eFlow3N Series Installation Guide
Overview:
Altronix eFlow3N power supply/chargers convert a 120VAC / 60Hz input to a 12VDC or 24VDC nominal output
(see Power Supply Configuration Reference Chart and Specifications)
.
eFlow3N Series Power Supply Configuration Reference Chart:
Altronix Model Number
Nominal DC Outputs
Maximum Supply Current for Main and Aux. Outputs (A)
Power-Limited Output
Input Rating: 120VAC, 60Hz
Input Fuse Rating
Battery Fuse Rating
Ripple Voltage (mV)
Under low battery condition
Power Distribution Modiule
Number of Outputs
Fused Outputs Ratings
Auto-Resettable PTC Outputs Ratings Accommodates up to 7AH Batteries Accommodates up to 12AH Batteries
[DC]
[AUX]
12VDC Output Range (V)
24VDC Output Range (V)
12VDC Output Range (V)
24VDC Output Range (V)
eFlow3N
10.13-
13.2
20.28-
26.39
10.15-
13.2
20.2-
26.39 2A
P
3.5A
5A/
250V
3A/
32V
960
N/A
1
–
–
P
–
eFlow3NX
–
–
–
P
eFlow3N4
10.13-
13.2
20.28-
26.39
10.15-
13.2
20.2-
26.39 2A
P
3.5A
5A/
250V
3A/
32V
960
PD4UL
4
2A
–
P
–
eFlow3NX4
2A
–
–
P
eFlow3N4D
9.78-
13.2
20.0-
26.39
10.15-
13.2
20.2-
26.39 2A
P
3.5A
5A/
250V
3A/
32V
960 PD4ULCB 4
–
2A
P
–
eFlow3NX4D
–
2A
–
P
These units are classified as Power-Limited stand alone power supplies with stand-by battery and they are suitable to power:
sensors, electro-mechanical devices (e.g. electric door strikes) defined in the National Electrical Code/NFPA70/NFPA72 and the
Canadian Electrical Code, Part 1.
UL Listings for US Installations:
UL 294, 7th edition
- UL Listed for Access Control System Units.
Access Control Performance Levels:
Destructive Attack - I; Endurance - I; Line Security - I;
Stand-by Power: 7AH - II, 12AH - III, 40AH/65AH - IV.
UL 603
- UL Listed for Power Supplies for Use with Burglar-Alarms Systems.
UL 1481
- UL Listed for Power Supplies for Fire Protective Signaling Systems.
UL Listings for Canadian Installations:
ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control.
California State Fire Marshal
European Conformity
Factory Mutual Approved (eFlow3N and eFlow3NX only).
Stand-by Specifications:
Battery
Burg. Applications
4 hr. Stand-by/
15 min. Alarm
Fire Applications
24 hr. Stand-by/
5 min. Alarm
Access Control
Applications
Stand-by
7AH
0.4A/2A
N/A
1.5 Hours/2A
12AH
(for eFlow3NX refer to Fig. 7, pg. 10)
1A/2A
0.3A/2A
3.5 Hours/2A
40AH
2A/2A
1.2A/2A
Over 4 Hours/2A
65AH
2A/2A
1.5A/2A
Over 4 Hours/2A