Altronix ACMJ Series Скачать руководство пользователя страница 2

 

- 2 - 

ACMJ Series

Overview:

Altronix ACMJ Series units distribute and switch power to access control systems and accessories. They convert 
a 115VAC 60Hz input into eight (8) independently controlled 12VDC or 24VDC fuse protected outputs. These 
power outputs can be converted to dry form “C” contacts. Outputs are activated by an open collector sink or 
normally open (NO) dry trigger input from an Access Control System, Card Reader, Keypad, Push Button, PIR, 
etc. Units will route power to a variety of access control hardware devices including: Mag Locks, Electric Strikes, 
Magnetic Door Holders, etc. Outputs will operate in both Fail-Safe and/or Fail-Secure modes. The FACP Interface 
enables Emergency Egress, Alarm Monitoring, or may be used to trigger other auxiliary devices. The fire alarm 
disconnect feature is individually selectable for any or all of the eight (8) outputs.

ACMJ Series Configuration Reference Chart:

Altronix 
Model Number

115VAC 60Hz Input

(current draw)

Power Supply Board

Input Fuse Rating

Power Supply Board

Battery Fuse Rating

Maximum Battery 

Charge Current

12VDC Total

Output Current

24VDC Total 

Output Current

Fused Outputs

Individual Output 

Rating

Class 2 Rated

Power-Limited

Agency Listings

UL Listings

and

File Numbers

AL400ULACMJ

3.5A

5A/

250V

15A/

32V

0.7A 4A

3A

8

3.5A

P

UL File # BP6714

UL 294*

 UL Listed for 

Access Control 

System Units.

“Signal 

Equipment” 

Evaluated to CSA 

Standard C22.2 
No.205-M1983

AL600ULACMJ

3.5A

5A/

250V

0.7A 6A

6A

8

3.5A

AL1012ULACMJ 2.6A

5A/

250V

15A/

32V

0.7A 10A

8

3.5A

AL1024ULACMJ 4.2A

5A/

250V

15A/

32V

3.6A

10A

8

3.5A

LISTED

Altronix Corp.

140 58th St. Brooklyn, NY

California 

State Fire 

Marshal

NYC 

Dept. of 

Buildings

Altronix 
Model Number

* ANSI/UL 294 7th Ed.  Access Control Performance Levels

Destructive

Attack

Endurance

Test

Line

Security

Stand-by

Power

AL400ULACMJ

I

IV

I

I

AL600ULACMJ

I

IV

I

I

AL1012ULACMJ

I

IV

I

I

AL1024ULACMJ

I

IV

I

12AH - II, 40AH - III, 65AH - IV

Output Voltage and Stand-by Specification Charts:

AL400ULACMJ

Voltage

Switch Position

Stand-by Battery

4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm

12VDC

SW1 - ON

40AH

3.5A / 3.5A

0.5A / 3.5A

24VDC

SW1 - OFF

40AH

2.75A / 2.75A

0.75A / 2.75A

AL600ULACMJ

Voltage

Switch Position

Stand-by Battery

4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm

12VDC

SW1 - ON

40AH

5.5A / 5.5A

0.5A / 5.5A

24VDC

SW1 - OFF

40AH

5.75A / 5.75A

0.75A / 5.75A

AL1012ULACMJ

Voltage

Switch Position

Stand-by Battery

4 hr. Stand-by / 5 mins. Alarm 24 hr. Stand-by / 5 mins. Alarm

12VDC

N/A

40AH

9.5A / 9.5A

0.5A / 9.5A

AL1024ULACMJ 

(refer to AL1024ULACMJ Battery Size Calculation Worksheet, pg. 10).

Voltage

Stand-by 

Battery

15 mins. Stand-by /

5 mins. Alarm

4 hr. Stand-by /

5 mins. Alarm

24 hr. Stand-by /

5 mins. Alarm

60 hr. Stand-by /

5 mins. Alarm

24VDC

12AH

7.7A / 9.7A

1.2A / 9.7A

24VDC

65AH

7.7A / 9.7A

1.2A / 9.7A

200mA / 9.7A

Содержание ACMJ Series

Страница 1: ...s Access Power Controllers with Power Supplies Installation Guide Models Include AL400ULACMJ 12VDC 4A or 24VDC 3A Fused Outputs AL600ULACMJ 12VDC or 24VDC 6A Fused Outputs AL1012ULACMJ 12VDC 10A Fused...

Страница 2: ...P UL File BP6714 UL 294 UL Listed for Access Control System Units Signal Equipment Evaluated to CSA Standard C22 2 No 205 M1983 AL600ULACMJ 3 5A 5A 250V 0 7A 6A 6A 8 3 5A AL1012ULACMJ 2 6A 5A 250V 15A...

Страница 3: ...nstalling or servicing equipment There are no user serviceable parts inside Refer installation and servicing to qualified service personnel Input Power input 115VAC 60Hz see ACMJ Series Power Supply C...

Страница 4: ...ble FACP disconnect for an output turn the corresponding switch SW1 SW8 ON a Normally Open NO input For non latching hook up Fig 5 pg 8 For latching hook up see Fig 6 pg 9 b Normally Closed NC input F...

Страница 5: ...IL NC C NO Used to indicate low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 28VDC A removed battery is reported within 5 minutes Ba...

Страница 6: ...ectromagnetic Door Holders AC or DC Power Supply optional AC or DC Power Supply req d FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Ke...

Страница 7: ...er limited Unswitched 115VAC power mains non power limited DC Output to devices power limited for AL400ULACMJ non power limited for all other models Fire Alarm Interface Optional Rechargeable Stand by...

Страница 8: ...referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 O...

Страница 9: ...7 Normally Closed Non Latching FACP trigger input Fig 8 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 6 Normally Open FACP Latching trigger input...

Страница 10: ...larm ___________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm ___________ H H Battery capacity required for Alarm E F G ___________ AH I Total calculated battery capacity D H ___________ AH...

Страница 11: ...ACMJ Series 11 Notes...

Страница 12: ...Series E28S MEMBER Enclosure Dimensions 18 x 14 5 x 4 625 457 2mm x 368 3mm x 117 5mm 1 5 38 1mm 1 0 25 4mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 25 31 75mm 1 25 31 75mm 1 0 25 4mm 1 5 38 1mm 1 5 38 1m...

Отзывы: