Boiler Installation
BOILER LOCATION
Wood & Coal Burning Boilers are designed to
radiate heat freely, but this heat can be dangerous if
the boiler is improperly installed.
e Wood Gun™ is
designed and certi ed only for indoor installations
and therefore must be protected from the elements
by being located in a totally enclosed shelter.
e
Wood Gun™ must not be installed anywhere that
gasoline, or other Gammable vapors are present.
Unless special preparations are made to partition o:
an area for the boiler and to prevent Gammable
vapors from entering the boiler area, a garage is not
an approved location for a Wood Gun
TM
installation.
Check local building codes for restrictions on
installation.
e boiler must stand on a noncombustible
material such as brick, stone tile or concrete. NEVER
place a boiler directly on a wood Goor.
e
noncombustible material upon which the boiler
stands should extend at least 12 inches beyond the
base of the boiler in the rear and on the sides and at
least 36 inches in front.
e boiler must be installed
in an area dedicated to the boiler and its related
equipment.
is area must be partitioned or
separated from any living area of a residence.
e
room must have a constant fresh air supply to assure
proper combustion of the fuel as well as ventilation
of any by-products of combustion.
Boiler Room Requirements
1.
e room should be well-lit and should have
a source of emergency light.
2. A convenient water supply should be
available for boiler Gushing and to clean the
boiler room Goor.
3. Unobstructed Goor drains.
4. A boiler must not be installed where there is
the possibility of the accumulation of
explosive vapors.
1. Must have adequate air supply, which must
be kept clear at all times. Since the
combustion process requires a supply of air at
all times, it is essential that provisions are
made to supply adequate air to the boiler
room.
is air supply is necessary to insure
complete combustion and venting of any
gases or smoke that would be emi7ed from
this solid fuel-burning boiler in case boiler
malfunctions. If fans are used in the boiler
room or in the fuel storage room it is
important they are installed in such a way
that there is not a negative pressure in the
room where the boiler is located.
2. Provide an electrical disconnect at point of
entrance to boiler room.
3. Walls and ceiling must be of re rated
construction. Consult local or state codes for
requirements.
4. It is recommended to have at least one week
worth of fuel inside and kept out of the
weather. Do not store fuel within the
appliance installation clearances or within the
space required for fueling, ash removal, and
other routine maintenance operations.
- 5 -
A fire could be started if the boiler
is installed too close to walls,
carpet or draperies.
Содержание wood gun E100 SF
Страница 2: ......
Страница 24: ...Photo Smoke flap installed 19 ...
Страница 46: ...Steel Center Brick 8 Inch 41 ...
Страница 49: ...Appendix A Boiler Specification Diagram 44 ...
Страница 50: ... 45 ...
Страница 51: ... 46 ...
Страница 53: ...Appendix B Wiring Diagrams 48 ...
Страница 54: ... 49 ...
Страница 55: ... 50 ...
Страница 56: ... 51 ...
Страница 57: ... 52 ...
Страница 58: ... 53 ...
Страница 59: ... 54 ...
Страница 60: ... 55 ...
Страница 61: ...Appendix C Exploded Parts Drawings 56 ...
Страница 63: ... 58 ...
Страница 68: ...Appendix F Boiler Piping and Ducting Examples 63 ...
Страница 69: ...Wood Gun Air Inlet Ducting Installations 64 ...