AL1012ULX Series 

- 3 - 

4.  Connect devices to be powered:
 

a.  For Power Supply Board: connect to the terminals marked [+ DC -] (Fig. 1, pg. 5). 

 

b.  For Power Distribution Module(s): connect devices to be powered to the terminal pairs 1 to 4 marked  

 

 

[1P & 1N] through [4P & 4N] (Fig. 2, pg. 6) or 1 to 8 marked [1P & 1N] through [8P & 8N] (Fig. 3, pg. 6), 

 

 

carefully observing correct polarity.

5.  For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the
 

loss of output voltage. When the use of stand-by batteries is desired, they must be lead acid or gel type.

6.  Connect appropriate signaling notification devices to the terminals marked [AC FAIL & BAT FAIL] (Fig. 1, pg. 5) 
 

supervisory relay outputs.

 

Note: When used in fire alarm, burglar alarm or access control applications, “AC Fail” relay must be used to 

 

provide a visual indication of AC power on.

Wiring:

Use 14 AWG or larger for all power connections.
Note: Take care to keep power-limited circuits separate from non power-limited wiring (115VAC, Battery).

Maintenance:

Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test: Under normal load conditions the DC output voltage should be checked for proper voltage level.
Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage both at the 
battery terminal and at the board terminals marked [+ BAT --- ] to ensure that there is no break in the battery connection wires.
Note: Maximum charging current under discharges is 0.7A.
Note: Expected battery life is 5 years; however, it is recommended changing batteries in 4 years or less if needed.

LED Diagnostics:

AL1012ULXB - Power Supply Board

Red (DC)

Green (AC)

Power Supply Status

ON

ON

Normal operating condition.

ON

OFF

Loss of AC. Stand-by battery supplying power.

OFF

ON

No DC output.

OFF

OFF

Loss of AC. Discharged or no stand-by battery. No DC output.

PD4/PD4CB/PD8/PD8CB - Power Distribution Module

Green

Power Distribution Module Status

ON

Normal operating condition.

OFF

No Power Output.

Содержание AL1012ULX

Страница 1: ...de Models Include AL1012ULX Single Output AL1012ULXPD4 AL1012ULXPD4CB Four 4 Fused Outputs Four 4 PTC Outputs AL1012ULXPD8 AL1012ULXPD8CB Eight 8 Fused Outputs Eight 8 PTC Outputs AL1012ULXPD16 AL1012...

Страница 2: ...steners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two upper screws level and secure Mark the position of the lower two holes Remove the enclo...

Страница 3: ...e Take care to keep power limited circuits separate from non power limited wiring 115VAC Battery Maintenance Unit should be tested at least once a year for the proper operation as follows Output Volta...

Страница 4: ...he Power Supply Board AC trouble output delay option If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds BAT FAIL NO C NC Indicates low battery con...

Страница 5: ...ed Door Wire Strap from Enclosure to Door 115 power mains non power limited Divider CAUTION De energize unit prior to servicing Class 1 Battery and AC Supervision Circuit power limited Use separate kn...

Страница 6: ...2N 3P 3N 4P 4N DC Output to devices From Power Supply Board Factory Installed Used on PTC Models PD8 N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 1 ALTRONIX CORP MADE IN USA BROOKLYN N...

Страница 7: ...AL1012ULX Series 7 Notes...

Страница 8: ...imensions BC400 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm...

Отзывы: