background image

 

- 4 - 

AL125UL Series

The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user 
to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may 
be of sufficient magnitude to constitute an electric shock.

The exclamation point within an equilateral triangle is intended to alert the user to the presence of 
important operating and maintenance (servicing) instructions in the literature accompanying the 
appliance.

CAUTION: To reduce the risk of electric shock do not open 
enclosure. There are no user serviceable parts inside. Refer servicing 
to qualified service personnel.

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: 

Under normal load conditions, the DC output voltage should be checked for proper 

 

voltage level (Power Supply Output Specifications Table, pg. 2).

Battery Test

Under normal load conditions check that the battery is fully charged, check specified 

 

voltage both at battery terminal and at the board terminals marked [+ BAT –] to 

 

ensure that there is no break in the battery connection wires.

Note: 

Maximum charging current under discharge is 400mA.

Note: 

Expected battery life is 5 years; however, it is recommended changing batteries in 

 

4 years or less if needed.

LED Diagnostics:

Red

Power Supply Status

ON

Normal function.

OFF

No DC output.

Slow Blink

Loss of AC.

Rapid Blink

Unit is triggered, awaiting reset. Fire alarm interface activated.

Содержание AL125UL Series

Страница 1: ...ludes power supply transformer cam lock and enclosure 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm Accommodates up to two 2 12VDC 7AH batteries AL125ULE includes power supply cam lock and enclosure 8 5...

Страница 2: ...hr of Stand by 5 min of Alarm Output 4hr of Stand by 5 min of Alarm 12VDC 4AH Battery 0 5A 1A 12VDC 7AH Battery 1A 1A 24VDC 4AH Battery 0 5A 1A 24VDC 7AH Battery 1A 1A Agency Listings UL Listed for Ac...

Страница 3: ...ces to the terminals marked COM and STRIKE Fig 1 Application Diagram pg 5 6 Connect normally open access control device i e card reader request to exit device access control system to the terminals ma...

Страница 4: ...nel Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper volta...

Страница 5: ...Device Normally Open Reset Device 2 2K EOL supplied MAG LOCK NC FACP NO FACP Note If 2 2K resistor is not installed unit will be in alarm condition Card Reader ON ON Transformer Stand by Batteries Fi...

Страница 6: ...6 AL125UL Series Notes...

Страница 7: ...5mm x 88 9mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 125 28 575mm 1 25 4mm 1 25 4mm 1 25 4mm 5 25 133 35mm 6 05 153 67mm 6 05 153 67mm 3 5 88 9mm 3 5 88 9mm 7 25 184 15mm 2 50 8mm 2 50 8mm 8 125 206...

Страница 8: ...de in U S A IIAL125ULseries C20R MEMBER Enclosure Dimensions H x W x D AL125ULX 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 1...

Отзывы: