- 4 -
AL1012ULX Series
Terminal Identification:
AL1012ULXB - Power Supply Board
Terminal Legend Function/Description
L, N
Connect 115VAC to these terminals: L to Hot, N to Neutral. Do not use the [G] terminal.
--- DC +
12VDC @ 10A continuous non power-limited output.
AC FAIL
NC, C, NO
Indicates loss of AC power, e.g. connect to annuciator/alarm panel. Relay normally energized when
AC power is present. Contact rating 1A @ 30VDC. AC Fail condition will report approximately
one (1) to one minute after loss of AC. To delay report for 6 hours cut jumper J1 on the Power
Supply Board (AC trouble output delay option). If this mode is selected, the Power Supply Board
must be reset by removing all power to it for 30 seconds.
BAT FAIL
NO, C, NC
Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC
power is present. Contact rating 1A @ 30VDC. Low battery conditions will report approximately
10.5VDC. Battery presence detection will report approximately 1 minute after battery remains
undetected (missing or removed).
+ BAT ---
Stand-by battery connections. Maximum charge rate 0.7A.
PD4/PD4CB/PD8/PD8CB - Power Distribution Module
Terminal Legend
Function/Description
PD4/PD4CB
PD8/PD8CB
1P to 4P
1P to 8P
Positive DC power outputs.
1N to 4N
1N to 8N
Negative DC power outputs.