- 8 -
Maximal3F/Maximal5F/Maximal7F Access Power Controllers (Fused)
Access Power Controller Terminal Identification:
Terminal Legend
Function/Description
– Power +
12VDC or 24VDC from power supply/charger (factory connected).
These terminals are paralleled to the [– C] terminals.
– C
These terminals are paralleled to the [– Power +] terminals.
These terminals can be connected to an external Listed power-limited access control
power supply to provide isolated operating power for the devices (Not evaluated by UL).
Jumpers J1 and J2 must be removed.
TRIGGER INPUT1 -
INPUT 8 IN, GND
From normally open and/or open collector sink trigger inputs
(request to exit buttons, exit PIRs, etc.)
OUTPUT 1-
OUTPUT 8
NC, C, NO, COM
12VDC to 24VDC trigger controlled outputs are rated at 2.5A.
Maximal3F: 10.0-13.2VDC @ 4.6A or 20.19-26.4VDC @ 5.2A.
Maximal5F: 10.03-13.2VDC @ 8.6A.
Maximal7F: 20.17-26.4VDC @ 9.2A.
Fail-Safe [NC positive (+) & COM Negative (–)], Fail-Secure [NO positive (+) &
COM Negative (–)], Auxiliary output [C positive (+) & COM Negative (–)]. When
using AC power supplies polarity needs not to be observed. NC, C, NO convert to dry
form “C” 5A 24VAC/VDC rated dry outputs when fuses are removed.
Contacts shown in a non-triggered state.
FACP INTERFACE
T, + INPUT –
Fire Alarm Interface trigger input from FACP. Trigger inputs can be normally open,
normally closed from an FACP signaling circuit output (Figs. 5-9, pg. 12).
FACP INTERFACE
NC, C, NO
Form “C” relay contact rated @ 1A 28VDC for alarm reporting (not evaluated by UL).
Power Supply Board Stand-by Battery Specifications:
Battery
Maximal3F
Maximal5F
Maximal7F
7AH
10 Mins./6A
5 Mins./10A
5 Mins./10A
12AH
30 Mins./6A*
30 Mins./10A*
30 Mins./10A*
40AH
Over 4 Hours/6A*
Over 2 Hours/10A*
Over 2 Hours/10A*
65AH
Over 4 Hours/6A*
Over 4 Hours/10A*
Over 4 Hours/10A*
*Only these configurations can be utilized in ULC-S319 installations.