- 6 - 

eFlow3N Series Installation Guide

Fig. 2 - 

Battery Trouble Indication

For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure.

Wire one leg of a UL Listed, power-limited power source to the indicating lamp. 

Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact 

terminals marked [BAT FAIL - C, NO] (Fig. 2, pg. 6).

NC  C  NO 

NC  C  NO

BAT FAIL

AC FAIL

POWER

SOURCE

RED INDICATING

LAMP

–––––––––––––––––––––––––––––––––––––––––––––––––––––––––

Power Distribution Module(s):

Fig. 3a - PD4UL Power Distribution Board

Fig. 3b - PD4ULCB - Power Distribution Board

LED

F1

F2

F3

F4

1P

1N

2P

2N

3P

3N

4P

4N

DC Output to devices

1P-4P Power Outputs,

1N-4N Common Outputs

From Power Supply

Board

(Factory Installed)

Replace fuses with the same type and rating 3.5A/250V  

LED

F1

F2

F3

F4

1P

1N

2P

2N

3P

3N

4P

4N

DC Output to devices

1P-4P Power Outputs,

1N-4N Common Outputs

From Power Supply

Board

(Factory Installed)

Содержание eFlow3N

Страница 1: ...4 2A 12VDC or 24VDC Four 4 Class 2 Power Limited Fused Outputs eFlow3N4D eFlow3NX4D 2A 12VDC or 24VDC Four 4 Class 2 Power Limited PTC Outputs Installation Guide Rev 3NRP013019 More than just power TM...

Страница 2: ...4 2A P eFlow3NX4D 2A P These units are classified as Power Limited stand alone power supplies with stand by battery and they are suitable to power sensors electro mechanical devices e g electric door...

Страница 3: ...fer to Appendix A pg 13 4 Measure output voltage before connecting devices This helps avoiding potential damage 5 Connect devices to be powered a For eFlow3N eFlow3NX connect devices to terminals mark...

Страница 4: ...or Access Control Applications mount UL Listed tamper switch Altronix Model TS112 or equivalent at the top of the enclosure Slide tamper switch bracket onto the edge or the enclosure approx 2 from the...

Страница 5: ...is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maximum ch...

Страница 6: ...inals marked BAT FAIL C NO Fig 2 pg 6 NC C NO NC C NO BAT FAIL AC FAIL POWER SOURCE RED INDICATING LAMP Power Distribution Module s Fig 3a PD4UL Power Distribution Board Fig 3b PD4ULCB Power Distribut...

Страница 7: ...e required for UL603 UL1481 and Canadian installations Optional Rechargeable Stand by Battery for UL294 Applications Note 12V batteries are required for UL603 UL1481 and Canadian installations CAUTION...

Страница 8: ...nal All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power suppl...

Страница 9: ...ble Stand by Battery for UL294 Applications Note 12V batteries required for ULC S319 installations CAUTION When power supply board is set for 12VDC use only one 1 12VDC stand by battery Keep power lim...

Страница 10: ...ional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be mounted adjacent to the power sup...

Страница 11: ...6mm 1 40 35 6mm 1 40 35 6mm 4 85 123 2mm 4 85 123 2mm 3 25 82 6mm 0 75 19 1mm 0 75 19 1mm 11 0 279 4mm 12 5 317 5mm 1 20 30 5mm 1 20 30 5mm 0 9375 23 8mm 0 9375 23 8mm 5 10 129 5mm 1 40 35 6mm 5 10 1...

Страница 12: ...1 375 34 9mm 1 125 28 6mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 4 5 114 3mm 4 5 114 3mm 1 25 31 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9m...

Страница 13: ...24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2W MOD Loop Test Maintenance Mod 30 50...

Страница 14: ...mote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Страница 15: ...ltronix is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warra...

Страница 16: ...2A Over 4 Hours 2A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Transfer to stand by...

Отзывы: