background image

2. Secure enclosure to earth ground. Connect AC power (115VAC / 60 Hz to terminals marked [L, G, N] (Fig. 1, pg. 3).

Use 14 AWG or larger for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power 
limited circuits (AC Fail/Low Battery reporting).  Keep power limited wiring separate from non-power limited wiring 
(115VAC / 60Hz Input, Battery Wires). Minimum .25” spacing must be provided.

3. Measure output voltage before connecting device. This helps avoid potential damage. 

When servicing the unit, AC mains should be removed.

4. Connect devices to be powered:

a. For AL1024ULX Power Supply connect devices to terminals marked [- DC +] (Fig. 1, pg. 3)
b. For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 4 marked 

[1P & 1N thru 4P & 4N] (Fig. 2A & 2B, pg. 5) or 1 to 8 marked [1P & 1N thru 8P & 8N] (Fig. 3A & 3B, pg. 5)
carefully observing correct polarity.

5. For Access Control applications, batteries are optional.  When batteries are not used a loss of AC will result in 

the loss of output voltage.  When the use of stand-by batteries is desired, they must be lead acid or gel type.

6. Connect appropriate signaling notification devices to terminals marked [AC FAIL & BAT FAIL] (Fig. 1, pg. 3)

supervisory relay outputs.
Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay must be used to 
provide a visual indication of AC power on.

7. Please insure that the cover is secured with the provided Key Lock.

LED Diagnostics:

AL1024ULXB -  Power Supply Board

Red (DC)

Green (AC)

Power Supply Status 

ON

ON

Normal operating condition

ON

OFF

Loss of AC, Stand-by battery supplying power

OFF

ON

No DC output

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

Terminal Identification:

AL1024ULXB - Power Supply Board

Terminal Legend

Function/Description

L, G, N

Connect 115VAC to these terminals: L to Hot, N to Neutral, G to ground.

- DC +

24VDC @ 8 amp continuous, 10 amp in alarm non-power limited output, 10 amp continuous when 
batteries are not used. 

AC FAIL

Used to notify loss of AC power, e.g. connect to annunciator/alarm panel. Relay normally

N.O., C, N.C.

energized when AC power is present. Contact rating 1 amp @ 28VDC.
AC or brownout fail is reported within 0ne (1)  minute of event. To delay reporting of up to 
6 hrs., cut “AC delay” jumper and reset power to unit.

BAT FAIL

Used to indicate low battery condition, e.g. connect to alarm panel. Relay normally energized

N.O., C, N.C.

when DC power is present. 
Contact rating 1 amp @ 28VDC.
A removed battery is reported within 1 minute. Battery reconnection is reported 
within 1 minute. Low battery threshold: @ approximately 21VDC.

+ BAT -

Stand-by battery connections. Maximum charge rate 3.6 amp.

- 4 -

Содержание AL1024ULXPD4

Страница 1: ...ingle Output AL1024ULXPD4 AL1024ULXPD4CB Four 4 Fused Outputs Four 4 PTC Outputs AL1024ULXPD8 AL1024ULXPD8CB Eight 8 Fused Outputs Eight 8 PTC Outputs AL1024ULXPD16 AL1024ULXPD16CB Sixteen 16 Fused Ou...

Страница 2: ...type batteries Automatic switch over to stand by battery when AC fails Maximum charge current 3 6 amp Zero voltage drop when switched over to battery backup Supervision AC fail supervision form C cont...

Страница 3: ...should be installed in accordance with article 760 of The National Electrical Code as well as NFPA 72 and all applicable Local Codes 1 Mount the unit in desired location DC BAT FAIL NO C NC NO C NC B...

Страница 4: ...en used in fire alarm burglar alarm or access control applications AC Fail relay must be used to provide a visual indication of AC power on 7 Please insure that the cover is secured with the provided...

Страница 5: ...ace fuses with the same type and rating 3 5A 250V Fig 2A Fig 3A Power Distribution Module s INPUT LED F1 F2 F3 F4 POWER OUTPUTS 1P 1N 2P 2N 3P 3N 4P 4N Class 2 Rated Power Limited DC Output to devices...

Страница 6: ...load conditions the DC output voltage should be checked for proper voltage level Battery Test Under normal load conditions check that the battery is fully charged check specified voltage both at batt...

Страница 7: ...A G Alarm duration Hours 15 Min 2 Hour Alarm ____________ H H Battery capacity required for Alarm E F G ____________ AH I Total calculated battery capacity D H ____________ AH J Battery capacity requ...

Страница 8: ...com e mail info altronix com Lifetime Warranty Made in U S A IIAL1024ULX series L22E MEMBER 8 875 1 1 3 9 97 13 53 6 625 2 25 3 68 4 56 1 22 1 22 3 5 1 13 25 2 1 22 12 15 5 4 5 2 25 3 68 4 56 1 22 1...

Отзывы: