Altronix StrikeIt1 Скачать руководство пользователя страница 3

Connect earth ground to a ground lug or ground lead. Do not connect to a receptacle controlled by a switch. Unit is 

intended for permanent connection using metal enclosed system. A fixed product shall be connected with one of the 

applicable wiring systems in accordance with CSA C22.1, Canadian Electrical Code, Part I, Safety Standard for 

Electrical Installations. 

Note: StrikeIt1 is intended to be permanently connected. 

3.   Measure aux. output voltage before connecting devices. This helps avoiding potential damage. 

4.   For ULC applications, all interconnecting devices must be ULC Listed. 

Connect panic hardware device # 1 to terminals marked [+ OUT1 --], connect panic hardware device # 2 to 

terminals marked [+ OUT2 --] (Fig. 1, pg. 5). Be sure to observe polarity. For devices requiring 24VDC holding 

voltage, set dip switch [SW2] to OFF, for 5VDC holding voltage, set dip switch [SW2] to ON (Fig. 3b, pg. 7)

Panic Hardware devices must be configured to Fail-Safe, maximum wire resistance for each output is 0.25 ohm (see 

wiring gauge and distance chart, pg. 6). The panic hardware device operating voltage specifications must cover 

20VDC to 26.4VDC range. 

Note: Refer to compatible panic hardware device list, pg. 5. 

5.   Set lock output release time by adjusting [OUT1] and [OUT2] potentiometers. Turn potentiometer clockwise to 

increase time or counter-clockwise to decrease time. Timing range is 300ms. to 30 seconds, 

(unit is factory set @ 300ms.) (Fig. 3a, pg. 7)

Note: When external control of door unlock time is desired, i.e., card reader, set time to minimum 

(completely counter-clockwise). 

6.   Connect Normally Open (NO) Dry Contacts from actuating devices such as an Access Control Panel, REX PIR, 

Keypad, etc. to terminals marked [GND, IN1] and [GND, IN2] (Fig. 1, pg. 5)

Note: When triggering both Input 1 and Input 2 from a single actuating device, set dip switch [SW1] to ON for 

sequential mode (100 ohm line resistance maximum)

7.   Connect auxiliary devices to be powered (Keypads, REX motion detectors, electronic timers, external relays ) to the 

appropriate auxiliary power output terminals. For 12VDC devices, use terminals marked [+ 12VDC --]. 

For 24VDC devices use terminals marked [-- 24VDC +] (Fig. 1, pg. 5)

Note: Operating voltage range of device should be 20VDC to 26.4VDC or wider. 

8.   Connect devices to be controlled to terminals marked [DELAYED1, DELAYED2] and/or [FOLLOWER1, 

FOLLOWER2] (Dry form “A” contacts are rated @ 600mA/28VDC) (Fig. 1, pg. 5). Adjust delay time using dip switch 

[SW3] 

(Fig. 3b, pg. 7) (0.5 seconds with SW3 in the OFF position, one (1) second with [SW3] in the ON position). 

Unit is factory set for 0.5 seconds delay. 

Note: For UL/ULC applications all interconnecting devices must be UL/ULC Listed respectively. 

9.  To hookup the Fire Alarm Disconnect feature, wire the normally closed (NC) dry contact output from a Fire Alarm 

Control Panel to the terminals marked [FACP] and [GND] of StrikeIt1. 

The “FA Select” dip switch [SW4] provides two (2) modes of operation (Fig. 3b, pg. 7)

a)  With dip switch [SW4] in the ON position, the application of a FACP trigger input (open circuit) while Input 1 and 

Input 2 are triggered will cause the unlocked (energized) panic hardware devices to relock (de-energize). 

Follower relays will release (de-energize). 

b)   With dip switch [SW4] in the OFF position, the application of a FACP trigger input (open circuit) while Input 1 

and Input 2 are not triggered will cause the locked (de-energized) panic hardware devices to unlock (energize). 

Follower relays will activate (energize). Delayed relays will energize momentarily. 

Note: With SW4 in the OFF position, the application of a FACP trigger input (open circuit) while Input 1 and 

Input 2 are triggered will have no affect on the operation of Output 1 or Output 2 and their corresponding 

Follower or Delayed relays. 

10.  When using stand-by batteries, they must be lead acid or gel type. 7AH batteries will provide 30 minutes of backup 

time. Connect two (2) 12VDC batteries wired in series to the terminals marked [+ BAT --]. 

For Access Control applications in the U.S. batteries are optional, for Canadian applications batteries are required. 

When batteries are not used, loss of AC will result in the loss of output voltage. 

11.  Mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide the tamper 

switch bracket onto the edge of the enclosure approximately 2” from the right side (Fig. 3, pg. 7). Connect tamper 

switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. To activate alarm 

signal open the door of the enclosure. 

Note: Do not exceed voltage and current ratings of tamper switch. Please refer to tamper switch installation instructions. 

12.  Upon completion of wiring secure enclosure door with screws or cam lock (supplied). 

StrikeIt1 LED Diagnostics: 

LED 

LED Status 

Panic Device Power Controller Status 

Power -

On 

Normal operating condition. 

Green (AC) 

Off 

Loss of AC. 

On 

Output 1 - Energized. 

INP1 - Red 

Slow Blink 

Output 1 - Open Circuit. 

Trigger Input 1 

Rapid Blink 

Output 1 - Short Circuit. 

Off 

Output 1 - De-energized. 

StrikeIt1 

 - 3 ­

                    Available from A1 Security Cameras 

     www.a1securitycameras.com   email: [email protected]

Содержание StrikeIt1

Страница 1: ...Panic Device Power Controller Installation Guide Altronix Corp 140 58th St Brooklyn NY Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com Rev 061813...

Страница 2: ...attery capacity for emergency stand by is 30 minutes Visual Indicators Green AC Power LED indicates 115VAC present Red trigger input LEDs indicate panic device status trouble activated short or open c...

Страница 3: ...W3 in the OFF position one 1 second with SW3 in the ON position Unit is factory set for 0 5 seconds delay Note For UL ULC applications all interconnecting devices must be UL ULC Listed respectively 9...

Страница 4: ...s with battery back up BAT 24VDC Stand by Battery Connection Two 2 12VDC batteries wired in series OUT 1 Connect 24VDC Panic Hardware Device 1 See compatibility chart for other UL Listed devices opera...

Страница 5: ...re Alarm Interface 1 2 3 4 Delayed 1 Follower 1 C NO C NO MIN MAX Auxiliary 24VDC Device AC Supervision Fire Alarm Control Panel Auxiliary Device Automatic Door Operator C NO C NO Delayed 2 Follower 2...

Страница 6: ...larm Interface Connect these terminals to a normally closed dry contact that opens upon fire alarm activation Input 1 Connect normally open dry contacts from key switch timer remote release or any mai...

Страница 7: ...N1 GND IN2 L G N 25A 32V 25A 6 3A 6 3A 250V AC OUT1 TIMER Manual Test OUT2 TIMER ON Option 1 Option 2 24 5V Hold Voltage Follow up Delay 0 5 1 sec Fire Alarm Interface 1 2 3 4 Power Limited Outputs Cl...

Страница 8: ...knockouts to be used Any conduit knockouts may be used For power limited applications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed w...

Страница 9: ...6mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25 83mm 3 25 83mm 1 0 25mm 1 0 25mm 10 5 267mm 1 0 25mm 1 0 25mm 0 75 19mm 0...

Страница 10: ...Notes 10 StrikeIt1 Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com...

Страница 11: ...Notes StrikeIt1 11 Available from A1 Security Cameras www a1securitycameras com email sales a1securitycameras com...

Страница 12: ...ge without notice 140 58th Street Brooklyn New York 11220 USA 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A IIStrikeIt1 F14P MEMBER 12...

Отзывы: