ALTEC

Technical Data

While temperature sensor connection breakdown 

VR

 is displayed, or while overrange 

SNB

 is displayed.

At this time, relay output are determined by 

PF1

 as shown in the parameter list.

6.5 Sensor Failure

WWW.ALTEC.CC

Sample rate

Measurement range

Resolution

Temperature sensor

Relay contact rating

Control algorithm

Power supply

Environmental

-50~150  °C

1  °C

NTC,  PVC  Wire,  2.0m

5(8)A/250VAC

125ms

ON/OFF

220V AC, 

2.0W

Temp:  -20~55  °C

,

Rel.  Humidity

:

85%

Dimensions

W78

H35

D78mm

×

×

SPK

Mnemonic

Setpoint high limit

Parameter

-50~150 °C

Adjustable Range

to limit 

L1

's adjustable range

Parameter

 

Description

3

SN

SPL

-50~150 °C

4

0~10

 

minutes

Compressor protection

6

RT1

Min. off time for relay

Setpoint low limit

1~25 °C

to limit 

KY1

's adjustable range

5

KYS

Hysteresis range

PF1

Sensor failure output

ON
0FF

Relay 'ON' while sensor failure
Relay 'OFF' while sensor failure

7

1

L  1

Setpoint

SPK

~

SPL

2

KY 1

Hysteresis

1~

KYS

Operation parameter

Switch off the controller; press keys ▲ and ▼ and hold on, switch the controller on 

again.  Parameter  SPK  appears  on  display.  Parameter  selection  and  the  display  of 

the value is obtained by pressing key S repeatedly; change with keys ▲ and ▼ and 

store with S.

6.4 Parameter List

6.3 Output Action

1) T2 > L1, relay RL1 will be ON, start the air conditioner to cool;

2) T2 < L1, relay RL2 will be ON, start the aeration fan to cool.

In order to avoid compressor switch off and on frequently, must set the minimum off 

time 

RT1 

between the switch OFF and switch ON, regardless of the input value.

The controller performs ON/OFF control algorithm, setpoint is 

L1

, hysteresis is 

KY1

.

When the indoor temperature T1 is greater than the setting temperature(i.e. setpoint) 

L1, the controller act due according to the following rules: