eFlow104NK8(D)QP Installation Guide
- 5 -
13.
Installation of tamper switch:
Mount UL Listed tamper switch (Altronix model TS112 or equivalent) at the top of the enclosure. Slide the
tamper switch bracket onto the edge of the enclosure approximately 2” from the right side
(Fig. 6a, pg. 8)
.
Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting
device. To activate alarm signal open the door of the enclosure.
Wiring:
Use 18 AWG or larger for all low voltage power connections.
Note:
Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test:
Under normal load conditions, the DC output voltage should be checked for proper
voltage level eFlow104NB: 24VDC nominal rated @ 10A max.
Battery Test:
Under normal load conditions check that the battery is fully charged, check specified voltage
(24VDC @ 26.4) both at battery terminal and at the board terminals marked [– BAT +] to ensure that there is no
break in the battery connection wires.
Note:
Maximum charging current under discharges is 1.54A.
Note:
Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Fig. 2 -
eFlow104N Board Configuration
2a
2b
2g
2h
2e 2f
2d
2c
– DC
+
– BAT
+
L G N
NC C NO NC C NO
AC FAIL
BAT FAIL
TRIGGER EOL
SUPERVISED
AC DC
AC1
NO GND
RESET
+ AUX -
1 min enable
2 hr disable