Boiler Installation
BOILER LOCATION
Coal Boilers radiate heat from multiple surfaces.
/is heat can be dangerous if the boiler is improperly
installed. /e boiler must stand on a noncombustible
material such as brick, stone tile or concrete. NEVER
place a boiler directly on a wood @oor. /e
noncombustible material upon which the boiler
stands should extend at least 12 inches beyond the
base of the boiler in the rear and on the sides and at
least 36 inches in front. /e boiler must be installed
in an area dedicated to the boiler and its related
equipment. /is area must be partitioned or
separated from any living area of a residence. /e
room must have a constant fresh air supply to assure
proper combustion of the fuel as well as ventilation
of any by-products of combustion.
A building fire could be started if the
boiler is installed too close to walls,
furniture, carpet or draperies.
Boiler Room Requirements
✔
Must have adequate lighting, and should
include a source of emergency light.
✔
A convenient water supply should be
available for boiler @ushing and to clean the
boiler room @oor.
✔
Unobstructed @oor drains should be available.
✔
Must not be installed where there is the
possibility of the accumulation of explosive
vapors.
✔
Must have adequate air supply, which must
be kept clear and unobstructed at all times.
Since the combustion process requires a
continuous supply of air, it is essential that
provisions are made to supply adequate air to
the boiler room. /is air supply is necessary
to insure complete combustion and venting of
any gases or smoke that would be emi ed
from this solid fuel-burning boiler in case the
boiler malfunctions.
Ventilation Fans in the boiler room
must not create negaive pressure.
Doing so will create an unsafe
condition and negatively impact
boiler performance.
✔
Electrical disconnect at point of entrance to
boiler room.
✔
Walls and ceiling must be of 1re-rated
construction. Consult local or state codes for
requirements.
✔
Use a Carbon Monoxide detector to monitor
CO levels. Include one in the boiler room and
at knee level within living areas in the home
as well.
RIGGING AND POSITIONING
OF BOILER
Do not a empt to move or oD-load the boiler
without the aid of a crane or dolly. All Alternate
Heating Systems boilers have at least one liEing lug
in the center of the top. On some units liEing lugs in
the front and rear are provided. Use caution
whenever moving a boiler. When choosing the
equipment to move and/or position the boiler,
always be sure of the load rating on the equipment
prior to use.
- 2 -
Содержание COAL GUN S130
Страница 2: ......
Страница 4: ......
Страница 34: ...Appendix A Boiler Specification Diagrams 28 ...
Страница 35: ... 29 ...
Страница 37: ...Appendix B Wiring Diagrams 31 ...
Страница 38: ... 32 ...
Страница 39: ... 33 ...
Страница 40: ...Appendix C Exploded Parts Drawing 34 ...
Страница 51: ...Appendix E Troubleshooting Guide 45 ...
Страница 54: ...Appendix F Table of Figures 48 ...
Страница 57: ...Appendix H Dump Zone Wiring Applications 51 ...
Страница 58: ... 52 ...
Страница 59: ... 53 ...
Страница 60: ... 54 ...
Страница 61: ... 55 ...
Страница 62: ... 56 ...
Страница 63: ...Appendix I Boiler Piping Examples 57 ...