NEC Power-Limited Wiring Requirements for eFlow104NV Models:

Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit 
wiring must remain at least 0.25” away from any non power-limited circuit wiring. Furthermore, all power-limited 
circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. 
One such example of this is shown below. Your specific application may require different conduit knockouts to 
be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field 
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).

Optional battery enclosure must be mounted adjacent to the power supply.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 6a).

Fig. 6

Fig. 6a

External

Jacketed

Shield

Incorrect Wire

Handling

Correct Wire

Handling

Pull back

external jacketed

shield approx. 1/2”.

Wire

Insulation

Solid Copper

Conductors

*  Outputs are non power-limited: 
  eFlow104NV, eFlow104N8V, eFlow104N16V.
  Outputs are power-limited: 
  eFlow104N8DV, eFlow104N16DV.

 Input 220VAC 50/60Hz

(non power-limited)

Optional Battery 

Enclosure

(non power-limited)

Supervisory,

Fire Alarm

Interface and

Aux. output

Connections

(power-limited)

Battery

Connections

(non power-limited)

DC Outputs*

Power 

Distribution

Содержание eFlow104N16DV

Страница 1: ..._____ Address ____________________________________________________ Phone ______________________ eFlow104NV eFlow104NXV 10A 24VDC eFlow104N8V eFlow104NX8V 10A 24VDC Eight 8 Fused Outputs eFlow104N16V e...

Страница 2: ...ange V eFlow104NV 20 17 26 4 20 28 26 4 10A 2 7A 6 3A 250V 15A 32V 700 N A 1 P eFlow104NXV P eFlow104N8V 20 17 26 4 20 28 26 4 10A 2 7A 6 3A 250V 15A 32V 700 PD8 8 2 5A P eFlow104NX8V 2 5A P eFlow104N...

Страница 3: ...y For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm Interface Connect device to terminals marked AUX Fig 1f pg 5 5 For Access Control applications...

Страница 4: ...wiring to the Access Control Panel input or the appropriate reporting device Wiring Use 18 AWG or larger for all low voltage power connections Note Take care to keep power limited circuits separate f...

Страница 5: ...is present Contact rating 1A 30VDC A removed battery is reported within 5 minutes Battery reconnection is reported within 1 minute power limited Fig 1b pg 5 BAT Stand by battery connections Maximum ch...

Страница 6: ...2 3 4 5 6 7 8 D1 INPUT R1 LED From Power Supply Board Factory Installed Replace fuses with the same type and rating 3 5A 250V DC Output to devices 1P 8P Power Outputs 1N 8N Common Outputs N COMMON POW...

Страница 7: ...AC Supervision Circuit Battery Connections Keep power limited wiring separate from non power limited Use minimum 0 25 spacing 7AH Rechargeable batteries are the largest batteries that can fit in this...

Страница 8: ...ptional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply Note...

Страница 9: ...eries are the largest batteries that can fit in this enclosure An external battery enclosure must be used if using the 40AH or 65AH batteries DC Output to devices refer to Fig 3a 3b for board configur...

Страница 10: ...tional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional battery enclosure must be mounted adjacent to the power supply Note...

Страница 11: ...342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 10 130mm 13 0 330mm 5 10 130mm 6 5625 167mm 1 20 31mm 1 20 31mm 1 20 31mm 3 25 83mm 3 25 83mm 3 25...

Страница 12: ...mm 1 25 31 75mm 1 25 31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38...

Страница 13: ...Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 39 2...

Страница 14: ...trol of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output state ch...

Страница 15: ...sponsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Made in U S A...

Страница 16: ...65AH 6A 10A 1 5A 10A Over 4 Hours 10A Battery Backup Built in charger for sealed lead acid or gel type batteries Maximum charge current 1 54A Automatic switch over to stand by battery when AC fails Tr...

Отзывы: