- 2 -  

AL1012ULX Series

Overview:

The AL1012ULX is a power supply that converts a 115VAC / 60Hz input to a 12VDC output (see specifications).
The AL1012ULX is a base unit for a series of UL Listed multi-output power supply/chargers including: AL1012ULXPD4, 
AL1012ULXPD4CB, AL1012ULXPD8, AL1012ULXPD8CB, AL1012ULXPD16, AL1012ULXPD16CB (Refer to 
AL1012ULX Series Power Supply Configuration Reference Chart below).

AL1012ULX Series Power Supply Configuration Reference Chart:

Altronix

Model Number

Accessory

Power Distribution 

Module(s)

Number of  Output(s)

Class 2 

Rated

Power- 

Limited 

Output(s)

Fused Outputs

PTC Outputs  (auto-resettable)

Output Rating  (A) per Output

Power Supply  Ouitput Fuse  Rating

Agency Listings

UL Listings

and 

File Numbers

AL1012ULX

-----

1

-----

-----

-----

10

15A/32V

UL 294

(File # BP6714)

 UL Listed for Access 

Control Systems.

“Signal Equipment” 

Evaluated to 

CSA Standard C22.2 

No.205-M1983

AL1012ULXPD4

PD4UL

4

-----

P

-----

3.5

15A/32V

AL1012ULXPD4CB

PD4ULCB

4

P

-----

P

2.5

15A/32V

AL1012ULXPD8

PD8UL

8

-----

P

-----

3.5

15A/32V

AL1012ULXPD8CB

PD8ULCB

8

P

-----

P

2.5

15A/32V

AL1012ULXPD16

Two (2) PD8UL

16

-----

P

-----

3.5

15A/32V

AL1012ULXPD16CB

Two (2) PD8ULCB

16

P

-----

P

2.5

15A/32V

Stand-by: 15 minutes of Stand-by at 10A.

Specifications:

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local 
codes and authorities having jurisdiction. Product is intended for indoor use only. 
1.  Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
 

enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure’s

 

upper keyholes over the two upper screws; level and secure. Mark the position of the lower two holes. Remove the

 

enclosure. Drill the lower holes and install two fasteners. Place the enclosure’s upper keyholes over the two

 

upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 8).

 

Secure enclosure to earth ground. 

2.  Connect AC power (115VAC / 60 Hz) to the terminals marked [L, N] (Fig. 1, pg. 5). Use 14 AWG or larger for all
 

power connections (Battery, DC output, AC input). Use 22 AWG to 18 AWG for power-limited circuits (AC Fail/

 

Low Battery reporting).

 

Note: Keep power-limited wiring separate from non power-limited wiring (115VAC / 60Hz Input, 

 

Battery Wires). Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or servicing equipment. 

 

There are no user serviceable parts inside. Refer installation and servicing to qualified service personnel.

3.  Mea sure output voltage before connecting device. This helps avoiding potential damage. 

Input:

•  Input 115VAC / 60Hz, 2.6A.
•  Input fuse rated @ 5A/250V.

Output:

•  12VDC output. 
•  10A total supply current at 12VDC. 
•  Filtered and electronically regulated outputs.
•  Short circuit and thermal overload protection.

Battery Backup:

•  Maximum charge current 0.7A.
•  Built-in charger for sealed lead acid or gel type batteries.

Battery Backup 

(cont’d)

:

•  Automatic switch over to stand-by battery when 
  AC fails.
•  Zero voltage drop when switched over to 
  battery backup.

Supervision:

•  AC fail supervision (form “C” contacts). 
•  Battery presence and low battery supervision 
  (form “C” contacts).

LED Indicators:

•  AC input, DC output and BAT trouble LED indicators. 

LISTED

Содержание AL1012ULX

Страница 1: ...de Models Include AL1012ULX Single Output AL1012ULXPD4 AL1012ULXPD4CB Four 4 Fused Outputs Four 4 PTC Outputs AL1012ULXPD8 AL1012ULXPD8CB Eight 8 Fused Outputs Eight 8 PTC Outputs AL1012ULXPD16 AL1012...

Страница 2: ...steners and screws in the wall with the screw heads protruding Place the enclosure s upper keyholes over the two upper screws level and secure Mark the position of the lower two holes Remove the enclo...

Страница 3: ...e Take care to keep power limited circuits separate from non power limited wiring 115VAC Battery Maintenance Unit should be tested at least once a year for the proper operation as follows Output Volta...

Страница 4: ...he Power Supply Board AC trouble output delay option If this mode is selected the Power Supply Board must be reset by removing all power to it for 30 seconds BAT FAIL NO C NC Indicates low battery con...

Страница 5: ...ed Door Wire Strap from Enclosure to Door 115 power mains non power limited Divider CAUTION De energize unit prior to servicing Class 1 Battery and AC Supervision Circuit power limited Use separate kn...

Страница 6: ...2N 3P 3N 4P 4N DC Output to devices From Power Supply Board Factory Installed Used on PTC Models PD8 N COMMON POWER OUTPUTS P FUSED POWER OUTPUTS 1 2 3 4 5 6 7 8 1 ALTRONIX CORP MADE IN USA BROOKLYN N...

Страница 7: ...AL1012ULX Series 7 Notes...

Страница 8: ...imensions BC400 15 5 x 12 x 4 5 393 7mm x 304 8mm x 114 3mm 1 5 38 1mm 1 5 38 1mm 1 5 38 1mm 5 0 127 0mm 5 0 127 0mm 1 5 38 1mm 2 0 50 8mm 2 0 50 8mm 1 75 44 45mm 1 75 44 45mm 4 5 114 3mm 1 25 31 75mm...

Отзывы: