Installation Instructions:

The units should be installed in accordance with article 760 of The National Electrical Code and NFPA 72 as 
well as all applicable Local Codes.
See Terminal Identification Chart on page 3 for a description of each terminal function.
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 
  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 
  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 
  two holes. Remove the enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper 
  keyholes over the two upper screws. Install two lower screws and make sure to tighten all screws
  (Enclosure Dimensions, pgs. 7-8). Secure green wire lead to the earth ground.
2. Power connections:
 a. 

AL125UL, AL125ULX: Connect 115VAC 50/60Hz to the black and white flying leads of the transformer.

    Use 18 AWG or larger for all power connections (Battery, AC input, DC outputs). 
    Use 22 AWG to 18 AWG for power-limited circuits (Trigger inputs, Dry outputs, DC outputs).
 b. 

AL125ULE, AL125ULP: Connect 24VAC from UL Listed 40VA plug-in transformer (included with 

    AL125ULP) to terminals marked [XFMR]. 
 

Keep power-limited wiring separate from non power-limited wiring (115VAC, 50/60Hz Input, 

  Battery Wires). Minimum 0.25” spacing must be provided.
  CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 
  equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified 
  service personnel.
3.

 Measure output voltage before connecting any devices to ensure proper operation. 

  Improper or high voltage will damage these devices.
4. Set the desired DC output voltage by setting switch SW2 (Fig. 1a - Application Diagram, pg. 5) to the 
  appropriate position (Power Supply Output Specifications Table, pg. 2).
5. Connect Fail-Safe locking devices to the terminals marked [COM –] and [LOCK+]. Connect Fail-Secure 
  locking devices to the terminals marked [COM –] and [] (Fig. 1 - Application Diagram, pg. 5). 
6. Connect normally open access control device (i.e. card reader, request to exit device, access control system) 
  to the terminals marked TRG INPUT [NO, GND] (Fig. 1 - Application Diagram, pg. 3). 
7. Connect FACP interface to the terminals marked [FACP1 and FACP2]. Wire the 2.2K resistor (supplied) in 
  series for a normally closed input or in parallel for a normally open input (Fig. 1 - Application Diagram, pg. 5). 
  
If  required, set the latching FACP interface mode by turning SW1 ON (Fig. 1a - Application Diagram, pg. 5)
  and connect a normally open reset device to the terminals marked RESET [NO, GND].
 

Note: If 2.2K resistor is not installed unit will be in alarm condition.

8. Connect battery to terminals marked [+ BAT –] (battery leads included). 
  Use two (2) 12VDC batteries connected in series for 24VDC operation.
 

Note: For Access Control applications batteries are optional. 

  When batteries are not used, a loss of AC will result in the loss of output voltage. 
  When the use of stand-by batteries is desired, they must be lead acid or gel type.
9. Please ensure that the cover is secured with the provided cam lock.

Terminal Identification:

Terminal Legend Function/Description
XFMR

Low voltage transformer connections.

+ AUX –

Aux. power output terminals. These terminals supply 12VDC or 24VDC not affected by 
trigger, reset or fire alarm interface.

LOCK +

COM –

Switched power output. Fail-Safe [LOCK +] supplies positive power when unit is not 
triggered and FACP interface is inactive. Fail-Secure [] supplies positive power 
when unit is triggered and/or fire alarm interface is activated. 
[COM –] supplies negative power.

FACP1
FACP2

Supervised by 2.2K end of line resistor FACP interface. Short or open will cause power to be 
dropped to terminal marked [LOCK +] and supply power to terminal marked []. 
Condition can be maintained even after restoration of the circuit (latching mode).

TRG INPUT
NO, GND

Short between these two terminals will cause power to be dropped to the terminal marked 
[LOCK+] and supplied to the terminal marked [].

RESET
NO, GND

Momentary short between these terminals would end latching FACP interface condition.
Feature active only if latching FACP is selected (SW1 ON).

+ BAT –

Stand-by battery connections.

Содержание AL125UL Series

Страница 1: ...ludes power supply transformer cam lock and enclosure 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm Accommodates up to two 2 12VDC 7AH batteries AL125ULE includes power supply cam lock and enclosure 8 5...

Страница 2: ...hr of Stand by 5 min of Alarm Output 4hr of Stand by 5 min of Alarm 12VDC 4AH Battery 0 5A 1A 12VDC 7AH Battery 1A 1A 24VDC 4AH Battery 0 5A 1A 24VDC 7AH Battery 1A 1A Agency Listings UL Listed for Ac...

Страница 3: ...ces to the terminals marked COM and STRIKE Fig 1 Application Diagram pg 5 6 Connect normally open access control device i e card reader request to exit device access control system to the terminals ma...

Страница 4: ...nel Maintenance Unit should be tested at least once a year for the proper operation as follows Output Voltage Test Under normal load conditions the DC output voltage should be checked for proper volta...

Страница 5: ...Device Normally Open Reset Device 2 2K EOL supplied MAG LOCK NC FACP NO FACP Note If 2 2K resistor is not installed unit will be in alarm condition Card Reader ON ON Transformer Stand by Batteries Fi...

Страница 6: ...6 AL125UL Series Notes...

Страница 7: ...5mm x 88 9mm 1 25 31 75mm 1 25 31 75mm 1 25 31 75mm 1 125 28 575mm 1 25 4mm 1 25 4mm 1 25 4mm 5 25 133 35mm 6 05 153 67mm 6 05 153 67mm 3 5 88 9mm 3 5 88 9mm 7 25 184 15mm 2 50 8mm 2 50 8mm 8 125 206...

Страница 8: ...de in U S A IIAL125ULseries C20R MEMBER Enclosure Dimensions H x W x D AL125ULX 13 5 x 13 x 3 25 342 9mm x 330 2mm x 82 6mm 1 40 36mm 1 40 36mm 4 85 123mm 4 85 123mm 1 40 36mm 1 40 36mm 5 10 130mm 5 1...

Отзывы: