

with

Two-Stage Cooling

Two-Stage Heating with Two-Stage Cooling

Thermostat Diagram

5 MINUTE DELAY

PERIOD WITH

JUMPER IN THIS

POSITION

10 MINUTE DELAY

PERIOD WITH

JUMPER IN THIS

POSITION

Two-Stage Heating (timed) and Two-Stage Cooling (timed) with Single 

Stage Thermostat Diagram 

Single Stage Thermostat

To use a single stage thermostat, move jumper located to the 

left of the terminal strip labeled “Stage Delay” from NONE to 

“5” or “10” minutes. This selection will cause the control to 

run on low stage for the selected time (5 or 10 minutes) then 

shift to HIGH STAGE. This option controls both cooling and 

heating modes. If the jumper is not moved, only low-stage 

cool and low-stage heat will operate.

Alternate Fan Only Speed

The APG16 models are equipped with ECM variable speed 

motors. Two FAN ONLY speeds are possible with these mo-

tors. To utilize the LOW HEAT blower speed for FAN ONLY 

operation, connect the wire from the thermostat’s G terminal 

to the ignition control board’s G terminal.  

To utilize the alternate FAN ONLY speed, connect the wire 

from  the  thermostat’s  G  terminal  to  the  unstripped  green 

wire in the control box. (DO NOT connect the thermostat’s 

G terminal to the ignition control’s G terminal.) This alternate 

FAN ONLY blower speed is approximately 75% of the HIGH 

COOL speed.   

24 Volt Dehumidistat Wiring

WARNING

High Voltage!

Disconnect ALL power before servicing or 

installing thus unit. Multiple power sources may 

be present. Failure to do so may cause property 

damage, personal injury, or death.

The optional usage of a dehumidistat allows the unit’s cir

-

culator blower to operate at a slightly lower speed (approx-

imately 80% of desired cooling speed) during a combined 

thermostat call for cooling and dehumidistat call for dehu-

midification. This can be done through an independent de

-

humidistat. This lower blower speed enhances dehumidi-

fication  of  the  conditioned  air  as  it  passes  through  the  air 

conditioning coil. For proper function, a dehumidistat applied 

to this package unit must operate on 24 VAC and utilize a 

switch which opens on humidity rise. Refer to the unit wiring 

diagram for additional wiring details.
To install/connect a dehumidistat:

1.  Turn OFF power to unit.

2.  To enable the dehumidify function, locate the ECM 

blower  motor  interface  module  in  the  unit’s  blower 

section. Locate the jumper label “HUM” on the interface 

module.  Cut  the  jumper  to  enable  dehumidification 

(see ECM Blower Motor Interface Module).

3.  Secure the dehumidistat neutral wire (typically the 

white lead) to the gray, unstripped wire in the unit’s 

control box.

4.  Secure the dehumidistat low voltage wire (typically 

the black lead) to the ignition control’s “R”  terminal.

5.  Secure the dehumidistat ground wire (typically the 

green lead) to the ground  screw to the unit’s sheet 

metal control box.

NOTE

: Ground wire may not be present on all 

dehumidistats.

6.  Turn ON power to unit.

Содержание APG 16 M Series

Страница 1: ...anada shown below ANSI Z21 47 CSA 2 3 Gas Fired Central Furnaces IMPORTANT This product has been designed and manufactured to meet ENERGY STAR criteria for energy efficiency when matched with appropri...

Страница 2: ...bcooling 18 TROUBLESHOOTING 18 Ignition Control Error Codes 18 Fault Recall 18 Abnormal Operation Heating 18 Internal Control Failure 18 External Lockout 18 Pressure Switch Stuck Open 19 Pressure Swit...

Страница 3: ...for use with this unit Serious property damage personal injury reduced unit performance and or hazardous conditions may result from the use of such non approved devices WARNING Heating unit should not...

Страница 4: ...hen Tested As Outlined Above Return Doors Windows Exhaust Fans Fireplace Dampers And Any Other Gas fired Burning Appliance To Their Previous Conditions Of Use RISQUE D INTOXICATION AU MONOXYDE DE CARB...

Страница 5: ...0259 216 El mon xido de carbono puede causar enfermedades severas como da o cerebral permanente muerte Las emisiones de mon xido de carbono pueden circular a trav s del aparato cuando se opera en cual...

Страница 6: ...maintained The combustion air inlet and flue outlet hoods on the unit must never be obstructed If used do not allow the economizer manual fresh air damper motorized fresh air damper to become blocked...

Страница 7: ...the Installation Manual provided with the LP kit for conversion from natural gas to propane gas Natural Min 5 0 W C Max 10 0 W C Propane Min 11 0 W C Max 13 0 W C INLET GAS PRESSURE Inlet Gas Pressure...

Страница 8: ...metallic fittings Aluminum alloy tubing must not be used in exterior locations Listedgasapplianceconnectorsusedinaccordance with the terms of their listing that are completely in the same room as the...

Страница 9: ...0 161 365 679 1 149 1 769 961 2 009 150 130 293 546 923 1 421 772 1 613 200 111 251 467 790 1 216 660 1 381 250 90 222 414 700 1 078 585 1 224 300 89 201 378 634 976 530 1 109 350 82 185 345 584 898 4...

Страница 10: ...Two FAN ONLY speeds are possible with these mo tors To utilize the LOW HEAT blower speed for FAN ONLY operation connect the wire from the thermostat s G terminal to the ignition control board s G term...

Страница 11: ...r HACR circuit breaker that is in excess of the circuit ampacity but less than or equal to the maximum overcurrent protection device DO NOT EXCEED THE MAXIMUM OVERCURRENT DEVICE SIZE SHOWN ON UNIT DAT...

Страница 12: ...aintained The supply duct should be provided with an access panel large enough to inspect the air chamber downstream of the heat exchanger A cover should be tightly attached to prevent air leaks For d...

Страница 13: ...indoor blower is de energized NOTE A 180 second anti short cycle is integral to the con trol and prevents recycling of the compressor Fan Only 1 Thermostat calls for FAN ONLY by energizing G 2 The ind...

Страница 14: ...t 3 Set the room thermostat to its lowest possible setting 4 Remove the heat exchanger door on the side of the unit by removing screws 5 This unit is equipped with an ignition device which automatical...

Страница 15: ...3 w c 2 0 w c High Stage 3 2 3 8 w c 3 5 w c Low Stage 5 7 6 3 w c 6 0 w c High Stage 9 7 10 3 w c 10 0 w c Gas Manifold Gas Pressure Natural Propane Manifold Gas Pressure 8 Remove regulator cover sc...

Страница 16: ...uct at the inlet of the unit Negative Pressure Total External Static 2 Measure the Static pressure of the supply duct Positive Pressure 3 Add the two readings together NOTE Both readings may be taken...

Страница 17: ...n the unit 7 If cooling and or air circulation will be desired turn ON the electrical power Cooling Startup NOTE The outdoor temperature must be 60 F or higher before making adjustments to charge Comp...

Страница 18: ...ing to heating is desired 3 Set the room thermostat to the desired temperature TROUBLESHOOTING Ignition Control Error Codes The following presents probable causes of questionable unit operation Refer...

Страница 19: ...tem peratures This can be caused by a dirty filter excessive duct static insufficient air flow or a faulty limit Check filters total external duct static blower motor blower motor speed tap see wirin...

Страница 20: ...as frequently as necessary to keep the finned areas free of lint hair and debris Condenser Evaporator and Induced Draft Motors Bearings on the air circulating blower motor condenser mo tor and the com...

Страница 21: ...at the thermostat Wait a few minutes since any dislodged dust will alter the normal flame appearance Flames should be predominantly blue and directed into the tubes They should not be yellow They shou...

Страница 22: ...uck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas Valve Closed 6 Flashes Short Cycle Compressor Delay Cooling Only Amber Light Signal Refer to Abnormal Heating or C...

Страница 23: ...120 150 180 Circulator Blower HIGH OFF Seconds Gas Valve Igniter Induced Draft Blower Thermostat 0 15 22 27 52 0 30 LOW HIGH OFF LOW OFF ON HIGH OFF LOW HIGH OFF LOW Circulator Blower Compressor Outd...

Страница 24: ...PPLY ENTRANCE CONDENSATE DRAIN CONNECTION 3 4 NPT FEMALE 16 1 8 19 1 8 EVAPORATOR CONTROL PANEL ACCESS PANEL 4 3 4 B 7 15 16 16 B 5 1 2 1 3 8 16 2 3 4 A 18 7 16 FLUE EXHAUST 51 47 BLOWER ACCESS PANEL...

Страница 25: ...HES CHECK FOR SHORTS IN FLAME SENSOR WIRING CHECK GAS VALVE CHECK ROLLOUT LIMIT SW CHECK AUXILIARY LIMIT SW CHECK MAIN LIMIT SWITCH CHECK WIRING FOR SHORTS CHECK PRESSURE SWITCH PRESSURE SWITCH CLOSED...

Страница 26: ...on 4 Ton Min Filter Size 1 20 x 25 x1 1 25 x 25 x 1 1 25 x 25 x 1 2 20 x 20 x 1 2 20 x 20 x 1 Clearance in accordance with local installation codes the requirements of the gas supplier and the manufac...

Страница 27: ...X Not recommended for heating application NOTE The shaded area indicates ranges in excess of maximum external static pressure allowable when heating For satisfactory operation external static pressure...

Страница 28: ...28 CFM OUTPUT AND DIP SWITCH SETTINGS...

Страница 29: ...motor is hermetically sealed and does not require additional oiling Annual Inspection Qualified Servicer Only Your package unit should be inspected by a qualified install er or service agency at leas...

Страница 30: ...Type NG Natural Gas LP Liquid Propane Residential Package Outdoor Section ELECTRICAL Supply Voltage Measure L1 and L2 Voltage L1 L2 Compressor Amps Condenser Fan Amps PRESSURES TEMPERATURES Suction Ci...

Страница 31: ...31 THIS PAGE IS LEFT INTENTIONALLY BLANK...

Страница 32: ...in all product comments Please fill out the feedback form on one of the following links Amana Brand Products http www amana hac com about us contact us You can also scan the QR code on the right for...

Отзывы: