Fig. 3
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
Replace fuse with the same type and rating: Input Fuse is rated at 6.3A/250V,
Battery Fuse rated at 25A/32V.
Earth
Ground
115VAC Input
60Hz, 5A
(non power
limited)
Wire
Strap
(from
Enclosure
to Door)
FACP
GND
GND
– OUT1 +
+ BAT –
– OUT2 +
IN1
GND
IN2
L
G
N
25A 32V
25A
6.3A
6.3A 250V
AC
OUT1
TIMER
Manual T
est
OUT2
TIMER
ON
Option 1-Option
2
24-5V Hold V
oltage
Follow-up Delay 0.5-1 sec.
Fir
e Alarm Interface
1
2
3
4
Power-Limited
Outputs
Class 2 Dry
Battery
Outputs
(non power
limited)
FACP and
Access Control
Trigger Inputs
(Power-Limited)
Power-Limited
Aux. Outputs
Class 2 Dry
Power-Limited
Outputs
Class 2 Dry
MIN
MAX
Tamper Switch
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
7AH Rechargeable batteries are the largest batteries that can fit in this enclosure.
A UL Listed external battery enclosure must be used if using 12AH, 40AH or 65AH batteries.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required for
Canadian installations.
Optional Rechargeable Stand-by
Battery for UL294 Applications.
Note: 12V batteries required
Canadian installations.
C
NO
C
NO
C
NC
+12VDC–
+24VDC–
Delayed 1
Follower
1
C
NO
C
NO
C
NO
C
NO
Delayed 2
Follower
2
C
NO
C
NO
FA
UL
T
C
NC
OUT1
TIMER
OUT2
TIMER
MIN
ON
Option 1-Option 2
24-5V Hold Voltage
Follow-up Delay 0.5-1 sec.
Fire Alarm Interface
1
2
3
4
MIN
MAX
Fig. 3a
Fig. 3b
Note: StrikeIt1 is intended for use with VON DUPRIN® panic hardware devices.
VON DUPRIN® is a registered trademark of Allegion.
StrikeIt1
- 7