- 6 -
Wiring:
USE 14 AWG or larger for all power connections.
Note: Take care to keep power limited circuits separate from non-power limited wiring (115VAC, Battery).
Maintenance:
Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at
battery terminal and at the board terminals marked [+ BAT -] to insure there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 3.6 amp.
Note: Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed.