eFlowNBV - Power Supply/Chargers 

- 5 -

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, the Canadian 
Electrical Code and with all local codes and authorities having jurisdiction . Product is intended for indoor use only . 
1 .  Mount the eFlowNBV power supply/charger in desired location/enclosure (mounting hardware included) . 
 

Use metal standoffs for the bottom mounting holes to provide sufficient grounding for the board . 

2 .  Set desired DC output voltage by setting SW1 to the appropriate position on the power supply board 
 

(Fig. 1i, pg. 5) . 

3 .  Connect unswitched AC power (220VAC, 50/60Hz) to terminals marked [L, G, N] (Fig. 1a, pg. 5) . 
 

Use 14 AWG or larger for all power connections . Secure green wire lead to earth ground .

 

Keep power-limited wiring separate from non power-limited wiring (220VAC, 50/60Hz Input, 

 

DC Output (refer to Specifications chart pg. 3), Battery Wires). 

 

Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts.

 

Shut branch circuit power before installing or servicing equipment. 

 

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

4 .  Measure output voltage before connecting devices . This helps avoiding potential damage .
5 .  Connect devices to be powered to terminals marked [– DC +] (Fig. 1h, pg. 5) .
 

For auxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm 

 

Interface . Connect device to terminals marked [+ AUX –] (Fig. 1f, pg. 5) .

6 .  For Access Control applications batteries are optional . When batteries are not used, a loss of AC will result 
 

in the loss of output voltage . When the use of stand-by batteries is desired, they must be lead acid or gel type .

 

Connect battery to terminals marked [– BAT +] (Fig. 1g, pg. 5) . Use two (2) 12VDC batteries connected in 

 

series for 24VDC operation (battery leads included) . Use batteries - Casil CL1270 (12V/7AH), CL12120 

 

(12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 batteries of 

 

an appropriate rating .

 

Note: Separate enclosure must be used for housing 40AH or 65AH batteries .

7 .  Connect appropriate signaling notification devices to AC FAIL & BAT FAIL (Fig. 1b, pg. 5) supervisory 
 

relay outputs .

8 .  To delay AC reporting for 2 hrs ., set SW2 to appropriate DIP switch position [AC Delay] (Fig. 1c, pg. 5) .
9 .  To enable or disable Low Output Power Shutdown set SW2 to appropriate DIP switch position [Shutdown] 
 

(Fig. 1c, pg. 5) .

10 .  A short or NO or NC input triggers FACP [Trigger EOL Shutdown] (Fig. 1d, pg. 5) .
11 .  Place a jumper for non-latching FACP . A momentary short on these terminals resets FACP latching 
 

[Trigger EOL Shutdown] (Fig. 1e, pg. 5) .

Fig. 1 - eFlowNBV configuration

L

G

N

NC  C  NO  NC  C  NO

BAT FAIL

AC FAIL

--- 

 DC  

+

AC

AC1

DC

--- 

BAT 

+

+ AUX –

TRIGGER EOL

SUPERVISED

Input

Fuse

Battery Fuse

NO        GND

RESET

OFF   

--- 

  24

V

ON   

--- 

  12

V

enable
disable

1 min.
2 hr.

AC DELAY   SHUTDOWN

O

N

1a

1b

1g

1h

1e

1f

1d

1c

1i

ON

Содержание eFlow Series

Страница 1: ...1418 Power Supply Charger Boards Installation Guide Models Include eFlow3NBV 12VDC or 24VDC 2A eFlow4NBV 12 or 24VDC 4A eFlow6NBV 12 or 24VDC 6A eFlow102NBV 12VDC 10A eFlow104NBV 24VDC 10A More than j...

Страница 2: ...ew pg 3 Specifications pg 3 Features pg 3 Stand by Specifications pg 4 Installation Instructions pg 5 eFlowNBV configuration pg 5 Wiring pg 6 Maintenance pg 6 LED Diagnostics pg 6 Terminal Identificat...

Страница 3: ...y Backup Built in charger for sealed lead acid or gel type batteries Automatic switch over to stand by battery when AC fails Transfer to stand by battery power is instantaneous with no interruption Fi...

Страница 4: ...urg Applications 4 hr Stand by 15 min Alarm Fire Applications 24 hr Stand by 5 min Alarm Access Control Applications Stand by 7AH 0 4A 6A 10 Mins 6A 12AH 1A 6A 0 3A 6A 35 Mins 6A 40AH 6A 6A 1 2A 6A Ov...

Страница 5: ...uxiliary device connection this output will not be affected by Low Power Disconnect or Fire Alarm Interface Connect device to terminals marked AUX Fig 1f pg 5 6 For Access Control applications batteri...

Страница 6: ...AC 50 60Hz to these terminals L to hot N to neutral G to ground Fig 1a pg 5 DC Fig 1h pg 5 eFlow3NBV 12VDC or 24VDC 2A continuous output power limited output eFlow4NBV 12VDC or 24VDC 4A continuous out...

Страница 7: ...x is not responsible for any typographical errors 140 58th Street Brooklyn New York 11220 USA phone 718 567 8181 fax 718 567 9056 website www altronix com e mail info altronix com Lifetime Warranty Ma...

Страница 8: ...te control of up to 2 two Altronix eFlow power output s via LAN and or WAN Monitor real time diagnostics DC output voltage output current AC battery status service input trigger state change output st...

Отзывы: