Maximal Rack Access Power Controllers (Fused) Installation Guide
- 3 -
Overview:
Altronix Maximal Rack Mount Series units distribute and switch power to access control systems and accessories.
They convert a 115VAC, 50/60Hz input into eight (8) or sixteen (16) independently controlled 12VDC and/or
24VDC fuse protected outputs. Outputs are activated by a normally open (NO) or normally closed (NC) dry trigger
input from an Access Control System, Card Reader, Keypad, Push Button, PIR, etc. Units will route power to a
variety of access control hardware devices including: Mag Locks, Electric Strikes, Magnetic Door Holders, etc.
Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface enables Emergency Egress,
Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm disconnect feature is individually
selectable for any or all of the outputs (see chart below).
Maximal Rack Mount Series Configuration Chart:
Altronix
Model Number
Power
Supply 1
(8 outputs)
Power
Supply 2
(8 outputs)
Total
Output
Current
Fuse
Protected
Outputs
Maximum
Current
Per
ACM8R-M
Output
115VAC
50/60Hz
Input
(current
draw)
Power
Supply
Board
Input Fuse
Rating
Maximal1RH
12VDC @ 4A
N/A
4A
8
2.5A
1.9A
5A/250V
24VDC @ 3A
N/A
3A
Maximal1R
12VDC @ 4A
N/A
4A
16
2.5A
1.9A
5A/250V
24VDC @ 3A
N/A
3A
Maximal3RH
12VDC @ 6A
N/A
6A
8
2.5A
1.9A
3.5A/250V
24VDC @ 6A
N/A
Maximal3R
12VDC @ 6A
N/A
6A
16
2.5A
1.9A
3.5A/250V
24VDC @ 6A
Maximal33R
12VDC @ 6A
12VDC @ 6A
12A
16
2.5A
3.8A
3.5A/250V
24VDC @ 6A
24VDC @ 6A
12VDC @ 6A
24VDC @ 6A
Specifications:
Inputs:
• Normally closed [NC] or normally open [NO]
dry contact inputs (switch selectable).
Outputs:
• Individually selectable Mag Lock/Strike (Fail-Safe,
Fail-Secure) solid state fuse protected power outputs.
• Thermal and short circuit protection with auto reset.
Fire Alarm Interface:
• Fire Alarm disconnect (latching with reset or
non-latching) is individually selectable for any or
all of the outputs.
• Remote reset capability for latching Fire Alarm
Interface mode.
• Fire Alarm disconnect input options:
a) Normally open [NO] or normally closed [NC]
dry contact input.
b) Polarity reversal input from
FACP
signaling
circuit.
Visual Indicators:
• Individual output status LEDs located on the
front panel.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries
(A separate enclosure is required for batteries).
• Maximum charge current 0.7A.
• Automatic switch over to stand-by battery
when AC fails.
• Zero voltage drop when unit switches over to
battery backup (AC failure condition).
Supervision:
• AC fail supervision (form “C” contact).
• Low battery supervision (form “C” contact).
Additional Features:
• Removable terminal blocks with locking
screw flange.
• 3-wire line cord.
• Illuminated master power disconnect circuit breaker
with manual reset.
Rack Dimensions
(H x W x D)
:
3.25” x 19.125” x 8.5”
(82.6mm x 485.8mm x 215.9mm).