Maximal Rack Access Power Controllers (Fused) Installation Guide
- 5 -
17.
Output connections:
Connect the devices to be powered to the removable terminals marked [– OUT1 +] to [– OUT8 +] for
Maximal1RH and Maximal3RH. For Maximal1R, Maximal3R, and Maximal33R connect devices to the
second set of terminals marked [– OUT1 +] to [– OUT8 +]
(Fig. 15c, pg. 12)
.
18.
Fire Alarm Interface connection options:
a. Connect the FACP trigger input to the removable terminals marked FACP1 and FACP2. When using the
polarity reversal from an FACP signaling circuit, connect the negative [–] to the terminal marked FACP1
and the positive [+] to the terminal marked FACP2 (polarity is in alarm condition)
(Rack Mechanical Drawing and Dimensions pg. 12)
.
b. For a latching fire alarm interface connect a normally [NO] reset switch to the removable terminals
marked [REST] and [GND]
(Figs. 6-11, pg. 9)
.
19. Set the power disconnect circuit breaker to the ON position
(Fig. 15a, pg. 12)
.
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test:
Under normal load conditions the DC output voltage should be checked for proper voltage
level
(Output Voltage and Stand-by Specification Charts, pg. 5).
Battery Test:
Under normal load conditions check that the battery is fully charged, check specified voltage at
the battery terminals and at the board terminals marked [– BAT +] to ensure that there is no break in the battery
connection wires.
Fire Alarm Interface Switch Settings:
Switch Position
FACP Input
SW1
SW2
OFF
OFf
FACP Signal Circuit (Polarity Reversal).
ON
ON
Normally Closed [NC] Trigger Input.
ON
OFF
Normally Open [NO] Trigger Input.
Output Voltage and Stand-by Specification Charts:
Altronix Model
Power Supply Board
Battery
20 Min. of
Backup
4 Hr. of
Backup
24 Hr. of
Backup
Maximal1RH
Maximal1R
OLS120
(Refer to Fig. 1a, pg. 4 for Switch
[SW1] location and position)
12VDC/40AH*
N/A
3.5A
0.5A
24VDC/40AH*
N/A
2.7A
0.7A
Maximal3RH
Maximal3R
Maximal33R
AL600ULXB
(Refer to Fig. 1a, pg. 4 for Switch
[SW1] location and position)
12VDC/40AH*
N/A
5.5A
5.5A
24VDC/40AH*
N/A
5.5A
0.7A
LED Diagnostics:
Power Supply Board
LED
Power Supply Status
Red (DC)
Green (AC)
ON
ON
Normal operating condition.
ON
OFF
Loss of AC. Stand-by battery supplying power.
OFF
ON
No DC output. Short circuit or thermal overload condition.
OFF
OFF
No DC output. Loss of AC. Discharged battery.
Output LEDs on Front Panel
ON
Output is triggered.
Blinking
FACP disconnect.