background image

 

- 4 - 

AL1024ULX Series

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with 
all local codes and authorities having jurisdiction. Product is intended for indoor use only. 
1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes 
  in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place 
  the enclosure’s upper keyholes over the two upper screws; level and secure. Mark the position of the lower 
  two holes. Remove the enclosure. Drill the lower holes and install three fasteners. Place the enclosure’s 
  upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws 
  (Enclosure Dimensions, pg. 8). Secure enclosure to earth ground. 
2. Connect AC power (115VAC / 60 Hz) to the terminals marked [L, N] (Fig. 1, pg. 3). Use 14 AWG or larger 
  for all power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power-limited circuits 
  (AC Fail/Low Battery reporting). 
  Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, 
  Battery Wires). Minimum 0.25” spacing must be provided.
  CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing 
  equipment. There are no user serviceable parts inside. Refer installation and servicing to qualified 
  service personnel.
  For Fire Alarm applications the outputs are “Special Applications” only, see list (refer to Appendix A, pg. 6)
3.  Measure output voltage before connecting device. This helps avoiding potential damage. 
  When servicing the unit AC mains should be removed.
4. Connect devices to be powered:
  a.  For AL1024ULX Power Supply: connect devices to the terminals marked [+ DC –] (Fig. 1, pg. 3) 
  b. For other Power Distribution Models: connect devices to be powered to terminal pairs 1 to 4 marked  
    [1P & 1N] through [4P & 4N] (Fig. 2a & 2b, pg. 5) or 1 to 8 marked [1P & 1N] through [8P & 8N]
  (Fig. 3a & 3b, pg. 5), carefully observing correct polarity.
5.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in
  the loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.
6. Connect appropriate signaling notification devices to the terminals marked [AC FAIL & BAT FAIL] 
  (Fig. 1, pg. 3) supervisory relay outputs.
 

Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay must be used 

  to  provide a visual indication of AC power on.
7. Please ensure that the cover is secured with the provided Key Lock.

Wiring:

Use 14 AWG or larger for all power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper 
voltage level.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage 
both at the battery terminal and at the board terminals marked [– BAT +] to ensure that there is no break in the 
battery connection wires.
Note: Maximum charging current under discharges is 3.6A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

AL1024ULXB2 - Power Supply Board

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery is supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

PD4UL/PD4ULCB/PD8UL/PD8ULCB - Power Distribution Module

Green (AC)

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Содержание AL1024ULX

Страница 1: ...24ULXPD4 Four 4 Fuse Protected Outputs AL1024ULXPD8 Eight 8 Fuse Protected Outputs AL1024ULXPD16 Sixteen 16 Fuse Protected Outputs AL1024ULXPD4CB Four 4 PTC Protected Outputs AL1024ULXPD8CB Eight 8 PT...

Страница 2: ...ice AL1024ULXPD4CB PD4ULCB 4 P P 2 5 AL1024ULXPD8 PD8UL 8 P 3 5 AL1024ULXPD8CB PD8ULCB 8 P P 2 5 AL1024ULXPD16 Two 2 PD8UL 16 P 3 5 AL1024ULXPD16CB Two 2 PD8ULCB 16 P P 2 5 Do not exceed total output...

Страница 3: ...6 5 hrs for 24VDC 65AH battery See battery size calculation worksheet for other batteries Page 7 DC BAT BAT FAIL NC C NO NC C NO AC FAIL DC AC L G N 5A 250V 15 AC DELAY 15A 32V Wire Strap from Enclos...

Страница 4: ...b For other Power Distribution Models connect devices to be powered to terminal pairs 1 to 4 marked 1P 1N through 4P 4N Fig 2a 2b pg 5 or 1 to 8 marked 1P 1N through 8P 8N Fig 3a 3b pg 5 carefully ob...

Страница 5: ...ULCB PD8UL PD8ULCB 1P to 4P 1P to 8P Positive DC power outputs 1N to 4N 1N to 8N Negative DC power outputs Power Distribution Module s INPUT LED PD4UL POWER DISTRIBUTING UNIT ALTRONIX CORP BROOKLYN NY...

Страница 6: ...35o Thermal Supervisory Relay 15 45 2312 24TB Photoelectric 0 12 50 2412 12 volt Photoelectric 0 12 77 2424 Photoelectric 0 10 41 2451 Photoelectric 0 10 39 2451TH with B402B Base Photoelectric 0 10 3...

Страница 7: ...________________ A G Alarm duration Hours 15 Min 0 25 Hour Alarm __________________ H H Battery capacity required for Alarm E F G __________________ AH I Total calculated battery capacity D H ________...

Страница 8: ...31 75mm 1 1 27 94mm 1 1 27 94mm 0 79 20 06mm 1 1 27 94mm 0 91 23 114mm 0 91 23 114mm 1 375 34 925mm 1 125 28 575mm 15 5 393 7mm 4 615 117 22mm 12 23 310 64mm 4 615 117 22mm 1 5 38 1mm 1 5 38 1mm 4 615...

Отзывы: