background image

Supervisor 3000 Installation Instructions

Page 20 

For assistance: [email protected]  +1 (909) 591-8431 PUD3628R1-2

I/O Control Board (13-0328 Rev. F)

Fig. 20

Fig. 20A

Master Cabinet

I/O Control Board 

(13-0328 Rev. F)

)

LEGEND

ITEM

NAME

J1

Input Terminals

J2

Output Terminals

JP1

RS485 Termination Resistor

JP2

RS485 Termination Resistor

JP3

Fire Alarm Jumper (N.O. - N.C.)

S1

Entry Side Open Test Button

S2

Entry Side Reject Test Button

S3

Previous Sensor Group

S4

Next Sensor Group

S5

Exit Side Open Test Button

S6

Exit Side Reject Test Button

Signal Inputs and Outputs 

 

To / From Access Control System 

Inputs

Signal inputs from outside systems 

are wired into the SU3000’s I/O control 

board. There are two types of input 

signals, momentary dry contacts (MDC) 

and sustained dry contacts (SDC). All 

input signals must be normally open 

(N.O.), voltage-free, dry contacts, with 

the exception of the fire alarm input, 

which can be configured (via jumper 

on the I/O control board) to accept 

either a normally open or normally 

closed (N.C.) sustained contact. MDC’s 

must be at least 100ms in duration to 

register. While the SU3000 can accept 

signals up to 2 seconds in duration, 

the suggested MDC input duration 

is 1 second or less to support rapid 

throughput in high volume applications.

Factory default Fire Alarm jumper 

setting is normally open (N.O.).

Outputs

Signal outputs are available from the 

SU3000’s I/O control board. Outputs 

are normally open, voltage-free, 

momentary dry contacts. The output 

signal length is 300ms in duration. 

Inability to Provide Specified Inputs

If the access control system does not 

have dry contact outputs, isolation 

relays should be used. NEVER connect 

signal lines containing voltage directly 

to the I/O control board.

NOTES

Содержание SU3000

Страница 1: ...Inc 12660 Colony Street Chino CA 91710 Phone 1 909 591 8431 Fax 1 909 628 1403 support alvaradomfg com www alvaradomfg com PUD3628R1 2 SUPERVISOR 3000 SU3000 Optical Turnstile with Motorized Barrier...

Страница 2: ...t 14 Baseplate Assembly Optional 15 Installation Instructions 16 Anchoring the Turnstile 16 Internal Card Reader Installation 18 Wiring Instructions 19 Primary Power 19 Crossover Cable 19 I O Control...

Страница 3: ...Alvarado parts to repair a damaged turnstile Closely follow the handling instructions for moving or lifting the turnstile during installation Power off the turnstile before connecting or disconnectin...

Страница 4: ...er Cabinets are used to create additional lanes for multi lane configurations Each additional lane includes the parts below Single Lane Parts List Center Cabinet Parts List Per Center Cabinet Concrete...

Страница 5: ...status display that communicates lane status to the user A card reader is normally installed during installation underneath the lid below the user status display Center cabinets contain both master an...

Страница 6: ...enabled Running Ethernet cabling to the SU3000 provides a number of benefits 1 It allows implementation of Alvarado s TCP IP control and monitoring software 2 It allows easy implementation of SU3000...

Страница 7: ...w Footprint Drawing Fig 3 28 Single Lane Plan Elevation Footprint Drawing For ease of installation and servicing Alvarado recommends a minimum of 6 of space between the cabinets and adjacent walls or...

Страница 8: ...lan View Footprint Drawing Fig 4 36 Single Lane Plan Elevation Footprint Drawing 0 2X 1 3 32 2X 1 4 35 1 8 44 2X 1 3 32 2X 1 4 35 1 8 44 0 2 51 7 7 196 16 7 424 2X 19 9 506 2 51 7 7 196 16 7 424 2X 19...

Страница 9: ...ggests the use of surge protection on the high voltage power line to further protect electronics Fig 5 SU3000 Conduit Lines For multi lane conduit requirements refer to Appendix B on Page 33 NOTE Seal...

Страница 10: ...inning the installation Card readers or other physical access devices may be installed in the reveal under the lid on either or both right hand sides of the lane Card readers physical access devices a...

Страница 11: ...panel with the key provided To remove slide each unlocked end panel up slightly and then pull it away from the cabinet See Figure 6 for more details When moving cabinets into place DO NOT attempt to...

Страница 12: ...7 for more details Removing a Side Panel Slide Across Pins Lift to Free Side Panel from Pins FIGURE 4 3 0 2 Removing the Side Pan Removing a Side Panel Slide Across Pins Lift to Fr Panel fro FIGURE 4...

Страница 13: ...ws under the lid the thumbscrews are located at the end of the cabinet two on each end there is a total of 4 thumbscrews and remove the lid by lifting the lid carefully off the turnstile See Figure 8...

Страница 14: ...Secondary Controller Side Main Controller Side Secondary Controller Side Main Controller Side Secondary Controller Side Main Controller Side INCORRECT INCORRECT Main Controller Side Secondary Control...

Страница 15: ...ntrols must be accessible and provided to the turnstile The side plate on the baseplate must be removed in order to provide external power data or the side plate may be drilled with appropriate holes...

Страница 16: ...optimum performance Use the following procedure to square each cabinet with respect to the floor and other cabinets A Measure the distance from the inside wall of one cabinet to the inside wall of th...

Страница 17: ...of the anchor must be inserted into the hole first Use a hammer to tap the anchors into place if needed Ensure that the anchors are flush with the concrete floor 6 If not already done pull all wires A...

Страница 18: ...Figure 17 4 Install the card reader per manufacturer s instructions If the distance between the installed card reader and top channel lid exceeds the read range of the card reader shims may be used to...

Страница 19: ...des The primary wiring lines for 110VAC and 220VAC consist of the following Terminal 110V 220V Ground Green Green Yellow Neutral White Blue Line Black Brown 1 Locate the pre installed power terminal b...

Страница 20: ...dry contacts SDC All input signals must be normally open N O voltage free dry contacts with the exception of the fire alarm input which can be configured via jumper on the I O control board to accept...

Страница 21: ...for one authorized passage until passage occurs or timeout 10 EXTALRX Unauthorized Presence Exit MDC An output occurs when there is entry into the lane area from the exit direction without authorizati...

Страница 22: ...Key Control If this option has been ordered for your turnstiles two 3 position key switches are installed on the turnstile Turning the key to one of the three positions allows each turnstile direction...

Страница 23: ...ate the ENTPAS and GND terminals 2 Using a wire jumper connect the ENTPAS and GND terminals Figure 22 Exit Direction 1 Locate the EXTPAS and GND terminals 2 Use a wire jumper to connect the EXTPAS and...

Страница 24: ...ation on SU3000 passage modes can be found in the SU3000 User Guide Flashing Passage Mode Description User Status Display Open Closed Status Light Controlled Passage The barrier arms are closed securi...

Страница 25: ...to Appendix A on Page 29 for instructions on setting the barrier arm Home Position The keys to power the turnstile ON OFF are packaged in the hardware box that was shipped with the turnstile Powering...

Страница 26: ...ntry Exit Authorized Entry Exit Unsecured Side Unauthorized Entry shown Authorized Entry shown Secured Side Unsecured Side TEST PROCEDURE TURNSTILE RESPONSE Enter the turnstile without authorization U...

Страница 27: ...e turnstile Barriers close after passage completion Enter the turnstile User Status Light red icon is illuminated Open Closed Status Light is red Unauthorized Entry alarm sounds Barriers remain closed...

Страница 28: ...ning the key to one of three positions overrides all existing settings placing the turnstile in Controlled Passage mode Free Passage mode or No Passage mode depending on the orientation of the key Ref...

Страница 29: ...arch programs and files field 5 Enter the following command ping XXX XXX X XXX where XXX XXX X XXX is the IP address of the turnstile Figure 29 6 A successful ping will result in the message shown in...

Страница 30: ...tioning properly Auditory alarms are playing back correctly Barrier arms move smoothly between the open and closed positions 3 Access Control Integration Installed card readers are successfully readin...

Страница 31: ...DC fuse on the motor controller board Locate the motor controller board fuses Figure 31 Using a multimeter check the 24VDC 6 3A fuse for continuity If the fuse is blown contact Alvarado for replacemen...

Страница 32: ...l operation mode 2 Press the Test Mode button for two seconds The D2 LED will be lit solid You are now in test mode Figure A1 3 Move the barrier arm a couple of inches in both directions and then plac...

Страница 33: ...uration Three Lane Configuration LANE 2 LANE 2 LANE 3 LANE 1 LANE 1 Master Cabinet Master Cabinet Center Cabinet Center Cabinet Slave Cabinet Center Cabinet Slave Cabinet Symbology Description Conduit...

Страница 34: ...not provided Wire gauge recommendations for 30 50 and 100 ft runs are provided on Page 36 If your installation requires runs beyond 100 ft ensure wire gauge is appropriate and in compliance with local...

Страница 35: ...onduit holes on the enclosure Figure C3 4 Locate the pre installed primary power terminal block Figure C3 There is one primary power terminal block per enclosure 5 Attach each primary power wire to th...

Страница 36: ...urnstiles Fig C4 Power Supply Output Terminal Block Fig C5 Turnstile Power Terminal Block The 24VDC V and GND V terminals are common NOTE If connecting to multiple turnstiles it is recommended to labe...

Страница 37: ...ort alvaradomfg com 1 909 591 8431 Page 37 LANE 1 MASTER CABINET CENTER CABINET SLAVE CABINET CENTER CABINET LANE 2 LANE 3 110VAC 220VAC INPUT POWER SUPPLY ENCLOSURE 24VDC OUTPUT TO CIRCUIT BREAKER Ex...

Страница 38: ...ation Instructions Page 38 For assistance support alvaradomfg com 1 909 591 8431 PUD3628R1 2 24VDC CONDUIT HOLES 110 220VAC CONDUIT HOLE Power Supply Enclosure Dimensions 15 80 401 4 9 50 241 3 6 23 1...

Страница 39: ...ble Connection Diagrams MASTER SLAVE Master Cabinet Slave Cabinet SLAVE SLAVE MASTER MASTER Master Cabinet Center Cabinet Slave Cabinet LANE 1 LANE 2 SLAVE SLAVE SLAVE MASTER MASTER MASTER Master Cabi...

Страница 40: ...0 05 20 14 A Flores Original document 1 1 07 14 14 A Flores Added Configuring Passage Modes section 1 2 11 13 15 A Flores Updated crossover cable length to 8 Appendix B Multi Lane Conduit Requirements...

Страница 41: ...This page intentionally left blank...

Страница 42: ...2014 Alvarado Manufacturing Company Inc This work may not be reproduced published or redistributed in whole or in part without the express prior written permission of Alvarado...

Отзывы:

Похожие инструкции для SU3000