- 4 - 

ACMJ Series

4.  Measure voltage before connecting devices. This helps avoiding potential damage.
5. 

Output options (Fig. 1, pg. 6):

 

The unit will provide either eight (8) switched power outputs, eight (8) dry form “C” outputs, or any

 

combination of both switched power and form “C” outputs, plus eight (8) unswitched auxiliary power outputs.

 

(a)  Switched Power outputs: 

 

  Connect the negative (–) input of the device being powered to the terminal marked [COM].

 

  For Fail-Safe operation connect the positive (+) input of the device being powered to the terminal 

 

  marked [NC]. 

 

  For Fail-Secure operation connect the positive (+) input of the device being powered to the terminal 

 

  marked [NO].

 

(b) Form “C” outputs:

 

    When form “C” outputs are desired the corresponding output fuse (1-8) must be removed. 

 

    Connect negative (–) of the power supply directly to the locking device. Connect the positive (+) of the 

 

    power supply to the terminal marked [C]. For Fail-Safe operation connect the positive (+) of the device 

 

    being powered to the terminal marked NC]. For Fail-Secure operation connect the positive (+) of the 

 

    device being powered to the terminal marked [NO].

 

(c)  Auxiliary Power outputs (unswitched):

 

    Connect positive (+) input of the device being powered to the terminal marked [C] and the negative (–) 

 

    of the device being powered to the terminal marked [COM]. Output can be used to provide power for 

 

    card readers, keypads, etc.

6. 

Input trigger options (Fig. 1, pg. 6):

 

(a)  Normally Open [NO] input trigger:

 

    Inputs 1-8 are activated by normally open or open collector sink inputs.

 

    Connect devices (card readers, keypads, request to exit buttons etc.) to terminals marked [IN] and [GND]. 

 

(b) Open Collector Sink inputs:

 

    Connect the access control panel open collector sink positive (+) to the terminal marked [IN] and the 

 

    negative (–) to the terminal marked [GND].

7. 

Fire Alarm Interface options (Figs. 4 through 8, pg. 8)

 

A normally closed [NC], normally open [NO] input or polarity reversal input from FACP signaling circuit 

 

will   trigger selected outputs. To enable FACP Disconnect for an output turn the corresponding switch 

 

[SW1-SW8] OFF. To disable FACP disconnect for an output turn the corresponding switch [SW1-SW8] ON.

 

(a)  Normally Open [NO] input:

 

    For non-latching hook-up (Fig. 5, pg. 8). For latching hook-up see Fig. 6, pg. 9.

 

(b) Normally Closed [NC] input:

 

    For non-latching hook-up (Fig. 7, pg. 9). For latching hook-up see Fig. 8, pg. 9.

 

(c)  FACP Signaling Circuit input trigger:

 

    Connect the positive (+) and negative (–) from the FACP signaling circuit output to the terminals marked 

 

    [+ INP –]. Connect the FACP EOL to the terminals marked [+ RET –] (polarity is referenced in an alarm 

 

    condition). Jumper located next to TRG LED must be cut (Fig. 1a, pg. 6)

8. 

FACP Dry form “C” output (Fig. 1a, pg. 6):

 

Connect desired device to be triggered by the unit’s dry contact output to the terminals marked [NO] and [C] 

 

FACP for normally open output or the terminals marked [NC] and [C] FACP for normally closed output.

9. 

Battery Connections (Fig. 2, pg. 7):

 

For Access Control applications batteries are optional. If batteries are not used, a loss of AC will result in 

 

the loss of output voltage. Batteries must be lead acid or gel type. 

 

Connect one (1) 12VDC battery to the terminals marked [+ BAT –] for 12VDC operation. 

 

Use two (2) 12VDC batteries wired in series for 24VDC operation. 

10. 

Battery and AC Supervision output (Fig. 2, pg. 7):

 

It is required to connect supervisory trouble reporting devices to outputs marked [AC Fail, BAT FAIL] 

 

supervisory relay outputs marked [NC, C, NO] to appropriate notification devices. Use 22 AWG to 18 AWG 

 

for AC Fail & Low/No Battery reporting. Cut “AC delay” jumper to delay report for 6 hours.

 Note: A tamper switch must be installed and connected to the appropriate notification device to report a
 

trouble condition when the enclosure door is open. 

11. 

Multiple power supply inputs (Fig. 1, pg. 6):

 

When using two (2) power supplies jumpers J1 and J2 (located to the left of the power/control terminals) 

 

must be cut (Fig. 1c, pg. 6 & Fig. 3 pg. 8). Connect power for the ACM8 to the terminals marked 

 

[– C] and connect power for the locking devices to the terminals marked [– Power +]. 

 

When using DC power supplies polarity must be observed. 

 

When using AC power supplies polarity need not be observed (Fig. 1d, pg. 6).

 

Note: For UL compliance the additional power supply must be power-limited, UL Listed for Access 

 

Control Systems and accessories.

Содержание ACMJ Series

Страница 1: ...s Access Power Controllers with Power Supplies Installation Guide Models Include AL400ULACMJ 12VDC 4A or 24VDC 3A Fused Outputs AL600ULACMJ 12VDC or 24VDC 6A Fused Outputs AL1012ULACMJ 12VDC 10A Fused...

Страница 2: ...P UL File BP6714 UL 294 UL Listed for Access Control System Units Signal Equipment Evaluated to CSA Standard C22 2 No 205 M1983 AL600ULACMJ 3 5A 5A 250V 0 7A 6A 6A 8 3 5A AL1012ULACMJ 2 6A 5A 250V 15A...

Страница 3: ...nstalling or servicing equipment There are no user serviceable parts inside Refer installation and servicing to qualified service personnel Input Power input 115VAC 60Hz see ACMJ Series Power Supply C...

Страница 4: ...ble FACP disconnect for an output turn the corresponding switch SW1 SW8 ON a Normally Open NO input For non latching hook up Fig 5 pg 8 For latching hook up see Fig 6 pg 9 b Normally Closed NC input F...

Страница 5: ...IL NC C NO Used to indicate low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 28VDC A removed battery is reported within 5 minutes Ba...

Страница 6: ...ectromagnetic Door Holders AC or DC Power Supply optional AC or DC Power Supply req d FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Ke...

Страница 7: ...er limited Unswitched 115VAC power mains non power limited DC Output to devices power limited for AL400ULACMJ non power limited for all other models Fire Alarm Interface Optional Rechargeable Stand by...

Страница 8: ...referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 O...

Страница 9: ...7 Normally Closed Non Latching FACP trigger input Fig 8 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 6 Normally Open FACP Latching trigger input...

Страница 10: ...larm ___________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm ___________ H H Battery capacity required for Alarm E F G ___________ AH I Total calculated battery capacity D H ___________ AH...

Страница 11: ...ACMJ Series 11 Notes...

Страница 12: ...Series E28S MEMBER Enclosure Dimensions 18 x 14 5 x 4 625 457 2mm x 368 3mm x 117 5mm 1 5 38 1mm 1 0 25 4mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 25 31 75mm 1 25 31 75mm 1 0 25 4mm 1 5 38 1mm 1 5 38 1m...

Отзывы: