- 8 -
eFlow104NK8(D)QP Installation Guide
Fig. 4 -
eFlow104NK8(D)QP
DC Output to devices
(
eFlow104NK8QP
- non power-limited,
eFlow104NK8QPD
- power-limited)
eFlow104NB
Power Supply
– DC
+
– BAT
+
L G N
Tamper Switch
AC FAIL NC C NC C BAT FAIL
+ INP1 - + INP2- +BAT IN- +BAT OUT-
BAT AC
NC C NC
C
LINQ8PD(CB)
AC FAIL NC C NO NC C NO BAT FAIL
PTC
Protected
Outputs on
eFlow104NK8QPD
-- OUT1 +
-- OUT2 +
-- OUT3 +
-- OUT4 +
-- OUT5 +
-- OUT6 +
-- OUT7 +
-- OUT8 +
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
~
Power Output
Factory wired to
LINQ8PD(CB) and VR6
(non power-limited)
Battery Output
Factory wired to
LINQ8PD(CB)
(non power-limited)
24VDC from
eFlow104NB
12VDC from VR6
(mounted under LINQ8PD(CB)
Battery input (factory wired)
Connect batteries
Factory wired supervisory connections (power-limited)
Factory wired supervisory
connections (power-limited)
FACP Interface
(power-limited)
Supervision
(power-limited)
Optional Rechargeable Stand-by Battery
for UL294 Applications
Note: 12V batteries required for
ULC-S319 installations.
Optional Rechargeable Stand-by Battery
for UL294 Applications
Note: 12V batteries required for
ULC-S319 installations.
CAUTION: Use two (2) 12VDC stand-by batteries.
Keep power-limited wiring separate from non power-limited.
Use minimum 0.25” spacing.
12AH Rechargeable batteries are the largest batteries that
can fit in this enclosure.
A UL listed external battery enclosure must be used if using
40AH or 65AH batteries.
Tamper Switch
(included)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Fig. 4a
Содержание eFLOW eFlow104NKA8D Series