Programming: BP Battery Protection
Programming / Commissioning Your System - The Smart BP-100 Battery Protection
1. Supply 12V power to the BP (+ to IN post, - to GND pin).
2. Open VictronConnect and select the Battery Protect.
3. The first screen has a switch to manually toggle the relay.
4. Click the gear in the top right to enter Settings.
5. Select “user defined” from the Preset menu.
6. Enter the following values:
Shut down: 10.5v
Restart: 11.5v
7. Mode: Leave on “B”
8. Alarm output: Select ”Relay” from the menu.
2. Select BatteryProtect from VictronConnect
5. Select “User defined” from the Preset
menu
7. Mode should be set to “Relay mode”
8. Alarm output: Select “Relay”
4. Select the gear icon
NOTE:
These setting were chosen on the conservative side, but can be adjusted depending on your needs. Do not lower the shut down voltage until you are
very familiar with your system, since dropping below 12v may result in battery degradation.
If your battery protect shuts down your loads, it’s important you recharge your batteries up to a full charge as soon as possible.
To Battery
BP100 Detail
NOTE: Remove
this existing wire.
To Breaker
To Shunt or Chassis Ground