AL1024ULX Series
- 7 -
Battery Size Calculation Worksheet:
A. AL1024ULX series internal current consumption
(stand-by)
__________________ 0.05 A
B. Load current consumption
(stand-by)
__________________ A
C. Stand-by time required (hours)
__________________ H
D. Battery capacity required for stand-by
(A+B)*C
__________________ AH
E. AL1024ULX series internal power consumption
(Alarm)
__________________ 0.05 A
F. Load current consumption
(Alarm)
__________________ A
G. Alarm duration (Hours; 15 Min. = 0.25 Hour)
(Alarm)
__________________ H
H. Battery capacity required for Alarm
(E+F)*G
__________________ AH
I. Total calculated battery capacity
D+H
__________________ AH
J. Battery capacity required
I*1.8 (safety factor) __________________ AH
Note: AL1024ULX series power supply is designed to work with batteries up to 65AH.
Please note: line [I] must not exceeds 36AH.
You have to reduce either stand-by current consumption or stand-by time in order to comply with requirement.
To determine actual battery size please round line [J] to the nearest larger standard battery size
(e.g. 3.5 AH = 4.0 AH).