Altronix StrikeIt1 Скачать руководство пользователя страница 4

StrikeIt1 LED Diagnostics 

(cont’d)

INP2 - Red 

On 

Output 2 - Energized. 

Slow Blink 

Output 2 - Open Circuit. 

Trigger Input 2 

Rapid Blink 

Output 2 - Short Circuit. 

Off 

Output 2 - De-energized. 

FAI - Green 

On 

FACP Input triggered (alarm condition). 

Off 

FACP normal (non-alarm condition). 

BAT Trouble 

Red 

Off 

Normal condition. 

On 

Manual test initiated. 

Slow Blink 

Battery low or missing, active during manual test or AC failure. 

AC Trouble 

Off 

AC normal. 

Green 

Slow blink 

AC low or missing. 

Maintenance: 

Unit should be tested at least once a year for the proper operation as follows: 

FACP Supervision: To ensure proper connection and operation of the Fire Alarm disconnect hookup, remove wire from 

the terminal marked [FACP] on StrikeIt1. With the dip switch [SW4] in ON positon, unlocked Panic Hardware Devices will

unlock. With dip switch [SW4] in the OFF position (Fig. 3b, pg. 7), locked Panic Hardware Devices will relock. 

Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level. 

Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at 

battery terminal and at the board terminals marked [+ BAT --] to ensure there is no break in the battery connection wires. 

Press Manual test button. The battery LED should be illuminated during the selftest (approximately 15 seconds. 

When the battery LED blinks slowly this indicates that the battery is low or missing and may need to be replaced or serviced. 

Note: Maximum charging current under discharge is 650mA. 

Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed. 

Caution: For continuous protection against risk of electric shock and fire hazard, replace input fuse with the same type

 and rating: 6.3A/250V. Do not expose to rain or moisture; indoor use only. 

StrikeIt1 Terminal Identification: 

Terminal Legend  Function/Description 
+ 12VDC – 

12VDC Auxiliary Output @ 0.75A in alarm, 0.5A in stand-by. 

+ 24VDC – 

24VDC Auxiliary Output @ 0.75A. 20VDC to 26.4VDC for applications with battery back-up. 

+ BAT – 

24VDC Stand-by Battery Connection (Two (2) 12VDC batteries wired in series). 

– OUT 1 + 

Connect 24VDC Panic Hardware Device #1 

(See compatibility chart for other UL Listed devices operating range of the device must cover 

20VDC to 26.4VDC range 0.25 ohm maximum wiring resistance)

– OUT 2 + 

Connect 24VDC Panic Hardware Device #2. 

(See compatibility chart for other UL Listed devices operating range of the device must cover 

20VDC to 26.4VDC range 0.25 ohm maximum wiring resistance)

FACP / GND 

Normally Closed Dry Contact from Fire Alarm Control 

(100 ohm maximum wiring resistance)

IN1 / GND 

Normally Open Trigger input controls Output 1. May be held closed for extended unlocking 

(100 ohm maximum wiring resistance)

IN2 / GND 

Normally Open Trigger input controls Output 2. May be held closed for extended unlocking 

(100 ohm maximum wiring resistance)

Delayed 1 

Dry form “A” contacts provide a 1 second momentary pulse after a preset delay. With dip switch [SW3] in the OFF 

position, the delay is 0.5 seconds. With dip switch [SW3] in the ON position, the delay is 1 second (Fig. 3b, pg. 7)

This permits the Panic Hardware Device to fully unlock before signaling auto operator to swing door. 

Delayed 2 

Dry form “A” contacts provide a 1 second momentary pulse after a preset delay. With dip switch [SW3] in the OFF 

position, the delay is 0.5 seconds. With dip switch [SW3] in the ON position, the delay is 1 second (Fig. 3b, pg. 7)

This permits the Panic Hardware Device to fully unlock before signaling auto operator to swing door. 

Follower 1 

Dry form “A” contact. Energizes while output 1 is energized. Enables outside ADA switch plate to actuate 

auto operator while door is unlocked. De-activates outside ADA actuator while door is locked. 

Follower 2 

Dry form “A” contact. Energizes while output 2 is energized. Enables outside ADA switch plate to actuate 

auto operator while door is unlocked. De-activates outside ADA actuator while door is locked. 

Supervision 

Indicates low DC output voltage condition. It may be caused by an AC brownout and low battery occuring 
simultaneously. Manual self test needs to be conducted to determine battery condition. 

- 4 -

StrikeIt1 

                    Available from A1 Security Cameras 

     www.a1securitycameras.com   email: [email protected]

Содержание StrikeIt1

Страница 1: ...Panic Device Power Controller Installation Guide Altronix Corp 140 58th St Brooklyn NY Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com Rev 061813...

Страница 2: ...attery capacity for emergency stand by is 30 minutes Visual Indicators Green AC Power LED indicates 115VAC present Red trigger input LEDs indicate panic device status trouble activated short or open c...

Страница 3: ...W3 in the OFF position one 1 second with SW3 in the ON position Unit is factory set for 0 5 seconds delay Note For UL ULC applications all interconnecting devices must be UL ULC Listed respectively 9...

Страница 4: ...s with battery back up BAT 24VDC Stand by Battery Connection Two 2 12VDC batteries wired in series OUT 1 Connect 24VDC Panic Hardware Device 1 See compatibility chart for other UL Listed devices opera...

Страница 5: ...re Alarm Interface 1 2 3 4 Delayed 1 Follower 1 C NO C NO MIN MAX Auxiliary 24VDC Device AC Supervision Fire Alarm Control Panel Auxiliary Device Automatic Door Operator C NO C NO Delayed 2 Follower 2...

Страница 6: ...larm Interface Connect these terminals to a normally closed dry contact that opens upon fire alarm activation Input 1 Connect normally open dry contacts from key switch timer remote release or any mai...

Страница 7: ...N1 GND IN2 L G N 25A 32V 25A 6 3A 6 3A 250V AC OUT1 TIMER Manual Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Delay 0 5 1 sec Fire Alarm Interface 1 2 3 4 Power Limited Outputs Cl...

Страница 8: ...knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed w...

Страница 9: ...6mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0...

Страница 10: ...Notes 10 StrikeIt1 Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com...

Страница 11: ...Notes StrikeIt1 11 Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com...