background image

 

- 4 - 

eFlowNBV - Power Supply/Chargers

Stand-by Specifications:

eFlow3NBV:

Battery

Burg. Applications

4 hr. Stand-by/15 min. Alarm

Fire Applications

24 hr. Stand-by/5 min. Alarm

Access Control

ApplicationsStand-by

7AH

0 .4A/2A

1 .5 Hours/2A

12AH

1A/2A

0 .3A/2A

3 .5 Hours/2A

40AH

2A/2A

1 .2A/2A

Over 4 Hours/2A

65AH

2A/2A

1 .5A/2A

Over 4 Hours/2A

eFlow4NBV:

Battery

Burg. Applications

4 hr. Stand-by/15 min. Alarm

Fire Applications

24 hr. Stand-by/5 min. Alarm

Access Control

Applications Stand-by

7AH

0 .4A/4A

15 Mins ./4A

12AH

1A/4A

0 .3A/4A

35 Mins ./4A

40AH

4A/4A

1 .2A/4A

Over 4 Hours/4A

65AH

4A/4A

1 .5A/4A

Over 4 Hours/4A

eFlow6NBV:

Battery

Burg. Applications

4 hr. Stand-by/15 min. Alarm

Fire Applications

24 hr. Stand-by/5 min. Alarm

Access Control

Applications Stand-by

7AH

0 .4A/6A

10 Mins ./6A

12AH

1A/6A

0 .3A/6A

35 Mins ./6A

40AH

6A/6A

1 .2A/6A

Over 4 Hours/6A

65AH

6A/6A

1 .5A/6A

Over 4 Hours/6A

eFlow102NBV:

Battery

Burg. Applications

4 hr. Stand-by/15 min. Alarm

Fire Applications

24 hr. Stand-by/5 min. Alarm

Access Control

Applications Stand-by

7AH

0 .4A/10A

N/A

5 Mins ./10A

12AH

1A/10A

0 .3A/10A

15 Mins ./10A

40AH

6A/10A

1 .2A/10A

Over 2 Hours/10A

65AH

6A/10A

1 .5A/10A

Over 4 Hours/10A

eFlow104NBV:

Battery

Burg. Applications

4 hr. Stand-by/15 min. Alarm

Fire Applications

24 hr. Stand-by/5 min. Alarm

Access Control

Applications Stand-by

7AH

0 .4A/10A

N/A

5 Mins ./10A

12AH

1A/10A

0 .3A/10A

15 Mins ./10A

40AH

6A/10A

1 .2A/10A

Over 2 Hours/10A

65AH

6A/10A

1 .5A/10A

Over 4 Hours/10A

Содержание eFlow Series

Страница 1: ...1418 Power Supply Charger Boards Installation Guide Models Include eFlow3NBV 12VDC or 24VDC 2A eFlow4NBV 12 or 24VDC 4A eFlow6NBV 12 or 24VDC 6A eFlow102NBV 12VDC 10A eFlow104NBV 24VDC 10A More than j...

Страница 2: ...ew pg 3 Specifications pg 3 Features pg 3 Stand by Specifications pg 4 Installation Instructions pg 5 eFlowNBV configuration pg 5 Wiring pg 6 Maintenance pg 6 LED Diagnostics pg 6 Terminal Identificat...

Страница 3: ...y Backup Built in charger for sealed lead acid or gel type batteries Automatic switch over to stand by battery when AC fails Transfer to stand by battery power is instantaneous with no interruption Fi...

Страница 4: ...urg Applications 4 hr Stand by 15 min Alarm Fire Applications 24 hr Stand by 5 min Alarm Access Control Applications Stand by 7AH 0 4A 6A 10 Mins 6A 12AH 1A 6A 0 3A 6A 35 Mins 6A 40AH 6A 6A 1 2A 6A Ov...

Страница 5: ...uxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm Interface Connect device to terminals marked AUX Fig 1f pg 5 6 For Access Control applications batteri...

Страница 6: ...AC 50 60Hz to these terminals L to hot N to neutral G to ground Fig 1a pg 5 DC Fig 1h pg 5 eFlow3NBV 12VDC or 24VDC 2A continuous output power limited output eFlow4NBV 12VDC or 24VDC 4A continuous out...

Страница 7: ...x is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Ma...

Страница 8: ...te control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output st...

Отзывы: