AL1024ULACMJ Battery Size Calculation Worksheet:

A. AL1024ULACMJ internal current consumption 

(stand-by) 

 __________  0.35A

B. Load current consumption 

(stand-by) 

 __________  A

C. Stand-by time required (Hours) 

 

 __________  H

D. Battery capacity required for stand-by 

(A+B)*C 

 __________  AH

E. AL1024ULACMJ internal power consumption 

(Alarm) 

 __________  0.35A

F. Load current consumption 

(Alarm) 

 __________  A

G. Alarm duration (Hours, example: 15 Min. = 0.25 Hour)  (Alarm) 

 __________  H

H. Battery capacity required for Alarm 

(E+F)*G 

 __________  AH

I.  Total calculated battery capacity 

D+H 

 __________  AH

J.  Battery capacity required 

I*1.8 (safety factor)   __________  AH

Note:  AL1024ULACMJ power supply is designed to work with batteries up to 65AH. Please note, line [I] 
   

must not exceed 36AH. You have to reduce either stand-by current consumption or stand-by time in

   

order to comply with requirement.

To determine actual battery size please round line [J] to the nearest larger standard battery size.

Содержание ACMJ Series

Страница 1: ...s Access Power Controllers with Power Supplies Installation Guide Models Include AL400ULACMJ 12VDC 4A or 24VDC 3A Fused Outputs AL600ULACMJ 12VDC or 24VDC 6A Fused Outputs AL1012ULACMJ 12VDC 10A Fused...

Страница 2: ...P UL File BP6714 UL 294 UL Listed for Access Control System Units Signal Equipment Evaluated to CSA Standard C22 2 No 205 M1983 AL600ULACMJ 3 5A 5A 250V 0 7A 6A 6A 8 3 5A AL1012ULACMJ 2 6A 5A 250V 15A...

Страница 3: ...nstalling or servicing equipment There are no user serviceable parts inside Refer installation and servicing to qualified service personnel Input Power input 115VAC 60Hz see ACMJ Series Power Supply C...

Страница 4: ...ble FACP disconnect for an output turn the corresponding switch SW1 SW8 ON a Normally Open NO input For non latching hook up Fig 5 pg 8 For latching hook up see Fig 6 pg 9 b Normally Closed NC input F...

Страница 5: ...IL NC C NO Used to indicate low battery condition e g connect to alarm panel Relay normally energized when DC power is present Contact rating 1A 28VDC A removed battery is reported within 5 minutes Ba...

Страница 6: ...ectromagnetic Door Holders AC or DC Power Supply optional AC or DC Power Supply req d FACP Fire Alarm Control Panel UL Listed Power Supply For this application corresponding fuse F8 must be removed Ke...

Страница 7: ...er limited Unswitched 115VAC power mains non power limited DC Output to devices power limited for AL400ULACMJ non power limited for all other models Fire Alarm Interface Optional Rechargeable Stand by...

Страница 8: ...referenced in alarm condition Fig 3 Optional hook up using two 2 isolated power supply inputs J2 J1 CUT JUMPERS J1 AND J2 ISOLATED POWER INPUT 12 OR 24 VAC OR VDC LOCK POWER ISOLATED POWER INPUT 12 O...

Страница 9: ...7 Normally Closed Non Latching FACP trigger input Fig 8 Normally Closed Latching FACP trigger input with reset This output has not been evaluated by UL Fig 6 Normally Open FACP Latching trigger input...

Страница 10: ...larm ___________ A G Alarm duration Hours example 15 Min 0 25 Hour Alarm ___________ H H Battery capacity required for Alarm E F G ___________ AH I Total calculated battery capacity D H ___________ AH...

Страница 11: ...ACMJ Series 11 Notes...

Страница 12: ...Series E28S MEMBER Enclosure Dimensions 18 x 14 5 x 4 625 457 2mm x 368 3mm x 117 5mm 1 5 38 1mm 1 0 25 4mm 4 5 114 3mm 1 0 25 4mm 1 0 25 4mm 1 25 31 75mm 1 25 31 75mm 1 0 25 4mm 1 5 38 1mm 1 5 38 1m...

Отзывы: