eFlowNA8D Series Installation Guide 

- 5 -

8. 

ACM8CB Fire Alarm Interface options 

(Figs. 6-10, pg. 10)

 

A normally closed [NC] or normally open [NO] input trigger from a fire alarm control panel or a polarity 

 

reversal input from an FACP signaling circuit will affect selected outputs. To enable FACP Disconnect for 

 

an output turn the corresponding switch(es) [SW1-SW8] OFF on each ACM8CB board. To disable FACP 

 

disconnect for an output turn the corresponding switch(es) [SW1-SW8] ON on each ACM8CB board.

 

(a)  Normally Open [NO] input:

 

    For non-latching hook-up refer to 

Fig. 7, pg. 10

. For latching hook-up refer to 

Fig. 8, pg. 10

.

 

(b)  Normally Closed [NC] input:

 

    For non-latching hook-up refer to 

Fig. 9, pg. 10

. For latching hook-up refer to 

Fig. 10, pg. 10

.

 

(c)  FACP Signaling Circuit input trigger:

 

    Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals 

 

    marked [+ INP –]. Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced 

 

    in an alarm condition). Jumper located next to TRG LED must be cut 

(Fig. 6, pg. 10)

9. 

FACP Dry form “C” output 

(Fig. 2b, pg. 7) 

(Not evaluated by UL):

 

FACP form “C” contacts can be use to trigger reporting or signaling devices. 

 

These contact switch upon a fire alarm input trigger to the ACM8CB board.

10. 

Stand-by Battery Connections

 

(Fig. 3, pg. 8)

:

 

For U.S. Access Control applications batteries are optional. Batteries are required for Canadian installations

 

(ULC-S319). When batteries are not used, a loss of AC will result in the loss of output voltage. When the 

 

use of stand-by batteries is desired, they must be lead acid or gel type.

 

Connect battery to terminals marked [– BAT + ] 

(Fig. 3, pg. 8)

. Use two (2) 12VDC batteries connected in 

 

series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 

 

(12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 and 

 

BAZR8 batteries of an appropriate rating. 

11. 

Battery and AC Supervision outputs 

(Fig. 3, pg. 8)

:

 

It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT Fail] 

 

supervisory relay outputs marked [NC, C, NO] to appropriate visual notification devices. 

 

Use 22 AWG to 18 AWG for AC Fail & Low/ No Battery reporting.

12.  To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position 

(Fig. 3, pg. 8)

.

 

To delay AC reporting for 1 min. set dip switch [AC Delay] to ON position 

(Fig. 3, pg. 8)

.

13.

  Fire Alarm Disconnect 

(Fig. 3, pg. 8)

:

 

To enable Fire Alarm Disconnect set dip switch [Shutdown] to ON position.

 

To disable Fire Alarm Disconnect set dip switch [Shutdown] to OFF position.

14. 

Installation of tamper switch 

(Fig. 3a, pg. 8)

:

 

Mount UL Listed tamper switch (Altronix model TS112 or equivalent) at the top of the enclosure. Slide the 

 

tamper switch bracket onto the edge of the enclosure approximately 2” from the right side 

(Fig. 3a, pg. 8)

 

Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting 

 

device. To activate alarm signal, open the door of the enclosure.

15. 

Multiple power supply inputs

 (Fig. 2, pg. 7) 

(Not evaluated by UL)

:

 

When using an additional Listed external power supply, jumpers J1 and J2 located on corresponding 

 

ACM8CB board must be cut 

(Fig. 2c, 2d, pg. 7 and Fig. 5, pg. 10)

. Connect external Listed power-limited 

 

access control power supply to the terminals marked [– Power +] (These terminals are paralleled to the 

 [– C] terminals). When using DC power supplies, polarity must be observed. When using AC 

 

power supplies, polarity need not be observed. 

(Fig. 2d, pg. 7) 

All field wiring connections must 

 

be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute) 

(Fig. 4a, pg. 9).

Содержание eFlow102NA8D

Страница 1: ...A8D 4A 12VDC or 24VDC Eight 8 PTC Outputs eFlow6NA8D 6A 12VDC or 24VDC Eight 8 PTC Outputs eFlow102NA8D 10A 12VDC Eight 8 PTC Outputs eFlow104NA8D 10A 24VDC Eight 8 PTC Outputs eFlowNAD8 Series Access...

Страница 2: ...mum Supply Current for Main and Aux Outputs A PTC Protected Power Limited Outputs Current per ACM8CB output A ACM8CB Board Input Fuse Rating ACM8CB Board Output PTC Rating DC AUX 12VDC Output Range V...

Страница 3: ...output voltage and supply current refer to eFlowNA8D Series Configuration Chart pg 2 Auxiliary Power Limited output rated 1A unswitched Overvoltage protection Built in charger for sealed lead acid or...

Страница 4: ...ovided Fig 3 pg 8 CAUTION Do not touch exposed metal parts Shut branch circuit power before installing or servicing equipment There are no user serviceable parts inside Refer installation and servicin...

Страница 5: ...leads included Use batteries Casil CL1270 12V 7AH CL12120 12V 12AH CL12400 12V 40AH CL12650 12V 65AH batteries or UL recognized BAZR2 and BAZR8 batteries of an appropriate rating 11 Battery and AC Sup...

Страница 6: ...8 pg 10 or Normally Closed Fig 10 pg 10 latching operation it is necessary to reset the Fire Alarm Disconnect by activating the Normally Closed reset switch Output Voltage Test Under normal load cond...

Страница 7: ...Access Power Controller Terminal Legend Function Description Power 12VDC or 24VDC from power supply charger factory connected These terminals are paralleled to the Control terminals Control These ter...

Страница 8: ...C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 FACP NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5...

Страница 9: ...RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Green Flying Lead Unswitched 120VAC power mains non power limited Optiona...

Страница 10: ...pplications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be...

Страница 11: ...n alarm condition Fig 5 Optional hook up using two 2 isolated power supply inputs Only applicable on eFlow4NA8D not evaluated by UL J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC...

Страница 12: ...TRG FACP Fig 9 Normally Closed Non Latching FACP trigger input Fig 10 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 8 Normally Open FACP Latching...

Страница 13: ...eFlowNA8D Series Installation Guide 13 Notes...

Страница 14: ...14 eFlowNA8D Series Installation Guide Notes...

Страница 15: ...8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 15 5 x 12 x 4...

Страница 16: ...emote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Отзывы: