AL125UL Series

Overview:

Altronix AL125UL Series power-limited Power Supply/Chargers convert 115VAC 50/60Hz input into two 
individually PTC protected auto-resettable 12VDC or 24VDC outputs (see specifications). They are intended 
for use in applications requiring UL Listing for Access Control (UL294) and applications requiring an interface 
with Fire Alarm Control Panels.

Specifications:

*Note: 

When unit is powered by battery back up (AC Fail condition), the voltage range is 9.3V-13.2V and 

 

19.55V-26.4V for 12 and 24 volt operation respectively. 

Power Supply Output Specifications:

 (AL125UL, AL125ULX)

Output VDC

Switch Position

Max. Stand-by

Load DC

Max. Alarm

Load DC

Battery

(optional)

12VDC

SW2 OFF

1A

1A

12VDC

24VDC

SW2 ON

1A

1A

24VDC

Power Supply Output Specifications:

 (AL125ULE, AL125ULP)

Output VDC

Switch Position

Max. Stand-by

Load DC

Max. Alarm

Load DC

Battery

(optional)

12VDC

SW2 OFF

1A

1A

12VDC

24VDC

SW2 ON

0.5A

0.5A

24VDC

Stand-by Specifications:

Output

4hr. of Stand-by &

5 min. of Alarm

Output

4hr. of Stand-by &

5 min. of Alarm

12VDC / 4AH Battery

0.5A / 1A

12VDC / 7AH Battery

1A / 1A

24VDC / 4AH Battery

0.5A / 1A

24VDC / 7AH Battery

1A / 1A

Agency Listings:

•  UL Listed for Access Control Systems (UL294).
  CUL Listed - CSA Standard C22.2 No.205-M1983, 
  Signal Equipment.
•  MEA - NYC Department of Buildings Approved.
•  NFPA 101 (Life Safety).

Input:

•   AL125UL, AL125ULX: 115VAC, 50/60 Hz, 0.6A.
•  AL125ULE, AL125ULP: 24VAC @ 40VA.

Output:

•  Two (2) 12VDC or 24VDC 
  Class 2 Rated Power-Limited Outputs.
•  1A total supply current @ 12VDC or 24VDC 
  (AL125UL & AL125ULX).
•  1A total supply current @ 12VDC, 0.5A total 
  supply current @ 24VDC
  (AL125ULP & AL125ULE).
•  Filtered and electronically regulated output.*

Battery Backup:

•  Built-in charger for sealed lead acid or 
  gel type batteries.
•  Maximum charge current: 400mA.
•  Automatic switch over to stand-by battery when 
  AC fails.

Special Features:

•  AC power and unit status indicator on 
  the front panel.
•  Normally Open [NO] trigger input.
•  Supervised Fire Alarm Disconnect 
  (Latching w/reset or Non-Latching).

Enclosure Dimensions 

(H x W x D)

:

AL125UL, AL125ULE, AL125ULP

8.5” x 7.5” x 3.5” (215.9mm x 190.5mm x 88.9mm).

AL125ULX

13.5” x 13” x 3.25” (342.9mm x 330.2mm x 82.6mm)

Содержание AL125UL Series

Страница 1: ...ludes power supply transformer cam lock and enclosure 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm Accommodates up to two 2 12VDC 7AH batteries AL125ULE includes power supply cam lock and enclosure 8 5...

Страница 2: ...hr of Stand by 5 min of Alarm Output 4hr of Stand by 5 min of Alarm 12VDC 4AH Battery 0 5A 1A 12VDC 7AH Battery 1A 1A 24VDC 4AH Battery 0 5A 1A 24VDC 7AH Battery 1A 1A Agency Listings UL Listed for Ac...

Страница 3: ...ces to the terminals marked COM and STRIKE Fig 1 Application Diagram pg 5 6 Connect normally open access control device i e card reader request to exit device access control system to the terminals ma...

Страница 4: ...nel Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper volta...

Страница 5: ...Device Normally Open Reset Device 2 2K EOL supplied MAG LOCK NC FACP NO FACP Note If 2 2K resistor is not installed unit will be in alarm condition Card Reader ON ON Transformer Stand by Batteries Fi...

Страница 6: ...6 AL125UL Series Notes...

Страница 7: ...5mm x 88 9mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 125 28 575mm 1 25 4mm 1 25 4mm 1 25 4mm 5 25 133 35mm 6 05 153 67mm 6 05 153 67mm 3 5 88 9mm 3 5 88 9mm 7 25 184 15mm 2 50 8mm 2 50 8mm 8 125 206...

Страница 8: ...de in U S A IIAL125ULseries C20R MEMBER Enclosure Dimensions H x W x D AL125ULX 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 1...

Отзывы: