Altronix Maximal R Series Скачать руководство пользователя страница 5

 

Maximal Rack Access Power Controllers (Fused) Installation Guide 

- 5 -

17. 

Output connections:

 

Connect the devices to be powered to the removable terminals marked [– OUT1 +] to [– OUT8 +] for 

 

Maximal1RH and Maximal3RH. For Maximal1R, Maximal3R, and Maximal33R connect devices to the 

 

second set of terminals marked [– OUT1 +] to [– OUT8 +] 

(Fig. 15c, pg. 12)

.

18. 

Fire Alarm Interface connection options:

 

a.  Connect the FACP trigger input to the removable terminals marked FACP1 and FACP2. When using the 

 

 

polarity reversal from an FACP signaling circuit, connect the negative [–] to the terminal marked FACP1 

 

 

and the positive [+] to the terminal marked FACP2 (polarity is in alarm condition) 

  

(Rack Mechanical Drawing and Dimensions pg. 12)

 

b.  For a latching fire alarm interface connect a normally [NO] reset switch to the removable terminals 

 

 

marked [REST] and [GND] 

(Figs. 6-11, pg. 9)

.

19.  Set the power disconnect circuit breaker to the ON position 

(Fig. 15a, pg. 12)

.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:

Output Voltage Test:

 Under normal load conditions the DC output voltage should be checked for proper voltage 

level 

(Output Voltage and Stand-by Specification Charts, pg. 5).

Battery Test: 

Under normal load conditions check that the battery is fully charged, check specified voltage at 

the battery terminals and at the board terminals marked [– BAT +] to ensure that there is no break in the battery 

connection wires.

Fire Alarm Interface Switch Settings:

Switch Position

FACP Input

SW1

SW2

OFF

OFf

FACP Signal Circuit (Polarity Reversal).

ON

ON

Normally Closed [NC] Trigger Input.

ON

OFF

Normally Open [NO] Trigger Input.

Output Voltage and Stand-by Specification Charts:

Altronix Model

Power Supply Board

Battery

20 Min. of 

Backup

4 Hr. of 

Backup

24 Hr. of 

Backup

Maximal1RH

Maximal1R

OLS120

(Refer to Fig. 1a, pg. 4 for Switch 

[SW1] location and position)

12VDC/40AH*

N/A

3.5A

0.5A

24VDC/40AH*

N/A

2.7A

0.7A

Maximal3RH

Maximal3R

Maximal33R

AL600ULXB

(Refer to Fig. 1a, pg. 4 for Switch 

[SW1] location and position)

12VDC/40AH*

N/A

5.5A

5.5A

24VDC/40AH*

N/A

5.5A

0.7A

LED Diagnostics:

Power Supply Board

LED

Power Supply Status

Red (DC)

Green (AC)

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output. Short circuit or thermal overload condition.

OFF

OFF

No DC output. Loss of AC. Discharged battery.

Output LEDs on Front Panel

ON

Output is triggered.

Blinking

FACP disconnect.

Содержание Maximal R Series

Страница 1: ...aximal R Series Rack Mount Access Power Controllers fused Models Include Maximal1RH 12VDC 4A or 24VDC 3A Eight 8 fuse protected outputs Maximal3RH 12VDC or 24VDC 6A Eight 8 fuse protected outputs Maxi...

Страница 2: ...Specification Charts pg 5 LED Diagnostics pg 5 Power Supply Board Output Voltage Settings pg 6 Fire Alarm Interface Output Selection and Input Type pg 7 Power Supply Boards Drawings pg 8 FACP Hook Up...

Страница 3: ...2VDC 6A N A 6A 8 2 5A 1 9A 3 5A 250V 24VDC 6A N A Maximal3R 12VDC 6A N A 6A 16 2 5A 1 9A 3 5A 250V 24VDC 6A Maximal33R 12VDC 6A 12VDC 6A 12A 16 2 5A 3 8A 3 5A 250V 24VDC 6A 24VDC 6A 12VDC 6A 24VDC 6A...

Страница 4: ...FACP signaling circuit will trigger the selected outputs Figs 6 11 pg 9 To program the Fire Alarm Interface set dip switches SW1 and SW2 on the ACM8R M board to the appropriate positions Figs 3a and...

Страница 5: ...roper voltage level Output Voltage and Stand by Specification Charts pg 5 Battery Test Under normal load conditions check that the battery is fully charged check specified voltage at the battery termi...

Страница 6: ...2V ON OFF 24V ON 12V ON ON OFF 24V ON 12V The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user to the presence of an insulated DANGEROUS VOLTAGE withi...

Страница 7: ...TYPE SW3 OUTPUT SELECT ON 4 3 1 2 ON 4 3 1 2 ON 4 3 1 2 ON 4 3 1 2 ON 4 3 1 2 FIRE ALARM INTERFACE OUTPUT SELECT ON 4 3 1 2 ON 4 3 1 2 ON 4 3 1 2 ON 4 3 1 2 INPUT TYPE SW3 SW3 DIP Switch for NO or NC...

Страница 8: ...harging Battery and AC Supervision LOW BAT NC C NO NC C NO AC FAIL ON Power Supply Board Maximal1RH Maximal1R Fig 4 BAT Built in Battery Charging L G N 5A 250V Built in Battery Charging Battery and AC...

Страница 9: ...m FACP Signal Circuit Normally Open NO Reset Switch 1 2 FACP RESET Latching Latching Latching Normally Closed Input from FACP GND IN8 GND Factory Installed Jumper Normally Closed NC Dry Trigger Input...

Страница 10: ...rack enclosure Fig 13a Use three 3 flat head screws B to secure brackets 3 Carefully place faceplate over LEDs and secure using three 3 pan head screws C on top and three 3 pan head screws C on the b...

Страница 11: ...Maximal Rack Access Power Controllers Fused Installation Guide 11 Notes...

Страница 12: ...IN13 IN12 GND GND GND ON Removable Terminal Block 3 Wire Line Cord OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 2 1 OUT8 IN1 IN2 IN3 IN5 IN6 IN7 IN8 IN4 GND GND GND RESET FACP GND GND Front Rear Top and Bottom...

Отзывы: