CD200D II 4-17 All rights reserved © ALTRONIC, LLC 2017

7

9.12  Run Speed Setting:

 

This numeric entry configures the transition speed from crank to run. This set-

ting also determines the transition of the diagnostic LED on the CD200D from 

crank to run modes. Default setting = 500 RPM.

9.13  Low Voltage Setting:

 

This numeric entry configures the threshold for the low voltage diagnostic of 

the DC input voltage to the CD200D. If the DC voltage decreases to this set-

ting, the diagnostic LED on the CD200D will blink the appropriate code. The 

CD200D will continue to try to fire outputs regardless of the voltage. Default 

setting = 6 volts. 

 

9.14  Enable LED Diagnostics Flag:

 

When this LED status flag is activated, the blink code diagnostics for primary 

and secondary outputs are enabled. Default setting is ON.

9.15  Switch CAL:

 

These numeric entries configure the timing retard for each position of the 

manual timing switch on the CD200D case. Entry range is 0 to 25.5 degrees 

of engine retard. The active entry is indicated in blue. Default setting is 7-6-5-

4-3-2-1. If two degrees change per switch position is desired, enter 14-12-10-

8-6-4-2. 

9.16  Loop CAL:

 

These numeric entries configure the interpolated lookup table for the ignition 

retard versus the analog current loop input signal. This allows the operator to 

create custom spark timing maps versus the current loop input signal. Entry 

range is 0 to 25.5 degrees of engine retard. The active entries are indicated 

in blue. Default sequence is 0 degrees retard at 4mA, 16 degrees retard at 

20mA.

9.17  RPM CAL:

 

These numeric entries configure the interpolated lookup table for retard versus 

the engine speed. This allows the operator to create custom spark timing maps 

versus engine rpm. Entry range is 0 to 25.5 degrees of engine retard. The 

active entries are indicated in blue. Default sequence is 6 degrees retard at 0 

RPM, decreasing to 0 degrees retard at 600 RPM.

9.18  Enable Slave Firing Flag:

 

When this LED status flag is activated, the ignition will generate a second 

slave firing for each (x+1) reference pulse. For a (6+1) disc pattern, the igni-

tion will fire 12 outputs when this flag is activated, and 6 outputs when this 

flag is not activated. Modification of this flag through the Terminal Program 

requires that the engine be stopped and the G-lead be grounded.

9.19  SLAVE FIRING ANGLE SETTING:

 

This numeric entry configures the angle of the slave firing relative to the stan-

dard firings that are generated for each (x+1) reference pulse. Entry range is 

25.0° to 60.0° which is used to set the slave firing angle on a 12 or 16-cylin-

der, 4-cycle engine. The slave angle must be the smaller of the two angles that 

define the engine firing pattern. For example, firing patterns of either 30°–60° 

or 60°–30° would require the slave angle be entered as “30”. Modification of 

this value through the Terminal Program requires that the engine be stopped 

and the G1 lead be grounded.

 

Common slave-firing patterns:

NO.

CYLS.

Engine

Firing
Angle

SECT. 9.5

DISC

SETTING

SECT. 9.20

SLAVE
ANGLE

IN FIRING ORDER,

OUTPUT A

CONNECTS TO:

8

60°–120°

4+1

60°

First cylinder

8

120°–60°

4+1

60°

Second cylinder

10

54°–90°

5+1

54°

First cylinder

NOTE: All 16-cylinder applications 
must be slave-firing patterns utilizing 
an 8+1 disc.

Содержание CD200D

Страница 1: ...Installation Instructions CD200D Digital Ignition System Form CD200D II 4 17...

Страница 2: ...set up for a trigger disc running at camshaft speed see SECTION 9 5 The setup is programmable by the use of the PC compatible CD200D terminal program see FIG 9 provided on a CD delivered with the unit...

Страница 3: ...1 0 degree 2 cycle ahead of the most advanced desired timing point on the compression stroke This is the point where the Hall effect pickup must line up with the edge of the magnet next to the x on t...

Страница 4: ...0D can also be shutdown by using the G lead of the output harness To shutdown the unit connect the G lead of the output harness to ground The CD200D will draw about 0 1 ampere from the power source wh...

Страница 5: ...oftware is used on a PC the Communica tions Port settings must be configured in order to establish communications After loading the Terminal Program from the CD ROM click on the Connection icon on the...

Страница 6: ...rn off until rotation stops After rotation stops it will blink the appropriate signal see section 11 2 Default setting OFF 9 7 On Crank Flag When this status flag is ON the ignition scales rpm measure...

Страница 7: ...rees retard at 20mA 9 17 RPM CAL These numeric entries configure the interpolated lookup table for retard versus the engine speed This allows the operator to create custom spark timing maps versus eng...

Страница 8: ...setting is 160 volts at the capacitor This voltage can only be mea sured using a device with an input impedance of 1 megaohm or higher with no other device connected 10 0 PC TERMINAL DISPLAY FUNCTIONS...

Страница 9: ...s the measured DC voltage supply level to the CD200D 10 14 Spark Ref A B C etc Indicates the current spark reference number for each cylinder 10 15 Syncing When red indicates that engine rotation has...

Страница 10: ...egard the first blink when first connecting 10 32 ChkSum When red indicates a software checksum failure of the unit s firmware 10 33 Low Volt When red indicates that the input DC voltage is at or belo...

Страница 11: ...ds between each blink sequence and the blinks occur evenly spaced at a faster rate 11 2 LED SIGNALS WITH THE ENGINE STOPPED ON Steady READY new power up or last start attempt aborted ON 1 Blink ON FIR...

Страница 12: ...2 InSync1 10003 InSync2 10004 Purging 10005 Trying 10006 Firing 10007 LockOut 10008 FIRED 10009 Cranking 10010 Running 10011 Wrong Disk 10012 GLead Shutdown Grounded 10013 Remote Shutdown Present 1001...

Страница 13: ...Cycle Counter HI 30016 Cycle Counter LO 30017 Supply Voltage xx xVolts 30018 Spark Ref Num Output A 30019 Spark Ref Num Output B 30020 Spark Ref Num Output C 30021 Spark Ref Num Output D 30022 Spark R...

Страница 14: ...REGARDING APPLICATION ADDRESS FUNCTION 40005 Disk 1 2 3 4 5 6 7 8 9 10 12 40006 Disk Lineup to TDC xx x DEG 40007 Insertion Ret MIN 2 0 DEG xx x 40008 Purge Delay Cycles 0 255 40009 RPM Over Speed Set...

Страница 15: ...ING SWITCH POS 7 DEG 12 9 21 READ WRITE REGISTERS FOR LOOP RET TABLE ADDRESS FUNCTION 40049 LOOP RET MAP 0mA 0 00V DEG 40050 LOOP RET MAP 1mA 0 25V DEG 40051 LOOP RET MAP 2mA 0 50V DEG 40052 LOOP RET...

Страница 16: ...T MAP 1400 RPM DEG 40085 RPM RET MAP 1500 RPM DEG 40086 RPM RET MAP 1600 RPM DEG 40087 RPM RET MAP 1700 RPM DEG 40088 RPM RET MAP 1800 RPM DEG 40089 RPM RET MAP 1900 RPM DEG 40090 RPM RET MAP 2000 RPM...

Страница 17: ...85 224 8 7 73 196 3 7 12 180 0 6 25 158 8 14 PIN 19 PIN OPERATING TEMPERATURE 40 C TO 85 C STORAGE TEMPERATURE 40 C TO 105 C INPUT VOLTAGE 12 TO 30 VDC OUTPUT VOLTAGE 160 VDC NOM 14 PIN CONNECTOR CONN...

Страница 18: ...UNIT 12VDC UNIT FORMULA GENERAL BY NUMBER OF SYSTEMS FOR MULTIPLE SYSTEMS MULTIPLY REQUIREMENTS 1 INFORMATION IS PER ONE 1 CD200D SYSTEM NOTE POWER SUPPLY SPECS 25 AMP PEAK PULSES 5 AMP CONTINUOUS D C...

Страница 19: ...CD200D II 4 17 All rights reserved ALTRONIC LLC 2017 19 FIGURE 3 CD200D MAGNETIC PICKUP AND DISC HOLE DETAIL...

Страница 20: ...CD200D II 4 17 All rights reserved ALTRONIC LLC 2017 20 FIGURE 4 CD200D PICKUP AND DISC INSTALLATION...

Страница 21: ...21 FIGURE 5 CD200D WIRING DIAGRAM TEMPLATE FOR SINGLE FIRING SYSTEM WITH MAGNETIC PICKUP A GND 791090 IGNITION PRIMARY PIN CYLINDER ANGLE 8 12 16 B C D E F K L M N P R S T U V J 2 1 3 1 4 1 5 1 6 1 7...

Страница 22: ...2 FIGURE 6 CD200D WIRING DIAGRAM TEMPLATE FOR SINGLE FIRING SYSTEM WITH HALL EFFECT PICKUP A GND 791090 IGNITION PRIMARY PIN CYLINDER ANGLE 8 12 16 B C D E F K L M N P R S T U V J 2 1 3 1 4 1 5 1 6 1...

Страница 23: ...CD200D II 4 17 All rights reserved ALTRONIC LLC 2017 23 FIGURE 7 CD200D HOOK UP FOR ANALOG TIMING SIGNAL...

Страница 24: ...CD200D II 4 17 All rights reserved ALTRONIC LLC 2017 24 FIGURE 8 PC TO CD200D...

Страница 25: ...CD200D II 4 17 All rights reserved ALTRONIC LLC 2017 25 FIGURE 9 CD200D TERMINAL PROGRAM SCREEN VERSION 1 0 5 0 NOTE This CD200D TERMINAL PROGRAM is compatible with CD200D Unit 791090 x...

Страница 26: ...CD200D II 4 17 All rights reserved ALTRONIC LLC 2017 26 FIGURE 10 CD200D TERMINAL PROGRAM SCREEN VERSION 5 1 ONWARD NOTE This CD200D TERMINAL PROGRAM is compatible with CD200D Unit 791090 x...

Страница 27: ...4 17 All rights reserved ALTRONIC LLC 2017 27 FIGURE 11 CD200D Remote Control TERMINAL PROGRAM SCREEN VERSION 1 0 ONWARD NOTE This CD200D Remote Control TERMINAL PROGRAM is compatible with CD200D Unit...

Страница 28: ...Energy RAM ONLY Default Energy section 9 20 2 is pre loaded to this RMT Energy on initializa tion and on engine stop There are four RMT Energy settings for CD200D Unit 791090 xR Energy 0 Vcap 150 volt...

Страница 29: ...BIT 1 in Standard CD200D 791090 x is replaced by READ WRITE functionality of RMT Energy Selection in CD200D Unit 791090 xR Remote Control TABLE 12 11 12 5 4 READ WRITE REGISTERS MIRROR COIL BITS ADDRE...

Страница 30: ...DEG 40045 LOOP RET MAP 1mA 0 25V DEG 40046 LOOP RET MAP 2mA 0 50V DEG 40047 LOOP RET MAP 3mA 0 75V DEG 40048 LOOP RET MAP 4mA 1 00V DEG 40049 LOOP RET MAP 5mA 1 25V DEG 40050 LOOP RET MAP 6mA 1 50V D...

Страница 31: ...5 RPM RET MAP 1000 RPM DEG 40076 RPM RET MAP 1100 RPM DEG 40077 RPM RET MAP 1200 RPM DEG 40078 RPM RET MAP 1300 RPM DEG 40079 RPM RET MAP 1400 RPM DEG 40080 RPM RET MAP 1500 RPM DEG 40081 RPM RET MAP...

Страница 32: ...et Deg RAM 40108 OUTPUT F 06 Indv Ret Deg RAM 40109 OUTPUT K 07 Indv Ret Deg RAM 40110 OUTPUT L 08 Indv Ret Deg RAM 40111 OUTPUT M 09 Indv Ret Deg RAM 40112 OUTPUT N 10 Indv Ret Deg RAM 40113 OUTPUT P...

Отзывы: