Maximal3F/Maximal5F/Maximal7F Access Power Controllers (Fused)

 

Access Power Controller Terminal Identification:

Terminal Legend

Function/Description

– Power +

12VDC or 24VDC from power supply/charger (factory connected).
These terminals are paralleled to the [– C] terminals.

– C

These terminals are paralleled to the [– Power +] terminals.
These terminals can be connected to an external Listed power-limited access control 
power supply to provide isolated operating power for the devices (Not evaluated by UL). 
Jumpers J1 and J2 must be removed.

TRIGGER INPUT1 - 
INPUT 8 IN, GND

From normally open and/or open collector sink trigger inputs 
(request to exit buttons, exit PIRs, etc.)

OUTPUT 1-
OUTPUT 8 
NC, C, NO, COM

12VDC to 24VDC trigger controlled outputs are rated at 2.5A.
Maximal3F: 10.0-13.2VDC @ 4.6A or 20.19-26.4VDC @ 5.2A.
Maximal5F: 10.03-13.2VDC @ 8.6A.
Maximal7F: 20.17-26.4VDC @ 9.2A.
Fail-Safe [NC positive (+) & COM Negative (–)], Fail-Secure [NO positive (+) & 
COM Negative (–)], Auxiliary output [C positive (+) & COM Negative (–)]. When 
using AC power supplies polarity needs not to be observed. NC, C, NO convert to dry 
form “C” 5A 24VAC/VDC rated dry outputs when fuses are removed. 
Contacts shown in a non-triggered state.

FACP INTERFACE
T, + INPUT –

Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
normally closed from an FACP signaling circuit output (Figs. 5-9, pg. 12).

FACP INTERFACE
NC, C, NO

Form “C” relay contact rated @ 1A 28VDC for alarm reporting (not evaluated by UL).

Power Supply Board Stand-by Battery Specifications:

Battery

Maximal3F

Maximal5F

Maximal7F

7AH

10 Mins./6A

5 Mins./10A

5 Mins./10A

12AH

30 Mins./6A*

30 Mins./10A*

30 Mins./10A*

40AH

Over 4 Hours/6A*

Over 2 Hours/10A*

Over 2 Hours/10A*

65AH

Over 4 Hours/6A*

Over 4 Hours/10A*

Over 4 Hours/10A*

*Only these configurations can be utilized in ULC-S319 installations.

Содержание Maximal3F

Страница 1: ...Sixteen 16 fuse protected non power limited outputs Maximal7F 24VDC 9 2A Sixteen 16 fuse protected non power limited outputs Rev MSFF052419 More than just power TM Installing Company ________________...

Страница 2: ...upply Board LED Diagnostics pg 7 Access Power Controller LED Diagnostics pg 7 Power Supply Board Terminal Identification pg 7 Access Power Controller Terminal Identification pg 8 Power Supply Board St...

Страница 3: ...e V 12VDC Output Range V 24VDC Output Range V Maximal3F 3 5A 5A 250V 10A 32V 10 0 13 2 20 19 26 4 10 03 13 2 20 19 26 4 12VDC 4 6A or 24VDC 5 2A 16 2 5 10A 250V 3 5A 250V Maximal5F 3 5A 5A 250V 15A 32...

Страница 4: ...L eFlow Power Supply Charger provides common power for ACM8 board factory wiring and all connected access control devices field wiring ACM8 board main fuses are rated 10A Output fuses are rated 3 5A e...

Страница 5: ...user serviceable parts inside Refer installation and servicing to qualified service personnel 3 Select desired DC output voltage by setting SW1 to the appropriate position on the Maximal3F power suppl...

Страница 6: ...AWG for AC Fail Low No Battery reporting 12 To delay AC reporting for 2 hrs set DIP switch AC Delay to OFF position Fig 3 pg 10 To delay AC reporting for 1 min set DIP switch AC Delay to ON position...

Страница 7: ...G DC Factory connected to ACM8 board Trigger EOL Supervised Fire Alarm Interface trigger input from a short or FACP Trigger inputs can be normally open normally closed from an FACP output circuit Clas...

Страница 8: ...9 26 4VDC 5 2A Maximal5F 10 03 13 2VDC 8 6A Maximal7F 20 17 26 4VDC 9 2A Fail Safe NC positive COM Negative Fail Secure NO positive COM Negative Auxiliary output C positive COM Negative When using AC...

Страница 9: ...IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 TRG FACP NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5 NC C NO COM OUTPUT 6...

Страница 10: ...l ON Power Supply Board CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Connect red battery lead to the terminal marked BAT and to the positive terminal of the b...

Страница 11: ...connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring...

Страница 12: ...TRG J3 NO C NC FACP INTERFACE JUMPER N C DRY TRIGGER INPUT TRG J3 NO C NC FACP INTERFACE N C TRIGGER INPUT N C RESET SWITCH JUMPER TRG J3 N O TRIGGER INPUT TRG J3 NO C NC FACP INTERFACE N C RESET SWI...

Страница 13: ...Maximal3F Maximal5F Maximal7F Access Power Controllers Fused 13 Notes...

Страница 14: ...14 Maximal3F Maximal5F Maximal7F Access Power Controllers Fused Notes...

Страница 15: ...50 8mm 2 50 8mm 6 25 158 75mm 6 25 158 75mm 4 101 6mm 4 101 6mm 2 50 8mm 4 101 6mm 8 9 226 06mm 8 4 213 36mm 7 177 8mm 7 177 8mm 7 177 8mm 8 4 213 36mm 8 5 215 9mm 8 5 215 9mm 7 5 190 5mm 10 254mm 1 5...

Страница 16: ...ada Local or remote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state...

Отзывы: