Installation manual
15
EKHBH/X016AB
Indoor unit for air to water heat pump system
4PW42457-1
Domestic hot water tank installation configuration
Initial start-up at low outdoor ambient temperatures
Unit without optional backup heater
Unit with optional backup heater
During initial start-up and when water temperature is low, it is
important that the water is heated gradually. Failure to do so may
result in cracking of concrete floors due to rapid temperature change.
Please contact the responsible cast concrete building contractor for
further details.
To do so, the lowest leaving water set temperature can be decreased
to a value between 15°C and 25°C by adjusting the field setting
[9-01] (heating set point lower limit). Refer to
Pre-operation checks
Checks before initial start-up
After the installation of the unit, check the following before switching
on the circuit breaker:
1
Field wiring
Make sure that the field wiring between local supply panel and
indoor unit, outdoor unit and indoor unit, indoor unit and valves
(when applicable), indoor unit and room thermostat (when
applicable), and indoor unit and domestic hot water tank has
been carried out according to the instructions described in the
chapter
diagrams and according to European and national regulations.
2
Fuses or protection devices
Check that the fuses or the locally installed protection devices
are of the size and type specified in the chapter
. Make sure that neither a fuse nor a
protection device has been bypassed.
3
Booster heater circuit breaker F2B
Do not forget to turn on the booster heater circuit breaker F2B in
the switch box (applies only to units with optional domestic hot
water tank installed).
4
Earth wiring
Make sure that the earth wires have been connected properly
and that the earth terminals are tightened.
5
Internal wiring
Visually check the switch box on loose connections or damaged
electrical components.
6
Fixation
Check that the unit is properly fixed, to avoid abnormal noises
and vibrations when starting up the unit.
7
Damaged equipment
Check the inside of the unit on damaged components or
squeezed pipes.
8
Refrigerant leak
Check the inside of the unit on refrigerant leakage. If there is a
refrigerant leak, call your local dealer.
9
Power supply voltage
Check the power supply voltage on the local supply panel. The
voltage must correspond to the voltage on the identification label
of the unit.
10
Air purge valve
Make sure the air purge valve is open (at least 2 turns).
11
Pressure relief valve
Check if the backup heater vessel is completely filled with water
by operating the pressure relief valve. It should purge water
instead of air (applies only to units with optional backup heater
installed).
12
Shut-off valves
Make sure that the shut-off valves are correctly installed and
fully open.
Powering up the indoor unit
When power supply to the indoor unit is turned on, "
88
" is displayed
on the user interface during its initialisation, which might take up to
30 seconds. During this process the user interface cannot be
operated.
■
When no domestic hot water tank is
installed, toggle switch SS2-2 should be set to
OFF (default).
■
When a domestic hot water tank is installed,
toggle switch SS2-2 should be set to ON.
NOTE
To ensure that the unit operates within its operation
range as soon as possible (water temperature
≥
30°C),
the load during start-up must be reduced as much as
possible.
For example:
You can do this by switching off the fans of the fan
coil units until the water temperature has
increased to 30°C.
OR
For floor heating applications: start up circuit by
circuit using a (automatic) by-pass valve
guaranteeing that water returning to the unit is
more than 20°C.
NOTE
Heating between 15°C and 25°C is performed by the
backup heater only. This feature is not available on
units without a backup heater.
Switch off the power supply before making any
connections.
4
3
2
1
ON
OFF
4
3
2
1
ON
OFF
Operating the system with the backup heater vessel not
completely filled with water will damage the backup heater!
Operating the system with closed valves will damage the
pump!