AL1024ULX Series
- 3 -
Stand-by Specifications
(total current shown)
:
Output
15 min. of Stand-by
and 5 min. of Alarm
4 hr. of Stand-by
and 5 min. of Alarm
24 hr. of Stand-by
and 5 min. of Alarm
60 hr. of Stand-by
and 5 min. of Alarm
24VDC/12AH
Battery
Stand-By = 8A
Alarm = 10A
Stand-By = 1.5A
Alarm = 10A
Stand-By = 200mA
Alarm = 10A
Stand-By = 100mA
Alarm = 10A
Output
15 min. of Stand-by
and 5 min. of Alarm
4 hr. of Stand-by and
5 min. of Alarm
24 hr. of Stand-by
and 15 min. of Alarm
60 hr. of Stand-by
and 15 min. of Alarm
24VDC/65AH
Battery
–
Stand-By = 8.0A
Alarm = 10A
Stand-By = 1.5A
Alarm = 10A
Stand-By = 500mA
Alarm = 10A
For Access Control applications, battery capacity for 10A supply current - 1 hr. for 24VDC/12AH battery,
6.5 hrs. for 24VDC/65AH battery.
See battery size calculation worksheet for other batteries (Page 7).
+ DC
---
– BA
T
+
BAT FAIL NC C NO NC C NO AC FAIL
DC
AC
L
G
N
5A 25
0V
15
AC DELAY
15
A
32
V
Wire Strap
(from
Enclosure
to Door)
115VAC
power mains
non power-limited
Divider
CAUTION: De-energize unit prior to servicing. For continued protection
against risk of electric shock and fire hazard replace fuses with the same type
and rating. Do not expose to rain or moisture.
INPUT
1
2
Power
Distribution
Module(s)
Battery and AC
Supervision Circuit
(power limited).
non power-limited
Battery Connections
non power-limited
Class 1
Earth Ground
Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing.
CAUTION: Optional rechargeable stand-by batteries must match
the power supply output voltage setting.
Optional Rechargeable
Stand-by Battery
Optional Rechargeable
Stand-by Battery
Fig. 1