P54x/EN AP/La4
Application Notes
(AP) 6-38
MiCOM P543, P544, P545 & P546
AP
2.8
Earth fault (ground overcurrent) and sensitive earth fault (SEF) protection
Caution: The IEEE C.37.112 standard for IDMT curves permits some
freedom to manufacturers at which time dial (TD) value the
reference curve applies. Rather than pick a mid-range value, for
the MiCOM P54x the reference curve norm applies at a time dial
of 1. The time dial is merely a multiplier on the reference curve,
in order to achieve the desired tripping time. Take care when
grading with other suppliers' relays which may take TD = 5,
or TD = 7 as a mid-range value to define the IDMT curve. The
equivalent MiCOM P54x setting to match those relays is achieved
by dividing the imported setting by 5 or 7.
2.8.1
Directional earth fault protection
2.8.1.1 Residual voltage polarization
It is possible that small levels of residual voltage will be present under normal system
conditions due to system imbalances, VT inaccuracies, relay tolerances etc. Hence, the
relay includes a user settable threshold (
N>VNPol Set) which must be exceeded in order for
the DEF function to be operational. In practice, the typical zero sequence voltage on a
healthy system can be as high as 1% (i.e.: 3% residual), and the VT error could be 1% per
phase. A setting between 1% and 4% is typical. The residual voltage measurement
provided in the
Measurements
column of the menu may assist in determining the required
threshold setting during commissioning, as this will indicate the level of standing residual
voltage present.
2.8.2
General setting guidelines for directional earth fault (ground overcurrent) protection
When setting the relay characteristic angle (RCA) for the directional earth fault element, a
positive angle setting was specified. This was due to the fact that the quadrature polarizing
voltage lagged the nominal phase current by 90°; i.e. the position of the current under fault
conditions was leading he polarizing voltage and hence a positive RCA was required. With
directional earth fault DEF, the residual current under fault conditions lies at an angle lagging
the polarizing voltage. Hence, negative RCA settings are required for DEF applications.
This is set in cell 'I>N’ in the relevant earth fault menu.
The following angle settings are recommended for a residual voltage polarized relay:-
Distribution systems (solidly earthed)
-45°
Transmissions systems (solidly earthed)
-60°
For negative sequence polarization, the RCA settings must be based on the angle of the
upstream negative phase sequence source impedance.
2.8.3
Sensitive earth fault protection element (SEF)
SEF would normally be fed from a core balance current transformer (CBCT) mounted around
the three phases of the feeder cable. However, care must be taken in the positioning of the
CT with respect to the earthing of the cable sheath. See Figure 10 below.
Содержание MiCOM P54 Series
Страница 2: ......
Страница 4: ......
Страница 5: ...Safety Section P54x EN SS H11 SS SAFETY SECTION...
Страница 6: ...P54x EN SS H11 Safety Section SS...
Страница 8: ...P54x EN SS H11 Safety Section SS 2 SS...
Страница 16: ...P54x EN IT La4 Introduction MiCOM P543 P544 P545 P546 IT...
Страница 18: ...P54x EN IT La4 Introduction IT 1 2 MiCOM P543 P544 P545 P546 IT...
Страница 28: ...P54x EN IT La4 Introduction IT 1 12 MiCOM P543 P544 P545 P546 IT...
Страница 30: ...P54x EN TD La4 Technical Data MiCOM P543 P544 P545 P546 TD...
Страница 58: ...P54x EN GS La4 Getting Started MiCOM P543 P544 P545 P546 GS...
Страница 78: ...P54x EN ST La4 Settings MiCOM P543 P544 P545 P546 ST...
Страница 172: ...P54x EN ST La4 Settings ST 4 94 MiCOM P543 P544 P545 P546 ST...
Страница 174: ...P54x EN OP La4 Operation MiCOM P543 P544 P545 P546 OP...
Страница 362: ...P54x EN OP La4 Operation OP 5 188 MiCOM P543 P544 P545 P546 OP Figure 118 Auto relose timing diagram leader follower 1ph...
Страница 432: ...P54x EN OP B94 Operation OP 5 260 MiCOM P543 P544 P545 P546 OP Figure 61 CB2 synch check signals...
Страница 442: ...P54x EN OP B94 Operation OP 5 270 MiCOM P543 P544 P545 P546 OP...
Страница 444: ...P54x EN AP La4 Application Notes MiCOM P543 P544 P545 P546 AP...
Страница 534: ...P54x EN PL La4 Programmable Logic MiCOM P543 P544 P545 P546 PL...
Страница 538: ...P54x EN PL La4 Programmable Logic PL 7 4 MiCOM P543 P544 P545 P546 PL...
Страница 602: ...P54x EN PL La4 Programmable Logic PL 7 68 MiCOM P543 P544 P545 P546 Output Contacts PL...
Страница 603: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 69 Output Contacts PL...
Страница 606: ...P54x EN PL La4 Programmable Logic PL 7 72 MiCOM P543 P544 P545 P546 PL...
Страница 616: ...P54x EN PL La4 Programmable Logic PL 7 82 MiCOM P543 P544 P545 P546 Output Contacts PL...
Страница 619: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 85 PL...
Страница 620: ...P54x EN PL La4 Programmable Logic PL 7 86 MiCOM P543 P544 P545 P546 PL...
Страница 621: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 87 PL...
Страница 624: ...P54x EN PL La4 Programmable Logic PL 7 90 MiCOM P543 P544 P545 P546 PL...
Страница 629: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 95 Output Contacts PL...
Страница 630: ...P54x EN PL La4 Programmable Logic PL 7 96 MiCOM P543 P544 P545 P546 PL...
Страница 631: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 97 PL...
Страница 633: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 99 PL...
Страница 637: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 103 PL...
Страница 641: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 107 Output Contacts PL...
Страница 642: ...P54x EN PL La4 Programmable Logic PL 7 108 MiCOM P543 P544 P545 P546 Output Contacts PL...
Страница 643: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 109 LEDs PL...
Страница 644: ...P54x EN PL La4 Programmable Logic PL 7 110 MiCOM P543 P544 P545 P546 PL...
Страница 645: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 111 PL...
Страница 647: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 113 PL...
Страница 653: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 119 Output Contacts PL...
Страница 655: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 121 Output Contacts PL...
Страница 656: ...P54x EN PL La4 Programmable Logic PL 7 122 MiCOM P543 P544 P545 P546 LEDs PL...
Страница 663: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 129 PL...
Страница 667: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 133 Output Contacts PL...
Страница 669: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 135 Output Contacts PL...
Страница 671: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 137 PL...
Страница 672: ...P54x EN PL La4 Programmable Logic PL 7 138 MiCOM P543 P544 P545 P546 PL...
Страница 676: ...P54x EN PL La4 Programmable Logic PL 7 142 MiCOM P543 P544 P545 P546 PL...
Страница 681: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 147 Output Contacts PL...
Страница 688: ...P54x EN PL La4 Programmable Logic PL 7 154 MiCOM P543 P544 P545 P546 PL...
Страница 689: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 155 PL...
Страница 690: ...P54x EN PL La4 Programmable Logic PL 7 156 MiCOM P543 P544 P545 P546 PL...
Страница 696: ...P54x EN PL La4 Programmable Logic PL 7 162 MiCOM P543 P544 P545 P546 Output Contacts PL...
Страница 698: ...P54x EN PL La4 Programmable Logic PL 7 164 MiCOM P543 P544 P545 P546 PL...
Страница 701: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 167 PL...
Страница 703: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 169 PL...
Страница 704: ...P54x EN PL La4 Programmable Logic PL 7 170 MiCOM P543 P544 P545 P546 PL...
Страница 705: ...Programmable Logic P54x EN PL La4 MiCOM P543 P544 P545 P546 PL 7 171 PL...
Страница 706: ...P54x EN PL La4 Programmable Logic PL 7 172 MiCOM P543 P544 P545 P546 LEDs PL...
Страница 708: ...P54x EN MR La4 Measurements and Recording MiCOM P543 P544 P545 P546 MR...
Страница 710: ...P54x EN MR La4 Measurements and Recording MR 8 2 MiCOM P543 P544 P545 P546 MR...
Страница 726: ...P54x EN FD La4 Firmware Design MiCOM P543 P544 P545 P546 FD...
Страница 748: ...P54x EN CM La4 Commissioning MiCOM P543 P544 P545 P546 CM...
Страница 754: ...P54x EN CM La4 Commissioning CM 10 6 MiCOM P543 P544 P545 P546 CM...
Страница 832: ...P54x EN CM La4 Commissioning CM 10 84 MiCOM P543 P544 P545 P546 CM Commissioning Engineer Customer Witness Date Date...
Страница 874: ...P54x EN MT La4 Maintenance MiCOM P543 P544 P545 P546 MT MT...
Страница 876: ...P54x EN MT La4 Maintenance MT 11 2 MiCOM P543 P544 P545 P546 MT...
Страница 882: ...P54x EN TS La4 Troubleshooting MiCOM P543 P544 P545 P546 TS...
Страница 884: ...P54x EN TS La4 Troubleshooting TS 12 2 MiCOM P543 P544 P545 P546 TS...
Страница 894: ...P54x EN SC La4 SCADA Communications MiCOM P543 P544 P545 P546 SC...
Страница 928: ...P54x EN SG La4 Symbols and Glossary MiCOM P543 P544 P545 P546 SG...
Страница 938: ...P54x EN SG La4 Symbols and Glossary SG 14 10 MiCOM P543 P544 P545 P546 SG...
Страница 940: ...P54x EN IN La4 Installation MiCOM P543 P544 P545 P546 IN...
Страница 947: ...Installation P54x EN IN La4 MiCOM P543 P544 P545 P546 IN 15 7 IN P0147ENd Figure 2 Rack mounting of panel mount relays...
Страница 957: ...Installation P54x EN IN La4 MiCOM P543 P544 P545 P546 IN 15 17 IN 10P54400_1 Figure 10 P544 external connection diagram...
Страница 966: ...P54x EN IN La4 Installation IN 15 26 MiCOM P543 P544 P545 P546 IN Figure 19 P546 external connection diagram...
Страница 973: ...Installation P54x EN IN La4 MiCOM P543 P544 P545 P546 IN 15 33 IN Figure 26 P546 Final assembly drawing...
Страница 974: ...P54x EN IN La4 Installation IN 15 34 MiCOM P543 P544 P545 P546 IN...
Страница 976: ...P54x EN VH La4 Firmware and Service Manual Version History MiCOM P543 P544 P545 P546 VH...
Страница 1023: ......