background image

eFlow104NK8QP

  -  12VDC or 5VDC up to 6A and/or 24VDC up to 10A (240W total power) selectable by output.
  -  Eight (8) fuse protected outputs.
  -  Management interface for eFlow power supply/charger.
  -  Two (2) network controlled Form “C” relays. 
  -  Built-in Charger for sealed lead acid or gel type batteries.

eFlow104NKA8D

  -  12VDC or 5VDC up to 6A and/or 24VDC up to 10A (240W total power) selectable by output.
  -  Eight (8) Class 2 power-limited PTC protected outputs.
  -  Management interface for eFlow power supply/charger.
  -  Two (2) network controlled Form “C” relays. 
  -  Built-in Charger for sealed lead acid or gel type batteries.

eFlow104NK8QP Series

Networkable Dual Output 
Power Supply/Chargers

Models Include:

Rev. eFlow104NK8QP-072420

More than just power.

TM

Installing Company:  _______________ Service Rep. Name:  __________________________________  

Address:  _____________________________________________  Phone #:  __________________

Installation Guide

Содержание eFLOW eFlow104NKA8D Series

Страница 1: ...power selectable by output Eight 8 Class 2 power limited PTC protected outputs Management interface for eFlow power supply charger Two 2 network controlled Form C relays Built in Charger for sealed l...

Страница 2: ...4VDC Altronix power supplies to eight 8 independently controlled fuse eFlow104NK8QP or PTC eFlow104NK8DQP protected outputs Networkable power distribution module facilitates monitoring reporting and c...

Страница 3: ...il supervision form C contacts Battery fail presence supervision form C contacts Low power shutdown Shuts down DC output terminals if battery voltage drops below 71 73 for 12V units and 70 75 for 24V...

Страница 4: ...es are required for Canadian installations ULC S319 When batteries are not used a loss of AC will result in the loss of output voltage When the use of stand by batteries is desired they must be lead a...

Страница 5: ...should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper voltage level eFlow104NB...

Страница 6: ...these terminals L to hot N to neutral non power limited Fig 2a pg 5 DC 24VDC nominal 10A continuous output power limited output Fig 2h pg 5 Trigger EOL Supervised Fire Alarm Interface trigger input fr...

Страница 7: ...or Tamper Contact rating 1A 30VDC L AC Fail NC C Relay3 Programmable for AC Fail or AC Fail Battery Fail reporting Contact rating 1A 30VDC power limited M OUT1 to OUT8 24VAC 28VAC or 12VDC 24VDC cont...

Страница 8: ...t batteries Factory wired supervisory connections power limited Factory wired supervisory connections power limited FACP Interface power limited Supervision power limited Optional Rechargeable Stand b...

Страница 9: ...Click the button labeled Submit Network Settings A dialog box will display New network settings will take effect after the server is rebooted Click OK DHCP A After selecting DHCP in the IP Address Met...

Страница 10: ...e connected to any DC power supply ies or eFlow power supply ies being monitored prior to programing Factory Default settings IP Address 192 168 168 168 User Name admin Password admin 1 Set the static...

Страница 11: ...eFlow104NK8 D QP Installation Guide 11 Notes...

Страница 12: ...1 8mm 1 25 31 8mm 0 79 20 1mm 0 91 23 1mm 0 91 23 1mm 15 5 393 7mm 1 1 27 9mm 1 1 27 9mm 1 1 27 9mm 12 23 310 6mm 2 0 50 8mm 2 0 50 8mm 1 25 31 8mm 1 25 31 8mm Enclosure Dimensions BC400 15 5 x 12 x 4...