Installation manual
11
EKHBH/X016AB
Indoor unit for air to water heat pump system
4PW42457-1
Charging water
1
Connect the water supply to a drain and fill valve (see
).
2
Make sure the automatic air purge valve is open (at least 2
turns).
3
Fill with water until the manometer indicates a pressure of
approximately 2.0 bar. Remove air in the circuit as much as
possible using the air purge valves. Air present in the water
circuit might cause malfunctioning of the optional backup heater.
4
For units with optional backup heater:
Check that the backup heater vessel is filled with water by
opening the pressure relief valve. Water must flow out of the
valve.
Piping insulation
The complete water circuit, inclusive all piping, must be insulated to
prevent condensation during cooling operation and reduction of the
cooling and heating capacity.
If the temperature is higher than 30°C and the humidity is higher than
RH 80%, then the thickness of the sealing materials should be at
least 20 mm in order to avoid condensation on the surface of the
sealing.
Field wiring
Overview
The illustration below gives an overview of the required field wiring
between several parts of the installation. Refer also to
application examples" on page 3
NOTE
■
During filling, it might not be possible to remove all
air in the system. Remaining air will be removed
through the automatic air purge valves during first
operating hours of the system. Additional filling
with water afterwards might be required.
■
The water pressure indicated on the manometer
will vary depending on the water temperature
(higher pressure at higher water temperature).
However, at all times water pressure should
remain above 0.3 bar to avoid air entering the
circuit.
■
The unit might dispose some excessive water
through the pressure relief valve.
■
Water quality must be according to EN directive
98/83 EC.
WARNING
■
A main switch or other means for disconnection,
having a contact separation in all poles, must be
incorporated in the fixed wiring in accordance with
relevant local and national legislation.
■
Switch off the power supply before making any
connections.
■
All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.
■
The field wiring must be carried out in accordance
with the wiring diagram supplied with the unit and the
instructions given below.
■
Be sure to use a dedicated power supply. Never use a
power supply shared by another appliance.
■
Be sure to establish an earth. Do not earth the unit to
a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
■
Be sure to install an earth leakage protector (30 mA).
Failure to do so may cause electrical shock.
A
Single power supply for
outdoor unit, backup
heater and booster
heater (optional)
F
3-way valve for domestic
hot water tank (field
supply, optional)
G
2-way valve for cooling
mode (field supply,
optional)
B
Outdoor unit
C
Backup heater
H
Domestic hot water tank
(optional)
D
Indoor unit
E
Room thermostat (field
supply, optional)
I
Booster heater
(optional)
Item
Description
Required
number of
conductors
Maximum
running current
1
Power supply cable for outdoor
unit
2+GND
(a)
(a) Refer to nameplate on outdoor unit
2
Indoor unit power supply and
communication cable
3+GND
(b)
(b) Cable section 2.5 mm
2
3
Power supply cable for backup
heater
2+GND or
3+GND
(c)
(c) See table under
"Connection of the backup heater power supply" on page 12
4
Room thermostat cable
3 or 4
100 mA
(d)
(d) Minimum cable section 0.75 mm
2
5
3-way valve control cable
2+GND
6
2-way valve control cable
2+GND
7
Booster heater power supply
and thermal protection cable
4+GND
8
Thermistor cable
2
(e)
(e) The thermistor and connection wire (12 m) are delivered with the domestic hot
water tank.
9
Booster heater power supply
cable
2+GND
13 A
T
M
M
2
B
1
3
4
C
5
6
7
8
D
A
9
E
H
I
G
F