background image

 

- 2 - 

AL1024ULX Series

Overview:

Altronix AL1024ULX is a power supply that converts a 115VAC / 60Hz input to a 24VDC regulating output 
(see specifications below). 
The AL1024ULX is the base power supply unit for the UL Listed multi-output power supply/charger 
series: AL1024ULXPD4, AL1024ULXPD4CB, AL1024ULXPD8, AL1024ULXPD8CB, AL1024ULXPD16, 
AL1024ULXPD16CB (Refer to AL1024ULX Series Power Supply Configuration Reference Chart below).

AL1024ULX Series Power Supply Configuration Reference Chart: 

Altronix
Model Number

Accessory Power

Distribution Module(s)

Number of Output(s)

Class 2 Rated

Power-Limited Outputs

Fused Outputs

PTC Outputs

(auto-resettable)

Output Rating (A)

per Output

Agency Listings

UL Listings

and

File Numbers

AL1024ULX(R)

1

10

NFPA 72 Compliant

(Fire-Protective Signaling Service).

UL File # S4707

UL 1481

UL Listed Power 

Supplies for 

Fire Protective 

Signaling Systems.

----------------------------------------

UL 294

 UL Listed for

Access Control 

System Units.

----------------------------------------

“Signal Equipment”

Evaluated to 

CSA Standard 

C22.2 

No.205-M1983

AL1024ULXPD4

PD4UL

4

P

3.5

NFPA 72 Compliant

(Fire-Protective Signaling Service).

AL1024ULXPD4CB

PD4ULCB

4

P

P

2.5

AL1024ULXPD8

PD8UL

8

P

3.5

AL1024ULXPD8CB

PD8ULCB

8

P

P

2.5

AL1024ULXPD16

Two (2)

PD8UL

16

P

3.5

AL1024ULXPD16CB

Two (2)

PD8ULCB

16

P

P

2.5

Do not exceed total output rating of 10A per unit.

Altronix Corp.

140 58th St. Brooklyn, NY

California 

State Fire 

Marshal

Factory 

Mutual

Approved

LISTED

LISTED

Specifications:

Input:

•  Input 115VAC / 60Hz, 4.2A.
•  Input fuse rated @ 5A/250V.

Output:

•  24VDC output. 
•  8A supply current in non-alarm condition with
  10A supply current during alarm for
  Fire Alarm Applications.
  10A supply current for
  Access Control Applications.
•  Filtered and electronically regulated outputs.
•  Short circuit and thermal overload protection.

Battery Backup:

•  Built-in charger for sealed lead acid or
  gel type batteries.
•  Automatic switch over to stand-by battery
  when AC fails.

Battery Backup 

(cont’d.)

:

•  Maximum charge current 3.6A.
•  Zero voltage drop when switched over to 
  battery backup.

Supervision:

•  AC fail supervision (form “C” contacts). 
•  Low battery supervision (form “C” contacts). 
•  Battery presence supervision (form “C” contacts).

LED Indicators:

•  AC input and DC output LED indicators.

Additional Features:

•   Power supply, enclosure, cam lock, and battery leads 
•  All models are available in red enclosure
  (add an “R” suffix to the part #, 
  e.g. AL1024ULXPD8R).

Содержание AL1024ULX

Страница 1: ...24ULXPD4 Four 4 Fuse Protected Outputs AL1024ULXPD8 Eight 8 Fuse Protected Outputs AL1024ULXPD16 Sixteen 16 Fuse Protected Outputs AL1024ULXPD4CB Four 4 PTC Protected Outputs AL1024ULXPD8CB Eight 8 PT...

Страница 2: ...ice AL1024ULXPD4CB PD4ULCB 4 P P 2 5 AL1024ULXPD8 PD8UL 8 P 3 5 AL1024ULXPD8CB PD8ULCB 8 P P 2 5 AL1024ULXPD16 Two 2 PD8UL 16 P 3 5 AL1024ULXPD16CB Two 2 PD8ULCB 16 P P 2 5 Do not exceed total output...

Страница 3: ...6 5 hrs for 24VDC 65AH battery See battery size calculation worksheet for other batteries Page 7 DC BAT BAT FAIL NC C NO NC C NO AC FAIL DC AC L G N 5A 250V 15 AC DELAY 15A 32V Wire Strap from Enclos...

Страница 4: ...b For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 4 marked 1P 1N through 4P 4N Fig 2a 2b pg 5 or 1 to 8 marked 1P 1N through 8P 8N Fig 3a 3b pg 5 carefully ob...

Страница 5: ...ULCB PD8UL PD8ULCB 1P to 4P 1P to 8P Positive DC power outputs 1N to 4N 1N to 8N Negative DC power outputs Power Distribution Module s INPUT LED PD4UL POWER DISTRIBUTING UNIT ALTRONIX CORP BROOKLYN NY...

Страница 6: ...35o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 3...

Страница 7: ...________________ A G Alarm duration Hours 15 Min 0 25 Hour Alarm __________________ H H Battery capacity required for Alarm E F G __________________ AH I Total calculated battery capacity D H ________...

Страница 8: ...31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38 1mm 1 5 38 1mm 4 615...