Altronix eFlow102NA8D Скачать руководство пользователя страница 4

 

- 4 - 

eFlowNA8D Series Installation Guide

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, 

The Canadian Electrical Code, Part I, Part II, and with all local codes and authorities having jurisdiction. 

The product must be located indoors within the protected premises. 

 

Power Supply Board LED Diagnostics 

(pg. 6)

 

Access Power Controller LED Diagnostics 

(pg. 6)

 

Power Supply Board Terminal Identification 

(pg. 6)

 

Access Power Controller Terminal Identification 

(pg. 6)

 

Power Supply Board Stand-by Battery Specifications 

(pg. 3)

 

Power Supply Board Output Voltage Settings 

(pg. 7)

 

Access Power Controller Typical Application Diagram 

(pg. 7)

 

FACP/Optional Power Supply Hook-up Diagrams 

(pgs. 10-11)

1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in 

 

the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the 

 

enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two 

 

holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure’s upper 

 

keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 

 

(Enclosure Dimensions, pg. 11)

. Secure enclosure to earth ground. 

2.  Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, N] 

(Fig. 3, pg. 8)

 

Do not use terminal marked [G]. Use 14 AWG or larger for all power connections. Secure green wire lead 

 

attached to the chassis to earth ground. The AC LED (Green) will illuminate, indicating power is present. 

 

This light can be seen through the LED lens on the door of the enclosure

 

Keep power-limited wiring separate from non power-limited wiring. 

 

Minimum 0.25” spacing must be provided 

(Fig. 3, pg. 8)

.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 

 

equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified 

 

service personnel.

3.  Select desired DC output voltage by setting SW1 to the appropriate position on the power supply board 

 

(eFlow4NA8D and eFlow6NA8D) 

(Fig. 1, pg. 7). 

eFlow102NA8D power supply is factory set at 12VDC. 

 

eFlow104NA8D power supply is factory set at 24VDC.

4.  Measure the output voltage of the unit before connecting any devices to ensure proper operation.

 

Improper or high voltage will damage these devices.

5. 

Output options 

(Fig. 2, pg. 7)

:

 

The unit will provide eight (8) switched power outputs.

 

(a)  Fail-Safe Switched Power outputs: 

 

    For Fail-Safe operation connect the positive (+) input of the access control devices to terminal 

 

    marked [NC]. Connect the negative (–) input of the access control devices to terminal marked [COM].

 

(b)  Fail-Secure Switched Power outputs:

 

    For Fail-Secure operation connect the positive (+) input of the access control devices to terminal 

 

    marked [NO]. Connect the negative (–) input of the access control devices to terminal marked [COM].

6. 

ACM8CB Auxiliary Power outputs (unswitched):

 

Connect access control devices that require constant power to terminals marked [C] positive (+) and 

 

[COM] negative (–). Outputs can be used to provide power for card readers, keypads etc.

 

eFlow Auxiliary outputs (unswitched):

 

For auxiliary device connection this output will not be affected by Low Power Disconnect or 

 

Fire Alarm Interface. Connect device to terminals marked [+ AUX – ] 

(Fig. 3, pg. 8).

7. 

Input trigger options 

(Fig. 2, pg. 7)

:

 

(a)  Normally Open [NO] input trigger:

 

    Inputs 1-8 are activated by normally open or open collector sink inputs. Connect access control panel 

 

    outputs, keypads, push buttons, REX PIRs, etc. to terminals marked [IN] and [GND]. 

 

(b)  Open Collector Sink inputs:

 

    Connect the access control panel open collector sink positive (+) to terminals marked [IN] and the 

 

    negative (–) to terminals marked [GND].

Содержание eFlow102NA8D

Страница 1: ...A8D 4A 12VDC or 24VDC Eight 8 PTC Outputs eFlow6NA8D 6A 12VDC or 24VDC Eight 8 PTC Outputs eFlow102NA8D 10A 12VDC Eight 8 PTC Outputs eFlow104NA8D 10A 24VDC Eight 8 PTC Outputs eFlowNAD8 Series Access...

Страница 2: ...mum Supply Current for Main and Aux Outputs A PTC Protected Power Limited Outputs Current per ACM8CB output A ACM8CB Board Input Fuse Rating ACM8CB Board Output PTC Rating DC AUX 12VDC Output Range V...

Страница 3: ...output voltage and supply current refer to eFlowNA8D Series Configuration Chart pg 2 Auxiliary Power Limited output rated 1A unswitched Overvoltage protection Built in charger for sealed lead acid or...

Страница 4: ...ovided Fig 3 pg 8 CAUTION Do not touch exposed metal parts Shut branch circuit power before installing or servicing equipment There are no user serviceable parts inside Refer installation and servicin...

Страница 5: ...leads included Use batteries Casil CL1270 12V 7AH CL12120 12V 12AH CL12400 12V 40AH CL12650 12V 65AH batteries or UL recognized BAZR2 and BAZR8 batteries of an appropriate rating 11 Battery and AC Sup...

Страница 6: ...8 pg 10 or Normally Closed Fig 10 pg 10 latching operation it is necessary to reset the Fire Alarm Disconnect by activating the Normally Closed reset switch Output Voltage Test Under normal load cond...

Страница 7: ...Access Power Controller Terminal Legend Function Description Power 12VDC or 24VDC from power supply charger factory connected These terminals are paralleled to the Control terminals Control These ter...

Страница 8: ...C NO COM OUTPUT 2 IN GND 1 IN GND 2 IN GND 3 IN GND 4 IN GND 5 IN GND 6 IN GND 7 MAIN IN GND 8 LED2 LED3 LED4 LED5 LED6 LED7 LED8 J2 FACP NC C NO COM OUTPUT 3 NC C NO COM OUTPUT 4 NC C NO COM OUTPUT 5...

Страница 9: ...RET NO C NC FACP INTERFACE Power Control F1 F2 F3 F4 F5 F6 F7 F8 MAIN TRG FACP 1 2 3 4 1 2 3 4 O N O N 1 2 3 4 1 2 3 4 O N O N Green Flying Lead Unswitched 120VAC power mains non power limited Optiona...

Страница 10: ...pplications use of conduit is optional All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire or equivalent substitute Optional UL Listed battery enclosure must be...

Страница 11: ...n alarm condition Fig 5 Optional hook up using two 2 isolated power supply inputs Only applicable on eFlow4NA8D not evaluated by UL J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC...

Страница 12: ...TRG FACP Fig 9 Normally Closed Non Latching FACP trigger input Fig 10 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 8 Normally Open FACP Latching...

Страница 13: ...eFlowNA8D Series Installation Guide 13 Notes...

Страница 14: ...14 eFlowNA8D Series Installation Guide Notes...

Страница 15: ...8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 15 5 x 12 x 4...

Страница 16: ...emote control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output...

Отзывы: