ACMJ Series 

- 3 -

Specifications:

Installation Instructions:

Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with 
all local codes and authorities having jurisdiction. Product is intended for indoor use only. 
1.  Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in 
 

the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the 

 

enclosure’s upper keyholes over the two upper screws, level and secure. Mark the position of the lower 

 

two holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s 

 

upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all 

 screws 

(Enclosure Dimensions, pg. 12). Secure enclosure to earth ground. 

 

It is recommended to first review the following tables to facilitate installation: 

 

Output Voltage and Stand-by Specifications Charts 

(pg. 2)

 

Typical Application Diagram 

(pg. 6)

 

LED Diagnostics 

(pg. 6)

 

Terminal Identification Tables 

(pg. 5)

 

Hook-up Diagrams 

(pg. 8-9)

2. 

Set output voltage:

 

AL400ULACMJ and AL600ULACMJ: set desired DC output voltage by setting switch SW1 to the 

 

appropriate position on the power supply board. AL1012ULACMJ is factory set at 12VDC and 

 

AL1024ULACMJ is factory set at 24VDC (Output Voltage and Stand-by Specification Chart, pg. 2).

3. 

Connect AC (Fig. 2, pg. 7):

 

Connect unswitched AC power (115VAC 60Hz) to terminals marked [L, N]. Use 14 AWG or larger for all 

 

power connections. Secure green wire lead to earth ground. Green “AC” LED on power supply board will 

 

turn on. This light can be seen through the LED lens on the door of the enclosure. 

 

Keep power-limited wiring separate from non power-limited wiring (115VAC 60Hz Input, 

 

Battery Wires). Minimum 0.25” spacing must be provided.

 

CAUTION: Do not touch exposed metal parts. Shut branch circuit power before installing or 

 

servicing equipment. There are no user serviceable parts inside. 

 

Refer installation and servicing to qualified service personnel.

Input:

•  Power input 115VAC, 60Hz 

 (see 

ACMJ Series Power Supply Configuration 

  Reference Chart, pg. 2).

• 

ACM8 Power Input Options:

  a) One (1) common power input for ACM8 and 

    lock power (factory installed).

  b) Two (2) isolated power inputs 

    (external power supply is required).

    Current is determined by the power supply 

    connected, not to exceed a maximum of 10A total.

•  Eight (8) Access Control System trigger inputs.

  Input options:

  a) Eight (8) normally open (NO) inputs.

  b) Eight (8) open collector inputs.

  c) Any combination of the above.

Outputs: 

•  Eight (8) independently controlled outputs.

  Output Options:

  a) Eight (8) Fail-Safe and/or Fail-Secure 

  power 

outputs.

  b) Eight (8) form “C” 5A rated relay outputs.

  c) Any combination of the above.

•  Eight (8) auxiliary power outputs (unswitched). 

•  ACM8 output fuses are rated 3.5A.

•  ACM8 board main fuse is rated at 10A.

•  Fire Alarm disconnect (latching or non-latching) is 

  individually selectable for any or all of the 

  eight (8) outputs.

•  Fire Alarm disconnect input options:

  a) Normally open (NO) or normally closed (NC) 

    dry contact input.

  b) Polarity reversal input from 

  FACP 

signaling 

circuit.

Outputs 

(cont’d)

•  Alarm output relay indicates that FACP input is 

  triggered (form “C” contact rated @ 1A 28VDC, 

  not evaluated by UL).

•  Filtered and electronically regulated outputs.

•  Thermal and short circuit protection with auto reset. 

Visual Indicators:

•  Green LED indicates when FACP disconnect 

  is triggered.

•  Red LEDs indicate outputs are triggered 

  (relays energized).

•  AC input and DC output LED indicators.

Battery Backup:

•  Built-in charger for sealed lead acid or 

  gel type batteries.

•  Automatic switch over to stand-by battery when 

  AC fails.

•  Zero voltage drop when switching over to 

  battery backup.

Supervision:

•  AC fail supervision (form “C” contact). 

•  Low battery supervision (form “C” contact). 

•  Battery presence supervision (form “C” contact).

•  Power fail supervision relay 

  (form “C” contact rated 1A @ 28VDC).

Enclosure Dimensions:

  18” x 14.5” x 4.625” 
  (457.2mm x 368.3mm x 117.5mm).

  Enclosure accommodates up to 

  two (2) 18AH batteries.

Содержание ACMJ Series

Страница 1: ...s Access Power Controllers with Power Supplies Installation Guide Models Include AL400ULACMJ 12VDC 4A or 24VDC 3A Fused Outputs AL600ULACMJ 12VDC or 24VDC 6A Fused Outputs AL1012ULACMJ 12VDC 10A Fused...

Страница 2: ...P UL File BP6714 UL 294 UL Listed for Access Control System Units Signal Equipment Evaluated to CSA Standard C22 2 No 205 M1983 AL600ULACMJ 3 5A 5A 250V 0 7A 6A 6A 8 3 5A AL1012ULACMJ 2 6A 5A 250V 15A...

Страница 3: ...nstalling or servicing equipment There are no user serviceable parts inside Refer installation and servicing to qualified service personnel Input Power input 115VAC 60Hz see ACMJ Series Power Supply C...

Страница 4: ...ble FACP disconnect for an output turn the corresponding switch SW1 SW8 ON a Normally Open NO input For non latching hook up Fig 5 pg 8 For latching hook up see Fig 6 pg 9 b Normally Closed NC input F...

Страница 5: ...IL NC C NO Used to indicate low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 28VDC A removed battery is reported within 5 minutes Ba...

Страница 6: ...ectromagnetic Door Holders AC or DC Power Supply optional AC or DC Power Supply req d FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Ke...

Страница 7: ...er limited Unswitched 115VAC power mains non power limited DC Output to devices power limited for AL400ULACMJ non power limited for all other models Fire Alarm Interface Optional Rechargeable Stand by...

Страница 8: ...referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 O...

Страница 9: ...7 Normally Closed Non Latching FACP trigger input Fig 8 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 6 Normally Open FACP Latching trigger input...

Страница 10: ...larm ___________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm ___________ H H Battery capacity required for Alarm E F G ___________ AH I Total calculated battery capacity D H ___________ AH...

Страница 11: ...ACMJ Series 11 Notes...

Страница 12: ...Series E28S MEMBER Enclosure Dimensions 18 x 14 5 x 4 625 457 2mm x 368 3mm x 117 5mm 1 5 38 1mm 1 0 25 4mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 25 31 75mm 1 25 31 75mm 1 0 25 4mm 1 5 38 1mm 1 5 38 1m...

Отзывы: